Notes | General: FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21) At least a basic level of insulation is maintained against adjacent modules in the DIN rail direction. If the application has higher requirements on the insulation (reinforced insulation), then these must be realized through suitable measures (e.g. partition plates). The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. |
Product properties | Product type: Relay Module Product family: RIFLINEcomplete Application: high inrush currents Operating mode: 100% operating factor Mechanical service life: 3x 107 cycles Insulation characteristics Insulation: Safe isolation, reinforced insulation Insulation characteristics: Standards/regulations Insulation: Safe isolation, reinforced insulation Overvoltage category: III Pollution degree: 2 |
Electrical properties | Maximum power dissipation for nominal condition: 0.43 W Test voltage (Winding/contact): 4 kV AC (50Hz, 1min., winding/contact) Standards/regulations Rated surge voltage: 6 kV |
Input data | Coil side Nominal input voltage UN: 24 VDC Input voltage range: 19.2 VDC ... 33.6 VDC (20°C) Input voltage range in reference to UN: see diagram Drive and function: monostable Drive (polarity): polarized Typical input current at UN: 18 mA Typical response time: 8 ms Typical release time: 10 ms Coil voltage: 24 VDC Protective circuit: Reverse polarity protection; Polarity protection diode Surge protection; Freewheeling diode Operating voltage display: Yellow LED |
Output data | Switching Contact switching type: 1 N/O contact Type of switch contact: Single contact Note regarding the switch contact: With tungsten leading contact Contact material: AgSnO Maximum switching voltage: 250 V AC/DC Minimum switching voltage: 12 V (100 mA) Limiting continuous current: 6 A 10 A (Value is permissible if connections 11 and 21, as well as connections 14 and 24 are bridged.) Maximum inrush current: 165 A (20ms) 800 A (200 µs) Min. switching current: 100 mA (12VDC) Interrupting rating (ohmic load) max.: 264 W (at 24VDC, observe contact derating) 58 W (at 48 V DC) 48 W (at 60 V DC) 50 W (at 110 V DC) 80 W (at 220 V DC) 2750 VA (at 250VAC, observe contact derating) Switching capacity min.: 1200 mW Utilization category CB Scheme (IEC 60947-5-1): AC15, 6 A/250 V (N/O contact) DC13, 2 A/24 V (N/O contact) |
Connection data | Connection method: Screw connection Stripping length: 8 mm Conductor cross section rigid: 0.5 mm² ... 4 mm² Conductor cross-section rigid (2 conductors with same cross section): 0.5 mm² ... 2.5 mm² Conductor cross section flexible: 0.5 mm² ... 4 mm² 0.5 mm² ... 4 mm² (Ferrule with plastic sleeve) Conductor cross section flexible (2 conductors with same cross section): 0.5 mm² ... 2.5 mm² 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) Conductor cross section AWG: 20 ... 10 (solid) 20 ... 12 (flexible) Tightening torque: 0.5 Nm ... 0.6 Nm |
Dimensions | Width: 16 mm Height: 90 mm Depth: 75 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection (Relay): RT II (Relay) Degree of protection (Relay base): IP20 (Relay base) Degree of protection (Installation location): ⥠IP54 (Installation location) Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m |
Approvals | Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group EN60068-2-60 |
Standards and regulations | Standards/regulations Standards/regulations: IEC 60947-5-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: in rows with zero spacing Mounting position: any |
ECLASS | ECLASS-11.0: 27371601 ECLASS-12.0: 27371601 ECLASS-13.0: 27371601 |
ETIM | ETIM 9.0: EC001437 |
UNSPSC | UNSPSC 21.0: 39122300 |