Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1079241
PHOENIX CONTACT 1079241
PHOENIX CONTACTAvailable

AXL SE PSDI8/3 - Safety module

Axioline SmartElements, Digital input module, Functional safety, PROFIsafe, only for connection to Phoenix Contact or Siemens controller, Safe digital inputs: 4 (2-channel assignment), 8 (1-channel assignment), 24 VDC, connection technology: 3-conductor, degree of protection: IP20
Product Code: 1079241
Partner cod.: 1079241
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
DimensionsDimensional drawing: https://caas.production.phoenixcontact.coremedia.cloud/caas/v1/stable/media/22530/full/b250?format=jpg
Width: 14.9 mm
Height: 62.2 mm
Depth: 62 mm
InterfacesSmartElement interface
Number of interfaces: 1
Connection method: Card edge connector
Transmission speed: See system in which you use the SmartElement.
System propertiesModule
Input address area: 6 Byte (PROFIsafe2.6.1)
Output address area: 5 Byte (PROFIsafe2.6.1)
Required configuration data: 6 Byte
Input dataDigital
Input name: Safe digital inputs
Description of the input: EN 61131-2, type 3
Number of inputs: 4 (2-channel assignment)
8 (1-channel assignment)
Cable length: max. 200 m (200 m from the clock output to the safe input (total based on forward and return path))
Connection method: Push-in connection
Connection technology: 3-conductor
Input voltage range "0" signal: -3 VDC ... 5 VDC
Input voltage range "1" signal: 11 VDC ... 30 VDC
Nominal input voltage UIN: 24 VDC
Nominal input current at UIN: typ. 2.7 mA
Input filter time: 1.5 ms
3 ms (Default)
5 ms
15 ms
Protective circuit: Polarity reversal protection of the inputs; Diode
Product propertiesType: modular
Product type: I/O component
Product family: Axioline SmartElements
Mounting position: any
Application: Functional safety
PROFIsafe
only for connection to Phoenix Contact or Siemens controller
Operating mode: PROFIsafe 2.4, PROFIsafe 2.6.1
Insulation characteristics
Overvoltage category: II (IEC 60664-1)
Pollution degree: 2 (EN60664-1)
Electrical propertiesTransmission medium: Copper
Potentials
Protection: external fusing via the system in which the SmartElement is used
Protective circuit: Surge protection of the supply voltage; electronic (35 V, 0.5 s)
Polarity reversal protection of the supply voltage; via the system in which the SmartElement is used
Potentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC (via bus base module)
Current draw: max. 140 mA (at UBus 5VDC)
typ. 101 mA (at UBus 5VDC)
Potentials: Communications power supply of the Smart Elements (U
Supply voltage: using card edge connectors
Potentials: I/O supply (U
Supply voltage: 24 VDC (using card edge connectors)
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 12 mA (Power supply from Up with 30VDC, all inputs set, without power supply to the sensors via clock supplies OUT_T1 and OUT_T2)
typ. 9 mA (Power supply from Up with 24VDC, all inputs set, without power supply to the sensors via clock supplies OUT_T1 and OUT_T2)
Current consumption: min. 8 mA (Power supply from Up with 19.2VDC, all inputs set, without power supply to the sensors via clock supplies OUT_T1 and OUT_T2)
Power consumption: max. 360 mW
min. 154 mW
Connection dataConnection technology
Connection name: I/O
Note on the connection method: Note the specification in the section Conductor cross sections, and stripping and insertion lengths.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.25 mm² ... 1.5 mm²
Conductor cross section flexible: 0.25 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
I/O
Connection method: Push-in connection
Note on the connection method: Note the specification in the section Conductor cross sections, and stripping and insertion lengths.
Conductor cross section, rigid: 0.25 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.25 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C
Degree of protection: IP20
Degree of protection at installation location: min. IP54
Air pressure (operation): 70 kPa ... 108 kPa
Air pressure (storage/transport): 66 kPa ... 108 kPa
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
Air clearances and creepage distances
Air clearances and creepage distances: IEC 60664-1
MountingMounting type: Smart Element slot
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27242604
ECLASS-12.0: 27242604
ECLASS-13.0: 27242604
ETIMETIM 9.0: EC001599
UNSPSCUNSPSC 21.0: 32151600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00111.pdf

Application_note_00183.pdf

Approvals_00833.pdf

Approvals_01465.pdf

Approvals_01798.pdf

Approvals_01799.pdf

Approvals_01938.pdf

Approvals_01945.pdf

Approvals_01952.pdf

Approvals_01953.pdf

Certification_00182.pdf

Manual_00046.pdf

Manual_00045.pdf

Manufacturer_declaration_01310.pdf

Manufacturer_declaration_02313.pdf

Manufacturer_declaration_06222.pdf

Package_slip_00778.pdf

Quick_start_guide_00007.pdf

Technical_drawing_07742.pdf