AXL SE IOL4 - Communication module

Axioline SmartElements, IO-Link master, IO-Link ports Class A: 4, connection method: Push-in connection, connection technology: 3-conductor, degree of protection: IP20
Product Code: 1088132
Partner cod.: 1088132
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
DimensionsDimensional drawing: https://caas.production.phoenixcontact.coremedia.cloud/caas/v1/stable/media/22530/full/b250?format=jpg
Width: 14.9 mm
Height: 62.2 mm
Depth: 62 mm
InterfacesSmartÂElement interface
Number of interfaces: 1
Connection method: Card edge connector
Transmission speed: See system in which you use the SmartÂElement.
Start time until ready to operate: < 500 ms
System propertiesModule
ID code (hex): none
Process data channel: 512 bit
Input address area: 64 Byte
Output address area: 64 Byte
Input dataDigital
Description of the input: IO-Link ports in digital input (DI) mode
Number of inputs: max. 4 (EN 61131-2 type 1)
Connection method: Push-in connection
Connection technology: 3-conductor
Nominal input voltage UIN: 24 VÂDC
Input voltage range "0" signal: -0.3 VÂDC ... 5 VÂDC
Input voltage range "1" signal: 11 VÂDC ... 30 VÂDC
Nominal input current: typ. 2.5 mA
Sensor current per channel: max. 500 mA (from L+/L-)
Input filter time: 1 µs
IO-Link
Number of ports: 4
Connection method: Push-in connection
Connection technology: 3-conductor
Port type: Class A
Output dataDigital
Output description: IO-Link ports in digital output (DO) mode
Connection method: Push-in connection
Connection technology: 2-, 3-conductor
Number of outputs: max. 4
Nominal output voltage: 24 VÂDC
Nominal current per channel: 200 mA
Product propertiesType: modular
Product type: I/O component
Product family: Axioline SmartÂElements
Mounting position: See the system in which the SmartÂElement is used.
Insulation characteristics
Overvoltage category: II (IEC 60664-1, ENÂ60664-1)
Pollution degree: 2 (IEC 60664-1, ENÂ60664-1)
Electrical propertiesSupply: IO-Link
Nominal voltage for I/O supply: 24 VÂDC
Supply voltage range: 18 VÂDC ... 30 VÂDC (including all tolerances, including ripple)
Nominal current for every IO-Link port: 500 mA (at L+/L-)
200 mA (at C/Q)
Protective circuit: Overload protection for L+; electronically limited to 0.6ÂA
Short-circuit protection for L+; by switching off after 55Âms
Potentials: Communications power supply of the Smart Elements (U
Supply voltage: using card edge connectors
Potentials: I/O supply (U
Supply voltage: 24 VÂDC (using card edge connectors)
Supply voltage range: 19.2 VÂDC ... 30 VÂDC (including all tolerances, including ripple)
Current draw: max. 2030 mA (Internal current consumption + full load of the 4 IO-Link ports (4 x 500ÂmA))
typ. 2020 mA
Current consumption: min. 18 mA (without connected peripherals)
Power consumption: max. 61 W (of which 1.45ÂW internal losses)
min. 432 mW
Protective circuit: Surge protection; See the system in which the SmartÂElement is used.
Reverse polarity protection; Polarity protection diode
Electrical isolation/isolation of the voltage ranges
Test voltage: Communications supply / 24 V supply (I/O): 500 VÂAC, 50 Hz, 1 min.
Test voltage: Communications supply / functional ground: 500 VÂAC, 50 Hz, 1 min.
Test voltage: 24ÂV supply (I/O) / functional ground: 500 VÂAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: I/O
Note on the connection method: Please observe the information provided on conductor cross sections in the âہ“AxiolineÂSmartÂElements” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.25 mm² ... 1.5 mm²
Conductor cross section flexible: 0.25 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm²
Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm²
Stripping length: 8 mm
I/O
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the âہ“AxiolineÂSmartÂElements” user manual.
Conductor cross section, rigid: 0.25 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.25 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm²
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Âm above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Âm above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, ENÂ61140, VDEÂ0140-1)
MountingMounting type: Smart Element slot
Mounting position: See the system in which the SmartÂElement is used.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00139.pdf

Approvals_01798.pdf

Approvals_01799.pdf

Data_sheet_00561.pdf

Manual_00006.pdf

Manual_00007.pdf

Manual_00045.pdf

Manufacturer_declaration_01281.pdf

Manufacturer_declaration_02463.pdf

Manufacturer_declaration_04371.pdf

Manufacturer_declaration_06300.pdf

Quick_start_guide_00004.pdf

Technical_drawing_08045.pdf