Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1104982
PHOENIX CONTACTNot available

PSR-M-EF6-SDOR4-SC - Extension module

Safe extension module with 4safe relay outputs, 4reset inputs, TBUS interface, up to SIL3, Cat.4/PLe, pluggable screw terminal block, TBUS connector included
Product Code: 1104982
Partner cod.: 1104982
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Safety device
Application: Safe shutdown
Insulation characteristics
Protection class: III
Times
Response time: see user manual
Restart time: min. 5 s (Boot time)
max. 10 s (Boot time)
Electrical propertiesMaximum power dissipation for nominal condition: 7.07 W
Nominal operating mode: 100% operating factor
Interfaces: DIN rail TBUS for connection to the master module, supplied as standard
Air clearances and creepage distances
Rated insulation voltage: 250 VAC
Rated surge voltage/insulation: Basic insulation 4 kV between all current paths and housing
Supply
Designation: A1/A2
Rated control circuit supply voltage US: 19.2 VDC ... 28.8 VDC
24 VDC -20%/+20% (external fuse, typically 4A)
Rated control supply current IS: typ. 120 mA
Power consumption at US: typ. 2.88 W
Inrush current: 2 A (Δt=1ms at Us)
Filter time: typ. 5 ms (at A1 in the event of voltage dips at Us)
Protective circuit: Serial protection against polarity reversal
Input dataDigital: Reset inputs (FBK1, FBK2, FBK3, FBK4)
Description of the input: IEC 61131-2 type 3
Number of inputs: 4
Input voltage range "0" signal: 0 VDC ... 5 VDC
Input voltage range "1" signal: 11 VDC ... 28.8 VDC
Input current range "0" signal: < 1 mA
Filter time: 250 ms ±2ms (Test pulse rate>500ms)
Cable length: max. 100 m (per input)
Max. permissible overall conductor resistance: 1.2 kΩ (Input and reset circuit at US)
Current consumption: typ. 10 mA (typically with US)
max. 13 mA (at a control voltage of 28.8VDC)
Output dataRelay: Enabling current paths (13_NO1/14_NO1,23_NO2/24_NO2,33_NO3/34_NO3,43_NO4/44_NO4)
Output description: safety-related N/O contacts
Number of outputs: 4 (1 NO per output)
Contact switching type: 4 safe outputs
Switching voltage: min. 10 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Switching capacity: min. 200 mW
Inrush current: min. 20 mA
max. 6 A
Switching capacity in accordance with IEC 60947-5-1: 3 A (250V (AC15))
2 A (24V (DC13))
Limiting continuous current: 4 A (observe derating)
Sq. Total current: 64 A2 (for 4xsingle-channel,observe derating)
32 A2 (for 2xtwo-channel,observe derating)
Switching frequency: 0.5 Hz
Mechanical service life: 40x 106 switching cycles
Output fuse: 4 A gL/gG
Connection dataConnection technology
pluggable: yes
Conductor connection
Connection method: Screw connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque: 0.5 Nm ... 0.6 Nm
SignalingStatus display: 4xLED (yellow)
4 x LED (green, yellow, red)
1 x LED (green), 2 x LED (orange)
Operating voltage display: 1 x green LED
Error indication: 2xLED (red)
DimensionsWidth: 22.61 mm
Height: 112.58 mm
Depth: 113.6 mm
Material specificationsHousing material: Polyamide PA non-reinforced
CharacteristicsSafety data
Stop category: 0
Safety data: ENISO13849
Performance level (PL): e (2-channel wiring)
c (1-channel wiring)
Safety data: IEC 61508 - High-demand for 2-channel wiring
Safety Integrity Level (SIL): 3
Safety data: IEC 61508 - High-demand for 1-channel wiring
Safety Integrity Level (SIL): 1
Safety data: ENIEC 62061
Safety Integrity Level (SIL): 3 (2-channel wiring)
1 (1-channel wiring)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -10°C ... 55°C (observe derating)
Ambient temperature (storage/transport): -20°C ... 85°C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 95 % (non-condensing)
Max. permissible relative humidity (operation): 95 % (non-condensing)
Shock: 10g for Δt=16ms (continuous shock, 1000 shocks in each space direction)
Vibration (operation): 10Hz...150Hz, amplitude 0.15mm, 2g
ApprovalsCE
Identification: CE-compliant
MountingMounting type: DIN rail mounting
Assembly instructions: Observe derating
Mounting position: vertical or horizontal
Connection method: Screw connection
Technical Specs
ECLASSECLASS-11.0: 27371819
ECLASS-13.0: 27371819
ECLASS-12.0: 27371819
ETIMETIM 9.0: EC001449
UNSPSCUNSPSC 21.0: 39122200
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00901.pdf

Approvals_01328.pdf

Approvals_01329.pdf

Certification_00224.pdf

Certification_00318.pdf

Data_sheet_00644.pdf

Manual_00058.pdf

Manual_00057.pdf

Manufacturer_declaration_01347.pdf

Manufacturer_declaration_02191.pdf

Manufacturer_declaration_05475.pdf