Industrial Automation
Input data | DC operation Nominal input voltage range: 500 VDC ... 1500 VDC Input voltage range: 450 VDC ... 1650 VDC Wide-range input: no Electric strength, max.: ⤠1800 VDC 1 s Typical national grid voltage: 500 VDC 1500 VDC Voltage type of supply voltage: DC Inrush current integral (I2t): typ. 0.15 A2s Current consumption: typ. 85 mA (450 V DC) typ. 30 mA (1500VDC) Recommended breaker for input protection: 2 A (1500VDC) |
Output data | Efficiency: typ. 88 % (500 V DC) typ. 87 % (900VDC) typ. 83 % (1500VDC) Nominal output voltage: 24 VDC ±3% Nominal output current (IN): 1.5 A Derating: > 60°C ... 70°C (2.5%/K) Feedback voltage resistance: ⤠35 VDC Protection against overvoltage at the output (OVP): ⤠30 VDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 0.1 % (change in input voltage ±10 %) Residual ripple: < 40 mVPP (Ripple) < 50 mVPP (Noise) Short-circuit-proof: yes No-load proof: yes Output power: 36 W Maximum no-load power dissipation: < 1.1 W (500VDC) < 1.4 W (900VDC) < 2.4 W (1500VDC) Power loss nominal load max.: < 4.2 W (500VDC) < 5.5 W (900VDC) < 7.5 W (1500VDC) Rise time: ⤠30 ms (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: No |
Connection data | Input Connection method: Push-in connection Conductor cross section, rigid min.: 1 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 1 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 1 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 1 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm² Conductor cross section AWG min.: 18 Conductor cross section AWG max.: 12 Stripping length: 10 mm Output Connection method: Push-in connection Conductor cross section, rigid min.: 1 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 1 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 1 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 1 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm² Conductor cross section AWG min.: 18 Conductor cross section AWG max.: 12 Stripping length: 10 mm |
Signaling | Types of signaling: LED Signal output: LED status indicator Signalization designation: DC OK Status display: "DC OK" LED green Note on status display: UOUT > 21.5 V: LED lights up Color: green DC OK: UOUT > 0.9 x UN (UN = 24VDC) |
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 4.2 kV DC (type test) 2.6 kV DC (routine test) |
Product properties | Product type: DC/DC converters Product family: TRIO POWER MTBF (IEC 61709, SN 29500): > 3300000 h (25°C) > 1760000 h (40°C) > 740000 h (60°C) Insulation characteristics Protection class: II Degree of pollution: 2 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3fd681ea4335214b842689c454daf9d0/-S204x204-FJPG Width: 48 mm Height: 130 mm Depth Device depth (DIN rail mounting): 115 mm (Device depth (DIN rail mounting)) Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 50 mm / 50 mm |
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: horizontally 0 mm (⤠40°C) 10 mm (⤠70°C), vertically 50 mm Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No |
Material specifications | Flammability rating according to UL94 (housing / terminal blocks): V0 Housing material: Plastic Type of housing: Polycarbonate |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K) Ambient temperature (storage/transport): -40°C ... 85°C Maximum altitude: ⤠4000 m (>2000m, Derating: 10%/1000m) Max. permissible relative humidity (operation): ⤠95 % (at 25°C, non-condensing) Shock: 11ms, 15g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and regulations | Standard - Electrical safety: EN62109-1:2011 Standard â Safety extra-low voltage: IEC 62109-1:2011 (SELV) Standard - Safe isolation: DINVDE0100-410 Overvoltage category IEC 62109-1: II |
Approvals | UL approvals: UL62109-1:2014 UL1741 |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Conducted noise emission: EN55016 EN61000-6-4 (Class A) Noise emission: EN55016 EN61000-6-4 (Class A) Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 4 kV (Test Level 2) Discharge in air: 8 kV (Test Level 3) Comments: Criterion A Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2.7 GHz 2.7 GHz ... 6 GHz Test field strength: 10 V/m (> Test intensity 3) 10 V/m (Test Level 2) 3 V/m (Test Level 1) Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 4 kV (Test Level 4 - asymmetrical) Output: 4 kV (Test Level 4 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: 3 kV (Test intensity >4 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 0.5 kV (Test Level 2 - symmetrical) 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Input/Output: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: EN61000-4-11 Emitted interference Standards/regulations: EN61000-6-4 Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassA industrial area of application Emitted radio interference in acc. with EN 55011: EN55011 (EN55022) ClassA industrial area of application Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
ECLASS | ECLASS-11.0: 27040701 ECLASS-12.0: 27040701 ECLASS-13.0: 27040701 |
ETIM | ETIM 9.0: EC002540 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products