Industrial Automation
CAPAROC PM PN - Power module


Notes | General Note: LABS release ââ¬Ã¢ in accordance with test specification VWÃPVÃ3.10.7:2005-0 When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules. |
Product properties | Product type: Device circuit breakers Product family: CAPAROC Number of slots: 4 Insulation characteristics Protection class: III Pollution degree: 2 |
System properties | PROFINET Device function: PROFINET device Specification: PROFINET-IO RT/IRT, Spec. 2.x Conformance Class: Conformance-Class C Redundancy: MRP (Media Redundancy Protocol) |
Electrical properties | General Operating voltage: 10 VÃDC ... 30 VÃDC Rated voltage: 12 VÃDC 24 VÃDC Rated current IN: 45 AÃDC (Total current input) Rated surge voltage: 0.5 kV Tripping method: E (electronic) Feedback resistance: max. 35 VÃDC Dielectric strength: 35 VÃDC (Load circuit) Efficiency: > 99 % Closed circuit current I0: typ. 85 mA (no load at 24ÃV) Power dissipation: typ. 2 W (no load at 24ÃV) < 3.6 W (at 40 A) Temperature derating: 45 A (Total current atÃ35°C) 40 A (Total current atÃ40°C) 15 A (Total current at 50°C) MTBF (IEC 61709, SN 29500): 3985174.15 h (at 25ðC with 21Ã% load) 1760834.9 h (atÃ40°C with 34.25%Ãload) 601892.76 h (at 35ðC with 100Ã% load) Voltage drop: 0.048 V (at 40 A) |
Connection data | Main circuit IN+ Connection method: Push-in connection Stripping length: 18 mm Conductor cross section AWG: 20 ... 8 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.5 mm² ... 16 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.5 mm² ... 16 mm² Main circuit IN- Connection method: Push-in connection Stripping length: 18 mm Conductor cross section AWG: 20 ... 8 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.5 mm² ... 16 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.5 mm² ... 16 mm² System communication Connection method: Push-in connection Stripping length: 8 mm Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 0.75 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 1.5 mm² |
Interfaces | PROFINET Maximum system extension: ââ°¤ 16 (Modules) Interface type: Ethernet Number: 2 Transmission speed: 100 Mbps (acc. to PROFINET standard) Transmission physics: Ethernet in RJ45 twisted pair Protocols supported: PROFINET |
Signaling | Connection X1 LED green: lit (connect) Connection X1 LED yellow: lit (traffic) Connection X2 LED green: lit (connect) Connection X2 LED yellow: lit (traffic) PROFINET bus fault (BF) LED red: lit (connection status not available) flashing (Ãonnection status OK, no communication connection to PROFINET controller) off (active communication connection to PROFINET controller) PROFINET group error (SF) LED red: lit (PROFINET error) off (no PROFINET error) PROFINET ready (RDY) LED green: lit (correct operation) flashing (waiting for application startup) off (operation not correct) Power (PWR) LED green: lit (Supply voltage) Power (PWR) LED red: lit (Supply voltage outside the nominal range) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/4e0dcfd05b91b14ea25261f3a9fe0f0b/-S204x204-FJPG Width: 24.8 mm Height: 132.4 mm Depth: 111.3 mm (incl. DIN rail 7.5Ãmm) |
Material specifications | Material: PA 6 PC Flammability rating according to UL 94: V-0 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -30°C ... 50°C Ambient temperature (storage/transport): -40°C ... 70°C Altitude: ââ°¤ 4000 m (amsl) Humidity test: 96Ãh, 95Ã%ÃRH, 40ðC Shock (operation): 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27) 25g (6Ãms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock) Vibration (operation): 5g (10 ... 150ÃHz / 10Ãcycles / axis / X,ÃY,ÃZ) |
Approvals | UL approval Identification: UL/C-UL Listed UL 508 UL 121201 Class I, Division 2, Groups A, B, C, D, T4A |
Standards and regulations | Standards/specifications: ENÃ61000-6-2 ENÃ61000-6-3 ENÃ60068-2-78 ENÃ50178 ENÃ60068-2-6 ENÃ60068-2-27 Note: EMC ââ¬Ã¢ Immunity for industrial areas EMC ââ¬Ã¢ Emission for residential, business and commercial properties and small operations Environmental influences ââ¬Ã¢ Moisture and heat, constant Equipping power installations with electronic equipment Environmental influences ââ¬Ã¢ Vibrations (sinusoidal) Environmental influences ââ¬Ã¢ Shocks |
Mounting | Mounting type: pluggable onto CAPAROC CRâ⬦ current rail |
Description other products