Industrial Automation
Notes | General Note: LABS release â in accordance with test specification VWPV3.10.7:2005-0 When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules. |
Product properties | Product type: Device circuit breakers Product family: CAPAROC Number of slots: 1 Insulation characteristics Protection class: III Pollution degree: 2 |
Electrical properties | General Operating voltage: 0 VDC ... 30 VDC Rated voltage: 12 VDC 24 VDC Rated current IN: 10 ADC (per output) 40 ADC (Total) Rated surge voltage: 0.5 kV Efficiency: > 99 % Power dissipation: < 0.4 W (in nominal operation at 24V and 4x 10A) MTBF (IEC 61709, SN 29500): 269532625 h (at 25°C with 21% load) 269532334.5 h (at40°C with 34.25%load) 269530881.5 h (at60°C with 100%load) Voltage drop: 9.7 mV (at 10 A) |
Connection data | Load circuit Connection method: Push-in connection Stripping length: 10 mm Conductor cross section flexible: 0.2 mm² ... 4 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 12 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 4 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 4 mm² |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/0dd1e25f74d56d44bf870654fe633935/-S204x204-FJPG Width: 6.2 mm Height: 132.4 mm Depth: 109.9 mm (incl. DIN rail 7.5mm) |
Material specifications | Material: PA 6 Flammability rating according to UL 94: V-0 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -30°C ... 65°C (The temperature range of the power module must be taken into consideration) Ambient temperature (storage/transport): -40°C ... 70°C Altitude: ⤠4000 m (amsl) Humidity test: 96h, 95%RH, 40°C Shock (operation): 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27) 25g (6ms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock) Vibration (operation): 5g (10 ... 150Hz / 10cycles / axis / X,Y,Z) |
Approvals | UL approval Identification: UL/C-UL Listed UL 508 UL 121201 Class I, Division 2, Groups A, B, C, D, T4A |
Standards and regulations | Standards/specifications: EN61000-6-2 EN61000-6-3 EN60068-2-78 EN50178 EN60068-2-6 EN60068-2-27 Note: EMC â Immunity for industrial areas EMC â Emission for residential, business and commercial properties and small operations Environmental influences â Moisture and heat, constant Equipping power installations with electronic equipment Environmental influences â Vibrations (sinusoidal) Environmental influences â Shocks |
Mounting | Mounting type: pluggable onto CAPAROC CR⦠current rail |
ECLASS | ECLASS-11.0: 27140401 ECLASS-12.0: 27140401 ECLASS-13.0: 27140401 |
ETIM | ETIM 9.0: EC003538 |
UNSPSC | UNSPSC 21.0: 39121400 |