PLC-RPT-120UC/21-21/SO46 - Relay Module

PLC-INTERFACE for protection against interference currents or interference voltages on the control side. Consisting of basic terminal block with Push-in connection and plug-in miniature relay with power contact up to 2x8A, 2changeover contacts, 120VAC input voltage
Product Code: 1136244
Partner cod.: 1136244
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesGeneral: The PLC-ATP partition plate must be installed for voltages greater than 250V (L1, L2, L3) between identical terminal blocks on adjacent modules.
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.
Product propertiesProduct type: Relay Module
Product family: PLC-INTERFACE
Application: Filter to prevent interference
Operating mode: 100% operating factor
Mechanical service life: approx. 3x 107 cycles
Insulation characteristics
Insulation: Basic insulation
Insulation characteristics: Air clearances and creepage distances between the power circuits
Insulation: Basic insulation
Overvoltage category: III
Pollution degree: 3
Electrical propertiesMaximum power dissipation for nominal condition: 0.84 W
Test voltage (Winding/contact): 4 kVrms (50Hz, 1min., winding/contact)
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 VAC
Rated surge voltage: 4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths)
Input dataCoil side
Nominal input voltage UN: 120 VAC
110 VDC
Input voltage range: 94.8 VAC ... 168 VAC (20°C)
93.5 VDC ... 168.3 VDC (20°C)
Mains frequency: 50/60 Hz
Drive and function: monostable
Drive (polarity): polarized
Typical input current at UN: 6 mA (50Hz)
7 mA (60Hz)
Typical response time: 7 ms
Typical release time: 10 ms
Typical release voltage: 16 VAC
Coil voltage: 110 VDC
Protective circuit: RC element
Bridge rectifier
Status display: Yellow LED
Output dataSwitching
Contact switching type: 2 changeover contacts
Type of switch contact: Single contact
Contact material: AgNi
Maximum switching voltage: 250 V AC/DC
Minimum switching voltage: 5 V (10mA)
Limiting continuous current: 6 A
Maximum inrush current: 15 A (300ms)
Min. switching current: 10 mA (5 V)
Interrupting rating (ohmic load) max.: 144 W (24VDC)
96 W (48VDC)
60 W (60VDC)
44 W (110VDC)
57 W (220VDC)
1500 VA (250VAC)
Switching capacity min.: 0.12 W
Connection dataConnection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.14 mm² ... 2.5 mm²
Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG: 26 ... 14
DimensionsWidth: 14 mm
Height: 80 mm
Depth: 94 mm
Environmental and real-life conditionsAmbient conditions
Degree of protection (Relay base): IP20 (Relay base)
Degree of protection (Relay): RT III (Relay)
Degree of protection (Installation location): IP54 (Installation location)
Ambient temperature (operation): -40°C ... 55°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
Shipbuilding approval
Certificate: TAE0000196
Corrosive gas test
Identification: ISA-S71.04. G3 Harsh Group
EN60068-2-60
DNV GL data
Temperature: D
Humidity: A
Vibration: B/C
EMC: B
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive
Electromagnetic compatibility: Conformance with EMC directive
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: IEC 60947-5-1
MountingMounting type: DIN rail mounting
Assembly instructions: in rows with zero spacing
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27371601
ECLASS-12.0: 27371601
ECLASS-13.0: 27371601
ETIMETIM 9.0: EC001437
UNSPSCUNSPSC 21.0: 39122300
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00006.pdf

Approvals_00240.pdf

Approvals_01560.pdf

Approvals_01561.pdf

Approvals_01883.pdf

Manufacturer_declaration_01426.pdf

Manufacturer_declaration_02212.pdf

Manufacturer_declaration_03393.pdf

Manufacturer_declaration_03394.pdf

Manufacturer_declaration_03599.pdf

Manufacturer_declaration_06568.pdf

Technical_drawing_09182.pdf