Industrial Automation
Notes | General: The PLC-ATP partition plate must be installed for voltages greater than 250V (L1, L2, L3) between identical terminal blocks on adjacent modules. The PLC-ATP separating plate should be installed for safe isolation between adjacent modules The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. The PLC-ATP separating plate is required at the start and end of every PLC terminal strip. |
Product properties | Product type: Relay Module Product family: PLC-INTERFACE Application: Filter to prevent interference Operating mode: 100% operating factor Mechanical service life: approx. 3x 107 cycles Insulation characteristics Insulation: Basic insulation Insulation characteristics: Air clearances and creepage distances between the power circuits Insulation: Basic insulation Overvoltage category: III Pollution degree: 3 |
Electrical properties | Maximum power dissipation for nominal condition: 0.84 W Test voltage (Winding/contact): 4 kVrms (50Hz, 1min., winding/contact) Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VAC Rated surge voltage: 4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths) |
Input data | Coil side Nominal input voltage UN: 120 VAC 110 VDC Input voltage range: 94.8 VAC ... 168 VAC (20°C) 93.5 VDC ... 168.3 VDC (20°C) Mains frequency: 50/60 Hz Drive and function: monostable Drive (polarity): polarized Typical input current at UN: 6 mA (50Hz) 7 mA (60Hz) Typical response time: 7 ms Typical release time: 10 ms Typical release voltage: 16 VAC Coil voltage: 110 VDC Protective circuit: RC element Bridge rectifier Status display: Yellow LED |
Output data | Switching Contact switching type: 2 changeover contacts Type of switch contact: Single contact Contact material: AgNi Maximum switching voltage: 250 V AC/DC Minimum switching voltage: 5 V (10mA) Limiting continuous current: 6 A Maximum inrush current: 15 A (300ms) Min. switching current: 10 mA (5 V) Interrupting rating (ohmic load) max.: 144 W (24VDC) 96 W (48VDC) 60 W (60VDC) 44 W (110VDC) 57 W (220VDC) 1500 VA (250VAC) Switching capacity min.: 0.12 W |
Connection data | Connection method: Push-in connection Stripping length: 10 mm Conductor cross section rigid: 0.14 mm² ... 2.5 mm² Conductor cross section flexible: 0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1 mm² (TWIN ferrule) Conductor cross section AWG: 26 ... 14 |
Dimensions | Width: 14 mm Height: 80 mm Depth: 94 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection (Relay base): IP20 (Relay base) Degree of protection (Relay): RT III (Relay) Degree of protection (Installation location): IP54 (Installation location) Ambient temperature (operation): -40°C ... 55°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant Shipbuilding approval Certificate: TAE0000196 Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group EN60068-2-60 DNV GL data Temperature: D Humidity: A Vibration: B/C EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive Electromagnetic compatibility: Conformance with EMC directive |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: IEC 60947-5-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: in rows with zero spacing Mounting position: any |