Industrial Automation
QUINT4-PS/3AC/24DC/40/IOL - Power supply unit


Input data | AC operation Network type: Star network Nominal input voltage range: 3x 400 VÃAC ... 500 VÃAC 2x 400 VÃAC ... 500 VÃAC Input voltage range: 3x 400 VÃAC ... 500 VÃAC -20Ã%Ã...Ã+10Ã% 2x 400 VÃAC ... 500 VÃAC -10Ã%Ã...Ã+10Ã% Typical national grid voltage: 400 VÃAC 480 VÃAC Voltage type of supply voltage: AC/DC Inrush current: typ. 1.5 A (at 25ðC) Inrush current integral (I2t): < 0.06 A2s Inrush current limitation: 1.5 A (after 1Ãms) AC frequency range: 50 Hz ... 60 Hz -10Ã%Ã...Ã+10Ã% Frequency range (fN): 50 Hz ... 60 Hz -10Ã%Ã...Ã+10Ã% Mains buffering time: typ. 26 ms (3x 400 V AC) typ. 26 ms (3x 480 V AC) Current consumption: 3x 1.8 A (400ÃVÃAC) 3x 1.5 A (480ÃVÃAC) 2x 3 A (400ÃVÃAC) 2x 2.5 A (480ÃVÃAC) 3x 1.5 A (500 V AC) 2x 2.4 A (500 V AC) Reverse polarity protection: yes Nominal power consumption: 1217 VA Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester Power factor (cos phi): 0.95 Switch-on time: < 1 s Typical response time: 300 ms (from SLEEP MODE) Recommended breaker for input protection: 3x 4 A ... 20 A (Characteristic B, C, D, K or comparable) Recommended fuse for input protection: ââ°¥ 300 VÃAC Discharge current to PE: < 3.5 mA 1 mA (550 V AC, 60 Hz) DC operation Nominal input voltage range: ñ 260 VÃDC ... 300 VÃDC Input voltage range: ñ 260 VÃDC ... 300 VÃDC -13Ã%Ã...Ã+30Ã% Current consumption: 2.2 A (ñ260ÃVÃDC) 1.9 A (ñ300ÃVÃDC) Nominal power consumption: 1217 VA Recommended breaker for input protection: 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms) Recommended fuse for input protection: ââ°¥ 1000 VÃDC |
Output data | Efficiency: typ. 95.4 % (400ÃVÃAC) typ. 95.4 % (480ÃVÃAC) Nominal output voltage: 24 VÃDC Setting range of the output voltage (USet): 24 VÃDC ... 29.5 VÃDC (constant capacity) Nominal output current (IN): 40 A Static Boost (IStat.Boost): 45 A Dynamic Boost (IDyn.Boost): 60 A (5 s) Selective Fuse Breaking (ISFB): 215 A (15 ms) Magnetic circuit breaker tripping: A1...A40 / B2...B25 / C1...C13 / Z1...Z16 Derating: > 60°C ... 70°C (2.5%/K) Feedback voltage resistance: ââ°¤ 35 VÃDC Protection against overvoltage at the output (OVP): ââ°¤ 32 VÃDC Control deviation: < 0.5 % (Static load change 10Ã% ... 90Ã%) < 3 % (Dynamic load change 10Ã% ... 90Ã%, (10 Hz)) < 0.25 % (change in input voltage ñ10 %) Residual ripple: < 50 mVPP (with nominal values) Short-circuit-proof: yes No-load proof: yes Output power: 960 W 1080 W 1440 W Maximum no-load power dissipation: < 5 W (400ÃVÃAC) < 5 W (480ÃVÃAC) Power loss nominal load max.: < 45 W (400ÃVÃAC) < 45 W (480ÃVÃAC) Power dissipation SLEEP MODE: < 2 W (400ÃVÃAC) < 2 W (480ÃVÃAC) Crest factor: typ. 1.6 (400ÃVÃAC) typ. 1.9 (480ÃVÃAC) Rise time: < 1 s (UOutÃ=Ã10Ã%Ã...Ã90Ã%) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal relay 13/14 (configurable) Default: closed (Uout > 0.9 USet) Digital: 24 VÃDC 1 A 30 V AC/DC 0.5 A |
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 10 Stripping length: 8 mm Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.5 mm² Conductor cross section, rigid max.: 16 mm² Conductor cross section flexible min.: 0.5 mm² Conductor cross section flexible max.: 16 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 16 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 16 mm² Conductor cross section AWG min.: 20 Conductor cross section AWG max.: 6 Stripping length: 10 mm Tightening torque, min: 1.2 Nm Tightening torque max: 1.5 Nm Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 1 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 1.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 1.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 1.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 16 Stripping length: 8 mm |
Interfaces | IO-Link Reverse polarity protection: yes IO-Linkââ¬Ã¢¹ Specification: V1.1 Interface: IO-Link Connection method: 3-conductor port classÃA Connection marking: 3.3 (L+) 3.4 (ï¡Ã¢¢) 3.5 (L-) Transmission speed: 230 kbps (COM3) Cycle time: 2 ms Electrical isolation: yes Amount of process data: 6 Byte (Input data) Device ID: 262657dec/ 0x040201hex Vendor ID: 00B0hex / 176dez System communication Interface: System communication Connection method: 2-conductor Connection marking: 3.6 (ï¡Ã) 3.5 (L-/Sgnd) Electrical isolation: yes |
Signaling | Signal output POut: > 100Ã% (LED lights up yellow, output power > 960ÃW) > 75Ã% (LED lights up green, output power > 720ÃW) > 50Ã% (LED lights up green, output power > 480ÃW) UOut: > 0.9ÃxÃUSet (LED lights up green) < 0.9ÃxÃUSet (LED flashes green) |
Electrical properties | Number of phases: 3.00 Insulation voltage input/output: 4 kV AC (type test) 2.4 kV AC (routine test) Insulation voltage output / PE: 0.5 kV DC (type test) 0.5 kV DC (routine test) Insulation voltage input / PE: 3.5 kV AC (type test) 2.4 kV AC (routine test) Switching frequency: 32 kHz ... 100 kHz (Auxiliary converter stage) 55 kHz ... 300 kHz (Main converter stage) 25 kHz ... 500 kHz (PFC stage) |
Product properties | Product type: Power supply Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 849000 h (25ðC) > 517000 h (40ðC) > 236000 h (60ðC) Environmental protection directive: RoHS Directive 2011/65/EU WEEE Reach Insulation characteristics Protection class: I Degree of pollution: 2 Life expectancy (electrolytic capacitors) Current: 20 A Temperature: 40°C Time: 394000 h Additional text: 400ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹ Current: 20 A Temperature: 40°C Time: 367000 h Additional text: 480ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 40 A Temperature: 25°C Time: 394000 h Additional text: 400ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 40 A Temperature: 25°C Time: 367000 h Additional text: 480ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 40 A Temperature: 40°C Time: 139000 h Additional text: 400ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 40 A Temperature: 40°C Time: 130000 h Additional text: 480ÃVÃAC |
Dimensions | Width: 120 mm Height: 130 mm Depth: 125 mm Installation dimensions Installation distance right/left: 5 mm / 5 mm Installation distance top/bottom: 50 mm / 50 mm |
Mounting | Mounting type: DIN rail mounting Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No |
Material specifications | Flammability rating according to ULÃ94 (housing / terminal blocks): V0 Housing material: Metal Hood version: Stainless steel X6Cr17 Side element version: Aluminum |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ââ°¤ 5000 m (> 2000 m, observe derating) Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 11Ãms, 15Ãg, in each space direction (according to IEC 60068-2-27) Vibration (operation): 5ÃHz ... 100ÃHz resonance search 0.7g, 90Ãmin., resonance frequency 0.7g, 90Ãmin. (in accordance with DNV GL Class A) 5ÃHz ... 100ÃHz resonance search 2.3g, 90Ãmin., resonance frequency 2.3g, 90Ãmin. (according to DNV GL Class C) mounted with UWA 130 - 2901664 |
Standards and regulations | Rail applications: ENÃ50121-3-2 ENÃ50121-5 IEC 62236-3-2 IEC 62236-5 HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard ââ¬Ã¢ Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61558-2-16 IEC 61010-2-201 Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1 Standard - Safety of transformers: ENÃ61558-2-16 Battery charging: DINÃ41773-1 Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMIÃF47-0706, ENÃ61000-4-11 Overvoltage category EN 61010-1: IIÃ(ââ°¤Ã5000Ãm) EN 62477-1: IIIÃ(ââ°¤Ã2000Ãm) ENÃ61558-2-16: IIÃ(ââ°¤Ã4000Ãm) |
Approvals | CSA: CAN/CSA-C22.2 No.Ã61010-1-12 CAN/CSA-C22.2 No.Ã61010-2-201 SIQ: CB-Scheme (IEC 61010-1, IEC 61010-2-201) UL approvals: UL Listed ULÃ61010-1 UL Listed ULÃ61010-2-201 ULÃ121201 & CSAÃC22.2ÃNo.Ã213-17 ClassÃI, DivisionÃ2, Groups A, B, C, D T4 (Hazardous Location) |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU EMC requirements, power plant: ENÃ61000-6-5 Conducted noise emission: ENÃ55016 ENÃ61000-6-3 (Class B) Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) ENÃ55016 ENÃ61000-6-3 (Class B) Harmonic currents Standards/regulations: ENÃ61000-3-2 ENÃ61000-3-2 (Class A) Frequency range: 0 kHz ... 2 kHz Flicker Standards/regulations: ENÃ61000-3-3 Frequency range: 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion B Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 4 - asymmetrical) Signal: 2 kV (Test Level 4 - asymmetrical) Comments: Criterion B Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 2 kV (Test Level 3 - symmetrical) 6 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion B Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Power frequency magnetic field Standards/regulations: ENÃ61000-4-8 Frequency: 16.7 Hz 50 Hz 60 Hz 50 Hz 60 Hz 0 Hz Test field strength: 100 A/m 1 kA/m 300 A/m Additional text: 60 s 3 s DC, 60Ãs Comments: Criterion A Frequency range: 50 Hz ... 60 Hz Voltage dips Standards/regulations: ENÃ61000-4-11 Voltage: 400 VÃAC Frequency: 50 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 0.5 / 1 / 25 periods 5 / 10 / 50 periods 0,5 / 1 / 5 / 50 / 250 periods Additional text: Test Level 2 Comments: Criterion A: 0.5 / 1 period Criterion B: 25 periods Criterion B Criterion A: 0.5 / 1 period Criterion B: 5 / 50 / 250 periods Pulse-shape magnetic field Standards/regulations: ENÃ61000-4-9 Test field strength: 1000 A/m Comments: Criterion A Attenuated sinusoidal oscillations (ring wave) Standards/regulations: ENÃ61000-4-12 Input: 2 kV (Test Level 4 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Comments: Criterion A Asymmetrical conducted disturbance variables Standards/regulations: ENÃ61000-4-16 Test level 1: 15 Hz 150 Hz (Test Level 3) Voltage: 10 V 1 V 1 V 1 V 10 V 10 V 10 V (Permanent) 100 V (1 s) Test level 2: 150 Hz 1.5 kHz (Test Level 3) Test level 3: 1.5 kHz 15 kHz (Test Level 3) Test level 4: 15 kHz 150 kHz (Test Level 3) Test level 5: 50 Hz 60 Hz (Test Level 3) Test level 6: 50 Hz 60 Hz (Test Level 3) Comments: Criterion A Attenuated oscillating magnetic field Standards/regulations: ENÃ61000-4-10 Test field strength: 100 A/m Test level 1: 100 kHz Test level 2: 1 MHz Comments: Criterion A Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Description other products