Industrial Automation
QUINT4-PS/3AC/24DC/20/IOL - Power supply unit


Input data | AC operation Network type: Star network Nominal input voltage range: 3x 400 VÃAC ... 500 VÃAC 2x 400 VÃAC ... 500 VÃAC Input voltage range: 3x 400 VÃAC ... 500 VÃAC -20Ã%Ã...Ã+10Ã% 2x 400 VÃAC ... 500 VÃAC -10Ã%Ã...Ã+10Ã% Typical national grid voltage: 400 VÃAC 480 VÃAC Voltage type of supply voltage: AC/DC Inrush current: typ. 2 A (at 25ðC) Inrush current integral (I2t): < 0.1 A2s Inrush current limitation: 2 A (after 1Ãms) AC frequency range: 50 Hz ... 60 Hz -10Ã%Ã...Ã+10Ã% Frequency range (fN): 50 Hz ... 60 Hz -10Ã%Ã...Ã+10Ã% Mains buffering time: typ. 33 ms (3x 400 V AC) typ. 33 ms (3x 480 V AC) Current consumption: 3x 0.99 A (400ÃVÃAC) 3x 0.81 A (480ÃVÃAC) 2x 1.62 A (400ÃVÃAC) 2x 1.37 A (480ÃVÃAC) 3x 0.8 A (500 V AC) 2x 1.23 A (500 V AC) Reverse polarity protection: yes Nominal power consumption: 541 VA Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester Power factor (cos phi): 0.94 Switch-on time: < 1 s Typical response time: 300 ms (from SLEEP MODE) Recommended breaker for input protection: 3x 4 A ... 20 A (Characteristic B, C or comparable) Recommended fuse for input protection: ââ°¥ 300 VÃAC Discharge current to PE: < 3.5 mA 1.7 mA (550 V AC, 60 Hz) DC operation Nominal input voltage range: ñ 260 VÃDC ... 300 VÃDC Input voltage range: ñ 260 VÃDC ... 300 VÃDC -13Ã%Ã...Ã+30Ã% Current consumption: 1.23 A (ñÃ260ÃVÃDC) 1.06 A (ñ300ÃVÃDC) Recommended breaker for input protection: 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms) Recommended fuse for input protection: ââ°¥ 1000 VÃDC |
Output data | Efficiency: typ. 94.1 % (400ÃVÃAC) typ. 94.9 % (480ÃVÃAC) Output characteristic: U/I Advanced Nominal output voltage: 24 VÃDC Setting range of the output voltage (USet): 24 VÃDC ... 29.5 VÃDC (constant capacity) Nominal output current (IN): 20 A Static Boost (IStat.Boost): 25 A Dynamic Boost (IDyn.Boost): 30 A (5 s) Selective Fuse Breaking (ISFB): 120 A (15 ms) Magnetic circuit breaker tripping: A1...A16 / B2...B13 / C1...C6 / Z1...Z16 Derating: > 60°C ... 70°C (2.5%/K) Feedback voltage resistance: ââ°¤ 35 VÃDC Protection against overvoltage at the output (OVP): ââ°¤ 32 VÃDC Control deviation: < 0.5 % (Static load change 10Ã% ... 90Ã%) < 3 % (Dynamic load change 10Ã% ... 90Ã%, (10 Hz)) < 0.25 % (change in input voltage ñ10 %) Residual ripple: < 60 mVPP (with nominal values) Short-circuit-proof: yes No-load proof: yes Output power: 480 W 600 W 720 W Apparent power: 686 VA (400ÃV, UOUT = 24ÃV, IOUT = stat. Boost) 698 VA (480ÃV, UOUT = 24ÃV, IOUT = stat. Boost) Maximum no-load power dissipation: < 6 W (400ÃVÃAC) < 6 W (480ÃVÃAC) Power loss nominal load max.: < 30 W (400ÃVÃAC) < 30 W (480ÃVÃAC) Power dissipation SLEEP MODE: < 5 W (400ÃVÃAC) < 5 W (480ÃVÃAC) Crest factor: typ. 1.78 (400ÃVÃAC) typ. 2.1 (480ÃVÃAC) Rise time: < 80 ms (UOutÃ=Ã10Ã%Ã...Ã90Ã%) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal relay 13/14 (configurable) Default: closed (Uout > 0.9 USet) Digital: 24 VÃDC 1 A 30 V AC/DC 0.5 A |
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 10 Stripping length: 8 mm Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 10 Stripping length: 8 mm Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 1 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 1.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 0.75 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 1.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 16 Stripping length: 8 mm |
Interfaces | IO-Link Reverse polarity protection: yes IO-Linkââ¬Ã¢¹ Specification: V1.1 Interface: IO-Link Connection method: 3-conductor port classÃA Connection marking: 3.3 (L+) 3.4 (ï¡Ã¢¢) 3.5 (L-) Transmission speed: 230 kbps (COM3) Cycle time: 2 ms Electrical isolation: yes Amount of process data: 6 Byte (Input data) Device ID: 262657dec/ 0x040201hex Vendor ID: 00B0hex / 176dez System communication Interface: System communication Connection method: 2-conductor Connection marking: 3.6 (ï¡Ã) 3.5 (L-/Sgnd) Electrical isolation: yes |
Signaling | Signal output POut: > 100Ã% (LED lights up yellow, output power > 480ÃW) > 75Ã% (LED lights up green, output power > 360ÃW) > 50Ã% (LED lights up green, output power > 240ÃW) UOut: > 0.9ÃxÃUSet (LED lights up green) < 0.9ÃxÃUSet (LED flashes green) |
Electrical properties | Number of phases: 3.00 Insulation voltage input/output: 4 kV AC (type test) 2.4 kV AC (routine test) Insulation voltage output / PE: 0.5 kV DC (type test) 0.5 kV DC (routine test) Insulation voltage input / PE: 3.5 kV AC (type test) 2.4 kV AC (routine test) Switching frequency: 90 kHz ... 110 kHz (Auxiliary converter stage) 56 kHz ... 500 kHz (Main converter stage) 25 kHz ... 500 kHz (PFC stage) |
Product properties | Product type: Power supply Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 985000 h (25ðC) > 638000 h (40ðC) > 311000 h (60ðC) Environmental protection directive: RoHS Directive 2011/65/EU WEEE Reach Insulation characteristics Protection class: I Degree of pollution: 2 Life expectancy (electrolytic capacitors) Current: 10 A Temperature: 40°C Time: 344000 h Additional text: 400ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹ Current: 10 A Temperature: 40°C Time: 320000 h Additional text: 480ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 20 A Temperature: 25°C Time: 445000 h Additional text: 400ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 20 A Temperature: 25°C Time: 432000 h Additional text: 480ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 20 A Temperature: 40°C Time: 157000 h Additional text: 400ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 20 A Temperature: 40°C Time: 152000 h Additional text: 480ÃVÃAC |
Dimensions | Width: 70 mm Height: 130 mm Depth: 125 mm Installation dimensions Installation distance right/left: 5 mm / 5 mm Installation distance top/bottom: 50 mm / 50 mm |
Mounting | Mounting type: DIN rail mounting Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No |
Material specifications | Flammability rating according to ULÃ94 (housing / terminal blocks): V0 Housing material: Metal Hood version: Stainless steel X6Cr17 Side element version: Aluminum |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ââ°¤ 5000 m (> 2000 m, observe derating) Climatic class: 3K22 (in accordance with ENÃ60721-3-3) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): 5ÃHz ... 100ÃHz resonance search 2.3g, 90Ãmin., resonance frequency 2.3g, 90Ãmin. (according to DNV GL Class C) |
Standards and regulations | Rail applications: ENÃ50121-3-2 ENÃ50121-5 IEC 62236-3-2 IEC 62236-5 HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard - Electrical safety: IEC 60950-1/VDEÃ0805 (SELV) Standard ââ¬Ã¢ Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61558-2-16 IEC 61010-2-201 Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1 Standard - Safety of transformers: ENÃ61558-2-16 Standard - power supply devices for low voltage with DC output: ENÃ61204-3 Battery charging: DINÃ41773-1 Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMIÃF47-0706, ENÃ61000-4-11 Overvoltage category EN 61010-1: IIÃ(ââ°¤Ã5000Ãm) EN 62477-1: IIIÃ(ââ°¤Ã2000Ãm) ENÃ61558-2-16: IIÃ(ââ°¤Ã5000Ãm) |
Approvals | CSA: CAN/CSA-C22.2 No.Ã61010-1-12 CAN/CSA-C22.2 No.Ã61010-2-201 SIQ: CB-Scheme (IEC 61010-1, IEC 61010-2-201) UL approvals: UL Listed ULÃ61010-1 UL Listed ULÃ61010-2-201 ULÃ121201 & CSAÃC22.2ÃNo.Ã213-17 ClassÃI, DivisionÃ2, Groups A, B, C, D T4 (Hazardous Location) |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU EMC requirements, power plant: ENÃ61000-6-5 Conducted noise emission: ENÃ55016 ENÃ61000-6-3 (Class B) Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) ENÃ55016 ENÃ61000-6-3 (Class B) Harmonic currents Standards/regulations: ENÃ61000-3-2 ENÃ61000-3-2 (Class A) Frequency range: 0 kHz ... 2 kHz Flicker Standards/regulations: ENÃ61000-3-3 Frequency range: 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 4 - asymmetrical) Signal: 2 kV (Test Level 4 - asymmetrical) Comments: Criterion B Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 2 kV (Test Level 3 - symmetrical) 6 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion B Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Power frequency magnetic field Standards/regulations: ENÃ61000-4-8 Frequency: 16.7 Hz 50 Hz 60 Hz 50 Hz 60 Hz 0 Hz Test field strength: 100 A/m 1 kA/m 300 A/m Additional text: 60 s 3 s DC, 60Ãs Comments: Criterion A Frequency range: 50 Hz ... 60 Hz Voltage dips Standards/regulations: ENÃ61000-4-11 Voltage: 400 VÃAC Frequency: 50 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 0.5 / 1 / 25 periods 5 / 10 / 50 periods 0,5 / 1 / 5 / 50 / 250 periods Additional text: Test Level 2 Comments: Criterion A: 0.5 / 1 period Criterion B: 25 periods Criterion B Criterion A: 0.5 / 1 period Criterion B: 5 / 50 / 250 periods Pulse-shape magnetic field Standards/regulations: ENÃ61000-4-9 Test field strength: 1000 A/m Comments: Criterion A Attenuated sinusoidal oscillations (ring wave) Standards/regulations: ENÃ61000-4-12 Input: 2 kV (Test Level 4 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Comments: Criterion A Asymmetrical conducted disturbance variables Standards/regulations: ENÃ61000-4-16 Test level 1: 15 Hz 150 Hz (Test Level 3) Voltage: 10 V 1 V 1 V 1 V 10 V 10 V 10 V (Permanent) 100 V (1 s) Test level 2: 150 Hz 1.5 kHz (Test Level 3) Test level 3: 1.5 kHz 15 kHz (Test Level 3) Test level 4: 15 kHz 150 kHz (Test Level 3) Test level 5: 50 Hz 60 Hz (Test Level 3) Test level 6: 50 Hz 60 Hz (Test Level 3) Comments: Criterion A Attenuated oscillating magnetic field Standards/regulations: ENÃ61000-4-10 Test field strength: 100 A/m Test level 1: 100 kHz Test level 2: 1 MHz Comments: Criterion A Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Description other products