Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1180148
PHOENIX CONTACT 1180148
PHOENIX CONTACT 1180148
PHOENIX CONTACTNot available

VAL-EV-T1/T2 264/12.5-P - Type 1/2 surge protection plug

CHARX protect advanced: Replacement plug for surge protective devices from the VALVETRABEV-T1/T2 product range for the L-N path.
Product Code: 1180148
Partner cod.: 1180148
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: I / II
T1 / T2
EN type: T1 / T2
IEC power supply system: TN-S
TN-C
TT
Type: DIN rail module, two-section, divisible
Product type: Replacement plug
Product family: VALVETRAB MS
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: pluggable
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/244085b8304de74e95f3135ca62ba23a/-S204x204-FJPG
Width: 17.5 mm
Height: 47.2 mm
Depth: 63.9 mm
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6/PBT
Material group: I
Housing material: PA 6.6
PBT
Protective circuitMode of protection: L-N
Direction of action: L-N / L-PEN
Nominal voltage UN: 240/415VAC (TN-C, TN-S)
240/415VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 264 VAC
Residual current IPE: ≤ 800 µA
Standby power consumption PC: ≤ 270 mVA
Nominal discharge current In (8/20) µs: 12.5 kA
Maximum discharge current Imax (8/20) µs: 50 kA
Impulse discharge current (10/350)µs, charge: 6.25 As
Impulse discharge current (10/350)µs, specific energy: 39 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 12.5 kA
Short-circuit current rating ISCCR: 25 kA
Voltage protection level Up: ≤ 1.2 kV
≤ 1.6 kV (30 kA - 8/20 µs)
Residual voltage Ures: ≤ 1.2 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3kA)
TOV behavior at UT: 415 VAC (5s / withstand mode)
457 VAC (120min / safe failure mode)
Response time tA: ≤ 25 ns
Max. backup fuse with branch wiring: 160 A (gG)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Standards and regulationsStandards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171292
ETIMETIM 9.0: EC002496
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00729.pdf

Flyer_00007.pdf

Flyer_00002.pdf

Flyer_00001.pdf

Manufacturer_declaration_01377.pdf

Manufacturer_declaration_02200.pdf

Package_slip_00461.pdf

Technical_drawing_09862.pdf