Product properties | Type: Stand-Alone Product type: Controller Product family: PLCnext Control Insulation characteristics Protection class: III (IEC 61140, EN61140, VDE0140-1) |
System properties | Processor: Intel® Core⢠i7-10700TE 8x 2 GHz (Standard) Arm® Cortex®-A9, 800 MHz (CPU1) Arm® Cortex®-A8, 600 MHz (CPU2) Retentive data storage: 4 Mbyte RAM: 16384 Mbyte DDR4-2400 IEC 61131 runtime system Program memory: 32 Mbyte Data storage system: 64 Mbyte PROFINET Device function: PROFINET controller, PROFINET device Update rate: min. 1 ms Functionality Programming languages supported: Instruction list (IL) Symbolic flowchart (SFC) Ladder diagram (LD) Function block diagram (FBD) Structured text (ST) C++ C# Java Python Simulink System requirements Engineering tool: PLCnext Engineer Eclipse Visual Studio MATLAB® Simulink® Application interface: OPCUA |
Electrical properties | Power consumption: typ. 50 W max. 55 W Maximum power dissipation for nominal condition: max. 55 W Supply Supply voltage (DC): 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (including ripple (3.6VPP)) Power supply connection: Screw terminal blocks, plug-in Max. current consumption: 2.3 A Typical current consumption: 2.1 A Real-time clock Realtime clock: Integrated (battery backup) |
Connection data | COMBICON connector Conductor cross section, rigid: 0.2 mm² ... 2.5 mm² Conductor cross section, flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 |
Interfaces | USB Number of interfaces: 1 Connection method: USB type A, male connector Ethernet Bus system: RJ45 Number of interfaces: 3 Connection method: RJ45 jack Transmission speed: 1000/2000 Mbps (1000 Mbps (LAN 2 and LAN 3), 1000/2000 Mbps (LAN 1)) |
Dimensions | External dimensions Width / Height / Depth: 218 mm / 250 mm / 135 mm (without fan module) 218 mm / 285 mm / 135 mm (With fan module) |
Characteristics | Safety data: ENISO13849 Category: max. 4 Performance level (PL): max. e Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): max. 3 Safety data: ENIEC 62061 Safety Integrity Level Claim Limit (SIL CL): max. 3 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): 0°C ... 60°C up to 2000m above mean sea level 0°C ... 55°C 2000m...3000m above mean sea level 0°C ... 50°C 3000m...4000m above mean sea level Ambient temperature (storage/transport): -30°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) Shock (operation): 15g (according to IEC 61131-2) Shock (storage/transport): 20g (in accordance with EN60068-2-27/IEC 60068-2-27) Vibration (operation): 3g (in accordance with EN60068-2-6/IEC 60068-2-6) Vibration (storage/transport): 3g (in accordance with EN60068-2-6/IEC 60068-2-6) Air pressure (operation): 60 kPa ... 108 kPa (up to 4000m above mean sea level) Air pressure (storage/transport): 58 kPa ... 108 kPa (up to 4500m above mean sea level) |
Mounting | Mounting type: Wall mounting |
ECLASS | ECLASS-11.0: 27242207 ECLASS-12.0: 27242207 ECLASS-13.0: 27242207 |
ETIM | ETIM 9.0: EC000236 |
UNSPSC | UNSPSC 21.0: 32151700 |