UPS-BAT/PB/24DC/12AH - Energy storage

Energy storage, VRLA-AGM, 24 VDC, 12 Ah, automatic detection and communication with QUINT UPS-IQ
Product Code: 1274119
Partner cod.: 1274119
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Energy storageInput
Input voltage: 24 VDC (SELV)
Nominal capacity: 12 Ah
Charging current: 3.6 A
End-of-charge voltage: 27.6 VDC (20°C)
Output
Output voltage: 24 VDC
Output current: max. 50 A
Output fuse: 2x 25 A
Buffer time: 21 min. (20A)
8 min. (40A)
General
Connection in parallel: yes
max. 5
Connection in series: No
Battery type: BBBattery
BP12-12FR
Battery technology: VRLA-AGM
IQ-Technology: yes
Latest startup date (battery only): 12 Months (0°C ... 20°C)
Latest startup (battery only) - range: 9 Months ... 12 Months (20°C...30°C)
6 Months ... 9 Months (30°C ... 40°C)
Accumulator module service life (according to Eurobat): 6 (20°C)
Size designation: Block
Battery pack: yes
Suitable for fast charging: yes
Temperature sensor: yes
Number of replacement battery kits: 1x (UPS-BAT-KIT/PB/2X12V/12AH (1283121))
Disposal: Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations.
Connection dataConductor connection
Connection method: Screw connection
rigid: 10 mm² ... 16 mm²
flexible: 10 mm² ... 16 mm²
rigid (AWG): 8 ... 6 (Cu)
Stripping length: 10 mm
Tightening torque: 1.2 Nm ... 1.5 Nm
Drive form screw head: Slotted L
Product propertiesProduct type: Battery unit
Product family: Energy storage
Application: for QUINT4 DC-UPS, QUINT4 AC-UPS, QUINT-UPS, and TRIO-UPS-2G
Disposal: Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations.
Insulation characteristics
Protection class: III
Degree of pollution: 2
DimensionsItem dimensions
Width: 202 mm
Height: 202 mm
Depth: 110 mm
Drill hole
Diameter: 5 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting position: horizontal DIN rail NS 35, EN 60715
Material specificationsHousing material: Metal
Type of housing: Galvanized sheet steel, powder-coated
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (storage/transport): -20°C ... 40°C
Ambient temperature (charge): 0°C ... 40°C
Ambient temperature (discharge): -20°C ... 50°C
Max. permissible relative humidity (operation): ≤ 95 %
Shock: 15g, 11ms, in each space direction (in accordance with IEC 60068-2-27)
Vibration (operation): 5Hz…100Hz, 0.7g (in accordance with DNV/IEC 600068-2-6)
ApprovalsUL
Identification: UL/C-UL Listed UL61010-1
UL​
Identification: UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Shipbuilding
Identification: DNV
Shipbuilding​
Identification: ABS
Shipbuilding​​
Identification: LR
Shipbuilding​​​
Identification: BV
Ex dataSuited for EX-applications: No
Technical Specs
ECLASSECLASS-11.0: 27050403
ECLASS-12.0: 27050403
ECLASS-13.0: 27050403
ETIMETIM 9.0: EC000357
UNSPSCUNSPSC 21.0: 26111700
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00058.pdf

Approvals_01194.pdf

Approvals_01291.pdf

Approvals_01296.pdf

Approvals_01317.pdf

Approvals_01477.pdf

Approvals_01478.pdf

Manufacturer_declaration_01298.pdf

Manufacturer_declaration_03197.pdf

Manufacturer_declaration_05506.pdf

Manufacturer_declaration_06885.pdf

Package_slip_02548.pdf

Technical_drawing_10720.pdf

Various_00047.pdf

Various_00039.pdf

Various_00050.pdf

Various_00006.pdf