PHOENIX CONTACT 1328357
PHOENIX CONTACTNot available

PLC-RSC- 24DC/1/CB1-6 - Relay module

Combination of relay interface and electronic fuse protection on overall width: 6.2 mm, individual configuration of the nominal current (1 A ... 6 A), adjustable output characteristic, active signal output, easy system integration, with screw connection
Product Code: 1328357
Partner cod.: 1328357
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Description
Tecnichal data
NotesNotes on operation: Repeated hard short circuits can reduce the melting integral of the integrated backup fuse.
A suitable flyback diode must be used when switching inductive loads
If the DIP switches are not covered by an adjacent module, the PLC-ATP partition plate must be used for ESD protection
The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-2.
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
Do not connect adjacent channels to SELV/ PELV and voltages dangerous to the touch.
At least one functional insulation against adjacent modules is complied with in the support rail direction.
If the application has higher requirements on the insulation (basic or reinforced insulation), then these must be realized through suitable measures (e. g., partition plates).
Do not use to separate SELV / PELV circuits from other circuits, because safe isolation is not guaranteed.
Product propertiesProduct type: Relay Module
Product family: PLC-INTERFACE
Application: with integrated electronic circuit breaker
Operating mode: 100% operating factor
Data management status
Article revision: 02
Insulation characteristics: Air clearances and creepage distances
Insulation: Functional insulation
Overvoltage category: I
Pollution degree: 2
Electrical propertiesMaximum power dissipation for nominal condition: < 1.6 W
Fuse: electronic
Input dataOperating voltage (UN): 24 V DC (UIn+ - UA2)
Operating voltage range (DC): 19.2 V DC ... 30 V DC (UIn+ - UA2)
Current consumption (In+): 12 mA
Tripping current (IN): 1 A (adjustable)
2 A (adjustable)
3 A (adjustable)
4 A (adjustable)
5 A (adjustable)
6 A (preset)
Measuring tolerance: ± 15 %
Power dissipation: 0.06 W (Without load, A1 low)
0.4 W (Without load, A1 high)
< 1.6 W (Normal operation)
Switching: Switching input A1
Nominal switch-on voltage: 24 V (UA1 - UA2)
Switch-on voltage range: 11 V ... 30 V (UA1 - UA2)
Switch-off voltage range: 0 V ... 2 V (UA1 - UA2)
Current consumption (IA1): 4 mA (24 V)
Switch-on time: 36 ms
Switch-off time: 10 ms
Switching frequency: ≤ 2.5 Hz
Output dataLoad circuit: Power MOSFET switching output (positive switching)
Voltage drop: 0.16 V (6 A, UIn+ - Uout)
Short-circuit switching capacity: 100 A DC
300 A DC (<5 short circuits)
Required backup fuse: Only required if Imax of power supply unit > short-circuit switching capacity. Integrated failsafe element
Fail-safe element: 15 A
Surge voltage protection: > 33 V
Max. capacitive load: 12000 µF (Depending on the current setting and the short-circuit current available)
Shutdown time (): ≤ 15 ms (Short circuit ≥3 x IN)
0.1 s (Short circuit 2 ... <3 x IN)
1 s (Short circuit 1.5 ... <2 x IN)
4 s (Short circuit 1.1 ... <1.5 x IN)
Undervoltage switch-off: ≤ 17.8 V (active)
≥ 19 V (inactive)
Overvoltage switch-off: ≥ 30.5 V (active)
≤ 29.5 V (inactive)
Waiting time: 5 s (Between the pulses)
Number: 5 (Start attempts in hiccup mode)
Signal: Feedback contact
Output voltage: UIn+ - 0.7 V (high level)
Current (Maximum current): ≤ 20 mA
State condition (Normal operation): low
State condition (Error): high (Fuse has blown)
State condition (Hiccup mode): high (After all 5 start attempts have been completed)
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross-section rigid (2 conductors with same cross section): 0.14 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
0.14 mm² ... 1.5 mm²
Conductor cross section flexible (2 conductors with same cross section): 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve)
Conductor cross section AWG: 30 ... 12
Tightening torque: 0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing))
DimensionsItem dimensions
Width: 6.2 mm
Height: 80 mm
Depth: 94 mm
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Degree of protection (Installation location): ≥ IP54
Ambient temperature (operation): -25 °C ... 55 °C (Observe derating in the connected state)
Ambient temperature (storage/transport): -40 °C ... 70 °C
Altitude: ≤ 2000 m (Without derating)
≤ 3000 m (With correction factor for ambient temperature (operation) x 0.88)
Permissible humidity (operation): 95 %
ApprovalsUL, USA/Canada
Identification: UL 2367
UL 60947-1
UL 60947-5-1
CSA C22.2 No. 60947-1
CSA C22.2 No. 60947-5-1
UL data
Operating mode: Indoor use
Standards and regulationsElectromagnetic compatibility (EMC)
Standards/regulations: EN 61000-6-2
EN 61000-6-3
Air clearances and creepage distances
Standards/regulations: IEC 60664
MountingMounting type: DIN rail mounting
Assembly note: in rows with zero spacing
Mounting position: any
Description
PLC-RSC- 24DC/1/CB1-6 Interruttore protez.