Industrial Automation
Product properties | Product type: Ground terminal block Number of positions: 4 Number of connections: 8 Number of rows: 4 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Rated surge voltage: 6 kV |
Connection data | Number of connections per level: 2 Nominal cross section: 2.5 mm² Protective conductor connection Stripping length: 8 mm ... 10 mm Internal cylindrical gage: A3 B3 Connection in acc. with standard: IEC 60947-7-2 Conductor cross section rigid: 0.14 mm² ... 4 mm² Cross section AWG: 26 ... 12 (converted acc. to IEC) Conductor cross section flexible: 0.14 mm² ... 4 mm² Conductor cross section, flexible [AWG]: 26 ... 12 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.14 mm² ... 2.5 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.14 mm² ... 2.5 mm² Nominal cross section: 2.5 mm² Feed-through level Stripping length: 8 mm ... 10 mm Connection in acc. with standard: IEC 60947-7-1 Conductor cross section rigid: 0.14 mm² ... 4 mm² Cross section AWG: 26 ... 12 (converted acc. to IEC) Conductor cross section flexible: 0.14 mm² ... 4 mm² Conductor cross section, flexible [AWG]: 26 ... 12 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.14 mm² ... 2.5 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.14 mm² ... 2.5 mm² Nominal current: 18 A Maximum load current: 20 A (with 4 mm² conductor cross-section) Nominal voltage: 500 V Nominal cross section: 2.5 mm² Disconnect zone Stripping length: 8 mm ... 10 mm Connection in acc. with standard: IEC 60947-7-1 Conductor cross section rigid: 0.14 mm² ... 4 mm² Cross section AWG: 26 ... 12 (converted acc. to IEC) Conductor cross section flexible: 0.14 mm² ... 4 mm² Conductor cross section, flexible [AWG]: 26 ... 12 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.14 mm² ... 2.5 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.14 mm² ... 2.5 mm² Nominal current: 18 A Maximum load current: 20 A (with 4 mm² conductor cross-section) Nominal voltage: 500 V Nominal cross section: 2.5 mm² Protective conductor connection Connection cross sections directly pluggable Conductor cross section rigid: 0.34 mm² ... 4 mm² Conductor cross section, rigid [AWG]: 20 ... 12 (converted acc. to IEC) Conductor cross section flexible: 0.5 mm² ... 2.5 mm² Conductor cross-section flexible (ferrule without plastic sleeve): 0.5 mm² ... 2.5 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.5 mm² ... 2.5 mm² Feed-through level Connection cross sections directly pluggable Conductor cross section rigid: 0.34 mm² ... 4 mm² Conductor cross section, rigid [AWG]: 20 ... 12 (converted acc. to IEC) Conductor cross section flexible: 0.5 mm² ... 2.5 mm² Conductor cross-section flexible (ferrule without plastic sleeve): 0.5 mm² ... 2.5 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.5 mm² ... 2.5 mm² Disconnect zone Connection cross sections directly pluggable Conductor cross section rigid: 0.34 mm² ... 4 mm² Conductor cross section, rigid [AWG]: 20 ... 12 (converted acc. to IEC) Conductor cross section flexible: 0.5 mm² ... 2.5 mm² Conductor cross-section flexible (ferrule without plastic sleeve): 0.5 mm² ... 2.5 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.5 mm² ... 2.5 mm² |
Dimensions | Width: 5.2 mm End cover width: 2.2 mm Height: 142.4 mm Depth on NS35/7,5: 68.6 mm Depth on NS35/15: 76.1 mm |
Material specifications | Color: gray Flammability rating according to UL 94: V0 Insulating material group: I Insulating material: PA Static insulating material application in cold: -60°C Relative insulation material temperature index (Elec., UL 746 B): 130°C Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3 Surface flammability NFPA 130 (ASTM E 162): passed Specific optical density of smoke NFPA 130 (ASTM E 662): passed Smoke gas toxicity NFPA 130 (SMP 800C): passed |
Electrical tests | Surge voltage test Test voltage setpoint: 7.3 kV Result: Test passed Temperature-rise test Requirement temperature-rise test: Increase in temperature â¤45K Result: Test passed Power-frequency withstand voltage Test voltage setpoint: 1.89 kV Result: Test passed |
Mechanical properties | Mechanical data Open side panel: Yes |
Mechanical tests | Mechanical strength Result: Test passed Attachment on the carrier DIN rail/fixing support: NS35 Result: Test passed Test for conductor damage and slackening Rotation speed: 10 (+/- 2) rpm Revolutions: 135 Conductor cross section/weight: 0.14 mm² / 0.2 kg 2.5 mm² / 0.7 kg 4 mm² / 0.9 kg Result: Test passed |
Environmental and real-life conditions | Aging Temperature cycles: 192 Result: Test passed Needle-flame test Time of exposure: 30 s Result: Test passed Oscillation/broadband noise Specification: DINEN50155 (VDE0115-200):2022-06 Spectrum: Service life test category2, bogie-mounted Frequency: f1 = 5 Hz to f2 = 150 Hz f1 = 5 Hz to f2 = 250 Hz ASD level: 6.12 (m/s²)²/Hz Acceleration: 0.964g 3.12g Test duration per axis: 5 h Test directions: X-, Y- and Z-axis Result: Test passed Shocks Specification: DINEN50155 (VDE0115-200):2022-06 Pulse shape: Half-sine Acceleration: 5g 30g Shock duration: 30ms 18ms Number of shocks per direction: 3 Test directions: X-, Y- and Z-axis (pos. and neg.) X-, Y- and Z-axis Result: Test passed Ambient conditions Ambient temperature (operation): -60°C ... 105°C (max. short-term operating temperature RTI Elec.) Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24h, -60°C to +70°C) Ambient temperature (assembly): -5°C ... 70°C Ambient temperature (actuation): -5°C ... 70°C Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-2 IEC 60947-7-1 IEC 60947-7-1 |
Mounting | Mounting type: NS 35/7,5 NS35/15 |
ECLASS | ECLASS-11.0: 27141141 ECLASS-13.0: 27250104 |
ETIM | ETIM 9.0: EC000901 |
Description other products