Industrial Automation
Notes | General Note: LABS release â in accordance with test specification VWPV3.10.7:2005-0 When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules. Observe the specified conditions for use in potentially explosive areas. Install the device in a suitable approved housing with at least IP54 degree of protection that meets the requirements of IEC/EN60079-0. Also observe the requirements of IEC/EN60079-14. |
Product properties | Type: Plug-in module Product type: Device circuit breakers Product family: CAPAROC Number of slots: 2 Insulation characteristics Protection class: III Pollution degree: 2 |
Electrical properties | General Operating voltage: 10 VDC ... 30 VDC Rated voltage: 12 VDC 24 VDC Rated current IN: 45 ADC (Total current input) Rated surge voltage: 0.5 kV Tripping method: E (electronic) Dielectric strength: 35 VDC (Load circuit) Efficiency: > 99 % Closed circuit current I0: typ. 9 mA (no load at 24V) Power dissipation: typ. 0.22 W (no load at 24V) < 1.5 W (in nominal operation at 24V and 45A) Temperature derating: 45 A (Total current at40°C) 30 A (Total current at 65°C) MTBF (IEC 61709, SN 29500): 18886912.65 h (at 25°C with 21% load) 5907048.64 h (at40°C with 34.25%load) 933563.97 h (at40°C with 100%load) Voltage drop: 0.03 V (at 45A) Reset Input voltage range: 7 VDC ... 30 VDC (Reset with falling edge) Current consumption: typ. 0.5 mA (at 24 V DC) Pulse length: ⥠50 ms Stripping length: 8 mm Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 0.75 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 1.5 mm² Status output Output voltage: max. 30 VDC (Input voltage±5% in the event of no error) 0 VDC (Error) Output current: max. 20 mA Stripping length: 8 mm Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 0.75 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 1.5 mm² Status outputâ Output voltage: max. 30 VDC (Input voltage±5% when I>80%at at least one channel) Output current: max. 20 mA Stripping length: 8 mm Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 0.75 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 1.5 mm² |
Connection data | Main circuit IN+ Connection method: Push-in connection Stripping length: 18 mm Conductor cross section rigid: 0.5 mm² ... 16 mm² Conductor cross section AWG: 20 ... 8 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.5 mm² ... 16 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.5 mm² ... 16 mm² Main circuit IN- Connection method: Push-in connection Stripping length: 18 mm Conductor cross section rigid: 0.5 mm² ... 16 mm² Conductor cross section AWG: 20 ... 8 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.5 mm² ... 16 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.5 mm² ... 16 mm² |
Signaling | Power (PWR) LED green: lit (with no channel errors) lit (Supply voltage in the nominal range) flashing (3x on deactivation of programming lock) Power (PWR) LED red: lit (Supply voltage outside the nominal range) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3ced5a3a44f3524a884d85a64ccfc6c8/-S204x204-FJPG Width: 12.4 mm Height: 132.4 mm Depth: 111.3 mm (incl. DIN rail 7.5mm) |
Material specifications | Material: PA 6 PC Flammability rating according to UL 94: V-0 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -30°C ... 65°C Ambient temperature (storage/transport): -40°C ... 70°C Altitude: ⤠4000 m (amsl) Humidity test: 96h, 95%RH, 40°C Shock (operation): 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27) 25g (6ms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock) Vibration (operation): 5g (10 ... 150Hz / 10cycles / axis / X,Y,Z) |
Approvals | UL approval Identification: UL/C-UL Listed UL 508 UL 121201 Class I, Division 2, Groups A, B, C, D, T4A ATEX Identification: TÃV22 ATEX8874 X II 3G Ex ec IIC T4 Gc IECEx Identification: IECExTUR22.0049X II 3G Ex ec IIC T4 Gc UKCAEx(UKEX) Identification: TÃV22UKEX7109X II 3G Ex ec IIC T4 Gc |
Standards and regulations | Standards/specifications: EN61000-6-2 EN61000-6-3 EN60068-2-78 EN50178 EN60068-2-27 IEC 60079-7 IEC 60079-0 Note: EMC â Immunity for industrial areas EMC â Emission for residential, business and commercial properties and small operations Environmental influences â Moisture and heat, constant Equipping power installations with electronic equipment Environmental influences â Shocks Explosive atmospheres â Part7: Equipment protection by increased safety âeâ Explosive atmospheres â Part0: Equipment â General requirements |
Mounting | Mounting type: pluggable onto CAPAROC CR⦠current rail |
ECLASS | ECLASS-11.0: 27140401 ECLASS-12.0: 27140401 ECLASS-13.0: 27140401 |
ETIM | ETIM 9.0: EC003538 |