PSR-ME40-4NO-2NC-24DC-SC - Safety relays

Safety relay as contact extension, dropout delay can be set from 0.5 s ... 36 s, 4 enabling current paths, 1 confirmation current path, together with basic device up to Cat. 3, PL d in accordance with EN ISO 13849, plug-in screw terminal block, width: 22.5 mm
Product Code: 1397654
Partner cod.: 1397654
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Description
Download
Tecnichal data
NotesNote on application
Note on application: Only for industrial use
Product propertiesProduct type: Safety relays
Product family: PSRclassic
Application: Extension module
Set comprises: 1397653 PSR-ME40-4NO-2NC-24DC-SC-SET35
Mechanical service life: approx. 107 cycles
Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Data management status
Article revision: 02
Times
Typical response time: typ. 40 ms (For Us autostart)
Typical release time: 50 ms (on demand via A1)
Delay time range: 0.5 s ... 30 s ±40 %
Restart time: < 1 s
Recovery time: Delay time +500 ms
Electrical propertiesMaximum power dissipation for nominal condition: 17 W (US = 26.4 V, IL² = 72 A², PTotal max = 2.6 W + 14.4 W)
Nominal operating mode: 100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 V
Rated surge voltage/insulation: See section âہ“Insulation coordination”
Supply
Designation: A1/A2
Rated control circuit supply voltage US: 24 V DC -15 % / +10 %
Rated control supply current IS: typ. 77 mA (at US)
Power consumption at US: typ. 1.85 W
Inrush current: < 2.5 A (typically with US, Δt = 1 ms)
Filter time: 5 ms (in the event of voltage dips at Us)
Protective circuit: Suppressor diode
Input dataDigital: K1/K2
Description of the input: safety-related
Number of inputs: 1
Input voltage range "0" signal: 0 V DC ... 5 V DC
Input voltage range "1" signal: 20.4 V ... 26.4 V
Input current range "0" signal: 0 mA ... 2 mA
Filter time: 1 ms (Test pulse width of low test pulses)
1 s (Test pulse rate for low test pulse)
No brightness test pulses / high test pulses permitted.
Max. permissible overall conductor resistance: 50 Ω
Protective circuit: Suppressor diode
Current consumption: typ. 14 mA
Output dataRelay: Enabling current paths (27/28, 37/38, 47/48, 57/58)
Output description: 2 N/O contacts each in series, safety-related, floating
Number of outputs: 4
Contact switching type: 4 enabling current paths
Contact material: AgSnO2
Switching voltage: min. 10 V AC/DC
max. 250 V AC/DC
Switching capacity: min. 100 mW
Inrush current: min. 10 mA
max. 6 A
Switching capacity in accordance with IEC 60947-5-1: 5 A (AC15)
6 A (DC13)
Limiting continuous current: 6 A (Observe derating and load limit curve)
Sq. Total current: 72 A2 (observe derating)
Switching frequency: max. 0.5 Hz
Mechanical service life: 10x 106 cycles
Output fuse: 10 A gL/gG
4 A gL/gG (for low-demand applications)
Relay: Confirmation current path (15/16)
Output description: Diagnostic contact, 2 NC in series, floating
Number of outputs: 1
Contact switching type: 2 N/C contacts in series
Contact material: AgSnO2
Switching voltage: min. 10 V AC/DC
max. 250 V AC/DC
Switching capacity: min. 100 mW
Inrush current: min. 10 mA
max. 1 A
Switching capacity in accordance with IEC 60947-5-1: 1 A (AC15)
1 A (DC13)
Limiting continuous current: 1 A
Sq. Total current: 1 A2
Switching frequency: max. 0.5 Hz
Mechanical service life: 10x 106 cycles
Output fuse: 1 A gL/gG
Relay: Signaling current path (65/66)
Output description: 2 N/C contacts parallel, non-safety-related, floating
Number of outputs: 1
Contact material: AgSnO2
Switching voltage: min. 10 V AC/DC
250 V AC/DC
Switching capacity: min. 100 mW
Inrush current: max. 1 A
Switching capacity in accordance with IEC 60947-5-1: 1 A (AC15)
1 A (DC13)
Limiting continuous current: 1 A (observe derating)
Sq. Total current: 1 A2 (observe derating)
Switching frequency: max. 0.5 Hz
Output fuse: 1 A (gL/gG)
Connection dataConnection technology
pluggable: yes
Conductor connection
Connection method: Screw connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque: 0.5 Nm ... 0.6 Nm
SignalingStatus display: 2 x LED (green)
Operating voltage display: 1 x green LED
DimensionsWidth: 22.5 mm
Height: 112.2 mm
Depth: 114.5 mm
Material specificationsColor (Housing): traffic grey B (RAL 7043)
Housing material: Polyamide
CharacteristicsSafety data
Stop category: 1
Safety data: EN ISO 13849
Category: 3
Performance level (PL): d
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL): 2
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL): 2
Safety data: EN IEC 62061
Safety Integrity Level (SIL): 2
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport): -40 °C ... 70 °C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing)
Shock: 15g
Vibration (operation): 10 Hz ... 150 Hz, amplitude 0.15 mm, 2g
ApprovalsCE
Identification: CE-compliant
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: DIN EN 60947-1
MountingMounting type: DIN rail mounting
Assembly note: See derating curve
Mounting position: vertical or horizontal
Description
PSR-ME40-4NO-2NC-24DC-SC Modulo sicurezza
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01118.pdf

Certification_00187.pdf

Data_sheet_01471.pdf

Manufacturer_declaration_03904.pdf

Manufacturer_declaration_03905.pdf

Manufacturer_declaration_05474.pdf

Manufacturer_declaration_07035.pdf

Package_slip_01984.pdf

Technical_drawing_12121.pdf