Industrial Automation
Notes | Safety note Safety note: WARNING: The connectors may not be plugged in or disconnected under load. Ignoring the warning or improper use may damage persons and/or property. ⢠WARNING: Commission properly functioning products only. The products must be regularly inspected for damage. Decommission defective products immediately. Replace damaged products. Repairs are not possible. ⢠WARNING: Only electrically qualified personnel may install and operate the product. They must observe the following safety notes. The qualified personnel must be familiar with the basics of electrical engineering. They must be able to recognize and prevent danger. The relevant symbol on the packaging indicates that only personnel familiar with electrical engineering are allowed to install and operate the product. ⢠The products are suitable for applications in plant, controller, and electrical device engineering. ⢠When operating the connectors in outdoor applications, they must be separately protected against environmental influences. ⢠Assembled products may not be manipulated or improperly opened. ⢠Only use mating connectors that are specified in the technical data of the standards listed (e.g. the ones listed in the product accessories online at phoenixcontact.com/products). ⢠When using the product in direct connection with third-party manufacturers, the user is responsible. ⢠For operating voltages > 50V AC, conductive connector housings must be grounded ⢠Ensure that when laying the cable, the tensile load on the connectors does not exceed the upper limit specified in the standards. ⢠Observe the corresponding technical data. You will find information: o On the product o On the packing label o In the supplied documentation o Online at phoenixcontact.com/products under the product ⢠Only use tools recommended by PhoenixContact ⢠Use a protective cap to protect connectors that are not in use. The suitable accessories are available online in the accessory section of the product at phoenixcontact.com/products ⢠Ensure that the protective or functional ground has been properly connected. ⢠VDE 0100/1.97 § 411.1.3.2 and DIN EN 60 204/11.98 § 14.1.3 are applicable when combining several circuits in a cable and/or connector ⢠The connector warms up in normal operation. Depending on the ambient conditions, the surface of the connector can continue to warm up. In this case, the user is responsible for posting warnings (e.g. DIN EN ISO 13732-1:2008-12). |
Mounting | Mounting type: Rear wall/screw mounting M16 x 1.5 Connection method: Bus line |
Product properties | Product type: Circular connectors (device side) Number of positions: 5 No. of cable outlets: 1 Shielded: yes Coding: B Thread type: M12 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Material specifications | Flammability rating according to UL 94: V0 Seal material: FKM Contact material: CuZn Contact surface material: Ni/Au Contact carrier material: PA 6.6 Material for screw connection: Zinc die-cast, nickel-plated Outer sheath, material: PUR Conductor material: Bare Cu litz wires |
Electrical properties | Rated surge voltage: 1.5 kV AC Contact resistance: ⤠3 mé Insulation resistance: ⥠10 Gé Nominal voltage UN: 48 VAC 60 VDC Nominal current IN: 4 A (Plug/socket in accordance with IEC 61076-2-101, cable technical data is to be observed) |
Connection data | Conductor connection Connection method: Bus line Contact connection type: Socket Conductor cross section: 0.25 mm² |
Mechanical properties | Mechanical data Max. bending cycles: 3000000 |
Cable/line | Cable length: 2 PROFIBUS[915] Cable weight: 74 kg/km Number of positions: 2 Shielded: yes Cable type: PROFIBUS[915] Conductor structure: 1x2xAWG24/19 Conductor structure signal line: 19x 0.14 mm AWG signal line: 24 Conductor cross section: 2x 0.25 mm² Wire diameter incl. insulation: 2.56 mm External cable diameter: 8 mm ±0.4mm Outer sheath, material: PUR External sheath, color: blue Conductor material: Bare Cu litz wires Material wire insulation: Foamed PE Single wire, color: red, green Thickness, outer sheath: approx. 0.8 mm Overall twist: 2 wires, twisted Optical shield covering: 70 % Insulation resistance: ⥠16 Gé*km Working capacitance: 28 nF (at 1 kHz) Nominal voltage, cable: ⤠100 V Test voltage Core/Core: 3600 VDC Minimum bending radius, flexible installation: 5 x D Max. bending cycles: 3000000 Tensile strength: ⤠100 N Flame resistance: according to IEC 60332-1 Resistance to oil: Resistant to mineral oils and grease Ambient temperature (operation): -40°C ... 80°C (Cable, flexible installation) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP67 (When plugged in) IP65 (When plugged in) IP65/IP67 Ambient temperature (operation): -25 ... -85 (Plug / socket) -40°C ... 80°C (cable, fixed installation) -20°C ... 80°C (Cable, flexible installation) |
Standards and regulations | Standards/specifications: according to IEC 61076-2-101 |
ECLASS | ECLASS-11.0: 27440102 ECLASS-12.0: 27440116 ECLASS-13.0: 27440116 |
ETIM | ETIM 8.0: EC002635 |
UNSPSC | UNSPSC 21.0: 39121400 |