Industrial Automation
Notes | General Note: Connection for signal line tested in accordance with EN61000-4-4 with 1 kV; if necessary, customer must provide appropriate protective measures Repeated hard short circuits can reduce the melting integral of the integrated backup fuse. |
Product properties | Type: DIN rail module, one-piece Product type: Device circuit breakers Product family: PTCB Number of positions: 1 No. of channels: 1 Insulation characteristics Protection class: III Pollution degree: 2 |
Electrical properties | No. of channels: 1 General Operating voltage: 10 VDC ... 30 VDC Rated voltage: 24 VDC Rated current IN: 15 ADC (Total current input) 0.5 ADC (Rated current output) 0.1/0.2/0.315/0.4/0.5/0.63ADC(adjustable) Rated current (pre-adjusted): 0.5 A Rated surge voltage: 0.5 kV Tripping method: E (electronic) Feedback resistance: max. 35 VDC Required backup fuse: Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element. Short-circuit switching capacity: 300 A Dielectric strength: max. 35 VDC (Load circuit) Active current limitation: ⤠1,2 x IN, depending on the current setting Fuse: electronic Efficiency: > 98.5 % Closed circuit current I0: typ. 5 mA Power dissipation: typ. 0.1 W (No-load operation) < 0.7 W (Nominal operation) Module initialization time: 40 ms Waiting time after switch off of a channel: 5 s (at overload / short circuit) Measuring tolerance I: ± 17 % (Depending on the nominal current setting) Temperature derating: 15 A (Total current at 60°C) 20 A (Total current at 50°C) MTBF (IEC 61709, SN 29500): 28409090 h (at 25°C with 21% load) 11519410 h (at40°C with 34.25%load) 1577983 h (at60°C with 100%load) Voltage drop: ⤠0.35 V (Depending on the nominal current setting) Fail-safe element: 4 ADC Load circuit Shutdown time: ⤠600 ms ⥠12 ms (Depending on the current setting and the available load) Shutdown ⤠1.2 x IN, depending on the nominal current setting Undervoltage switch-off: ⤠9.2 VDC (active) ⥠10.2 VDC (inactive) Overvoltage switch-off: ⥠30.5 VDC (active) ⤠29.5 VDC (inactive) Max. capacitive load: 4.7 mF (Depending on the current setting and the short-circuit current available) Indicator/remote signaling Connection name: Remote indication circuit Switching function: N/O contact Operating voltage: 0 VDC ... 30 VDC Operating current: 100 mA DC |
Connection data | Main circuit IN+ Connection method: Push-in connection Stripping length: 8 mm Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 12 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 2.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm² Main circuit IN- Connection method: Push-in connection Stripping length: 8 mm Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 12 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 2.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm² Main circuit OUT Connection method: Push-in connection Stripping length: 8 mm Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 12 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 2.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm² Remote indication circuit Connection method: Push-in connection Stripping length: 10 mm Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 14 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 2.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm² |
Signaling | Channel LED off: off (Channel switched off) Channel LED yellow: flashing (Programming mode active) Channel LED green: lit (Channel switched on) Channel LED red: lit (Channel switched off, over- or undervoltage active) ON temporarily (Channel switched off, 5s cool-down phase, overload or short-circuit release) flashing (Channel switched off, ready to be switched back on, overload or short-circuit release) flashing quickly (Channel switched off, external voltage at the output, possible installation error) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/91339568b73b714292afb2d2f0fc1b11/-S204x204-FJPG Width: 6.2 mm Height: 105.8 mm Depth: 55.6 mm (incl. DIN rail 7.5mm) |
Material specifications | Material: PBT Flammability rating according to UL 94: V-0 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -30°C ... 60°C Ambient temperature (storage/transport): -40°C ... 70°C Altitude: ⤠3000 m up to52°C (amsl) ⤠4000 m up to46°C (amsl) Humidity test: 96h, 95%RH, 40°C Shock (operation): 30g (IEC 60068-2-27, Test Ea) Vibration (operation): 10Hz...59.6Hz (Amplitude±0.35mm; in accordance with IEC 60068-2-6, Test Fc) 59.6Hzâ¦150Hz (Acceleration5g; in accordance with IEC 60068-2-6, Test Fc) 5Hzâ¦100Hz (Resonance search4g; resonance frequency4g; 90minin accordance with DNV GL Class B) |
Approvals | UL approval Identification: UL/C-UL Listed UL 508 UL Recognized UL 2367 NEC Class 2 according to UL 1310 UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) DNV GL Identification: Shipbuilding approval DNV GL data Temperature: A Humidity: B Vibration: B EMC: A Enclosure: A |
Standards and regulations | Standards/specifications: EN61000-6-2 EN61000-6-3 EN60068-2-78 EN50178 EN60068-2-6 EN60068-2-27 EN60068-2-30 Note: EMC â Immunity for industrial areas EMC â Emission for residential, business and commercial properties and small operations Environmental influences â Moisture and heat, constant Equipping power installations with electronic equipment Environmental influences â Vibrations (sinusoidal) Environmental influences â Shocks Environmental influences â Part 2â30: Tests â Test Db: Damp heat, cyclical |
Mounting | Mounting type: DIN rail: 35 mm |
ECLASS | ECLASS-11.0: 27140401 ECLASS-13.0: 27140401 ECLASS-12.0: 27140401 |
ETIM | ETIM 9.0: EC003538 |
Description other products