Industrial Automation
Product properties | Product type: Panel feed-through terminal block Product family: PWO 16-POT Number of positions: 1 Pitch: 12.1 mm Number of connections: 2 Number of potentials: 1 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Nominal current IN: 76 A Nominal voltage UN: 1000 V Degree of pollution: 3 Rated voltage (III/3): 1000 V Rated surge voltage (III/3): 8 kV Rated voltage (III/2): 1000 V Rated surge voltage (III/2): 8 kV Rated voltage (II/2): 1000 V Rated surge voltage (II/2): 6 kV |
Connection data | Connection technology Connector system: UW 16 / PW 16 Nominal cross section: 16 mm² Conductor connection exterior Connection method: Push-in spring connection Connection direction of the conductor to plug-in direction: 45° Conductor cross section rigid: 1.5 mm² ... 16 mm² Conductor cross section flexible: 1.5 mm² ... 16 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 1.5 mm² ... 16 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 1.5 mm² ... 16 mm² 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve: 1.5 mm² ... 4 mm² Stripping length: 18 mm Conductor connection interior Connection method: Cable lug connection Connection direction of the conductor to plug-in direction: 0° |
Mounting | Plate thickness: 1 mm ... 6 mm Attachment to feed-through panel Tightening torque: 1 Nm (Mounting screw torque) Screw: M4 |
Material specifications | Material data - contact Note: WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201 Contact material: Cu alloy Surface characteristics: tin-plated Material data - housing Color (Housing): gray (7042) Insulating material: PA Insulating material group: I CTI according to IEC 60112: 600 Flammability rating according to UL 94: V0 Glow wire flammability index GWFI according to EN60695-2-12: 850 Glow wire ignition temperature GWIT according to EN60695-2-13: 775 Temperature for the ball pressure test according to EN60695-10-2: 125°C |
Notes | Safety note Safety note: ⢠Only electrically qualified personnel may install and operate the product. To recognize and prevent danger, the qualified personnel must be familiar with the basics of electrical engineering. ⢠Observe the technical data provided here and refer to the documents listed under âDownloadsâ. The download area contains important information, such as installation notes, technical drawings, and 3D data. ⢠To maintain the nominal voltage, align the cable lugs straight and centered, and cast the terminals on the inside. ⢠The cable entry funnel is not safe to touch. Never connect or disconnect the terminal when it is energized. Take appropriate steps to ensure touch protection. |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/e840d33717330747ad0c7b5d4b264f71/-S204x204-FJPG Pitch: 12.1 mm Width [w]: 12 mm External dimensions Width [w]: 12 mm Height [h1]: 44.4 mm Length [l1]: 39.7 mm Internal dimensions Width [w]: 12 mm Height [h2]: 26 mm Length [l2]: 23.1 mm |
Mechanical tests | Test for conductor damage and slackening Specification: IEC 60947-7-1:2009-04 Result: Test passed Pull-out test Specification: IEC 60947-7-1:2009-04 Conductor cross section/conductor type/tractive force setpoint/actual value: 1.5 mm² / solid / > 40 N 1.5 mm² / flexible / > 40 N 16 mm² / solid / > 100 N 16 mm² / flexible / > 100 N |
Electrical tests | Temperature-rise test Specification: IEC 60947-7-1:2009-04 (following) Requirement temperature-rise test: Increase in temperature â¤45K Short-time withstand current Specification: IEC 60947-7-1:2009-04 Air clearances and creepage distances | 1. Insulation coordination Application: Internal part molded Control cabinet panel 1mm...4mm Specification: IEC 60947-1:2007-06 + A1:2010-12 Insulating material group: I Comparative tracking index (IEC 60112): CTI 600 Rated insulation voltage (III/3): 1000 V Rated surge voltage (III/3): 8 kV minimum clearance value - non-homogenous field (III/3): 8 mm minimum creepage distance (III/3): 12.5 mm Rated insulation voltage (III/2): 1000 V Rated surge voltage (III/2): 8 kV minimum clearance value - non-homogenous field (III/2): 8 mm minimum creepage distance (III/2): 8 mm Rated insulation voltage (II/2): 1000 V Rated surge voltage (II/2): 6 kV minimum clearance value - non-homogenous field (II/2): 5.5 mm minimum creepage distance (II/2): 5.5 mm Air clearances and creepage distances | 2. Insulation coordination Application: Internal part molded Control cabinet panel 5mm...6mm Specification: IEC 60947-1:2007-06 + A1:2010-12 Insulating material group: I Comparative tracking index (IEC 60112): CTI 600 Rated insulation voltage (III/3): 800 V Rated surge voltage (III/3): 8 kV minimum clearance value - non-homogenous field (III/3): 8 mm minimum creepage distance (III/3): 10 mm Rated insulation voltage (III/2): 1000 V Rated surge voltage (III/2): 8 kV minimum clearance value - non-homogenous field (III/2): 8 mm minimum creepage distance (III/2): 8 mm Rated insulation voltage (II/2): 1000 V Rated surge voltage (II/2): 6 kV minimum clearance value - non-homogenous field (II/2): 5.5 mm minimum creepage distance (II/2): 5.5 mm Air clearances and creepage distances | 3. Insulation coordination Application: Internal part not molded DP-PWO 16-3 (width: 3 mm) Specification: IEC 60947-1:2007-06 + A1:2010-12 Insulating material group: I Comparative tracking index (IEC 60112): CTI 600 Rated insulation voltage (III/3): 400 V Rated surge voltage (III/3): 4 kV minimum clearance value - non-homogenous field (III/3): 3 mm minimum creepage distance (III/3): 5 mm Rated insulation voltage (III/2): 500 V Rated surge voltage (III/2): 4 kV minimum clearance value - non-homogenous field (III/2): 3 mm minimum creepage distance (III/2): 3 mm Rated insulation voltage (II/2): 800 V Rated surge voltage (II/2): 4 kV minimum clearance value - non-homogenous field (II/2): 3 mm minimum creepage distance (II/2): 4 mm Air clearances and creepage distances | 4. Insulation coordination Application: Internal part not molded DP-PWO 16-6 (width: 6 mm) Specification: IEC 60947-1:2007-06 + A1:2010-12 Insulating material group: I Comparative tracking index (IEC 60112): CTI 600 Rated insulation voltage (III/3): 800 V Rated surge voltage (III/3): 6 kV minimum clearance value - non-homogenous field (III/3): 5.5 mm minimum creepage distance (III/3): 10 mm Rated insulation voltage (III/2): 800 V Rated surge voltage (III/2): 8 kV minimum clearance value - non-homogenous field (III/2): 8 mm minimum creepage distance (III/2): 8 mm Rated insulation voltage (II/2): 1000 V minimum clearance value - non-homogenous field (II/2): 0 mm minimum creepage distance (II/2): 5 mm Air clearances and creepage distances | 5. Insulation coordination Application: Internal part not molded DP-PWO 16-9 (width: 9 mm) Control cabinet panel 1mm...4mm Specification: IEC 60947-1:2007-06 + A1:2010-12 Insulating material group: I Comparative tracking index (IEC 60112): CTI 600 Rated insulation voltage (III/3): 1000 V Rated surge voltage (III/3): 8 kV minimum clearance value - non-homogenous field (III/3): 8 mm minimum creepage distance (III/3): 12.5 mm Rated insulation voltage (III/2): 1000 V Rated surge voltage (III/2): 8 kV minimum clearance value - non-homogenous field (III/2): 8 mm minimum creepage distance (III/2): 8 mm Rated insulation voltage (II/2): 1000 V Rated surge voltage (II/2): 6 kV minimum clearance value - non-homogenous field (II/2): 5.5 mm minimum creepage distance (II/2): 5.5 mm Air clearances and creepage distances | 6. Insulation coordination Application: Internal part not molded DP-PWO 16-9 (width: 9 mm) Control cabinet panel 5mm...6mm Specification: IEC 60947-1:2007-06 + A1:2010-12 Insulating material group: I Comparative tracking index (IEC 60112): CTI 600 Rated insulation voltage (III/3): 800 V Rated surge voltage (III/3): 8 kV minimum clearance value - non-homogenous field (III/3): 8 mm minimum creepage distance (III/3): 10 mm Rated insulation voltage (III/2): 1000 V Rated surge voltage (III/2): 8 kV minimum clearance value - non-homogenous field (III/2): 8 mm minimum creepage distance (III/2): 8 mm Rated insulation voltage (II/2): 1000 V Rated surge voltage (II/2): 6 kV minimum clearance value - non-homogenous field (II/2): 5.5 mm minimum creepage distance (II/2): 5.5 mm Air clearances and creepage distances | 7. Insulation coordination Application: Internal part not molded Specification: IEC 60947-1:2007-06 + A1:2010-12 Insulating material group: I Comparative tracking index (IEC 60112): CTI 600 minimum clearance value - non-homogenous field (III/3): 0 mm minimum creepage distance (III/3): 0 mm minimum clearance value - non-homogenous field (III/2): 0 mm minimum creepage distance (III/2): 0 mm minimum clearance value - non-homogenous field (II/2): 0 mm minimum creepage distance (II/2): 0 mm |
Environmental and real-life conditions | Vibration test Specification: IEC 60068-2-6:2007-12 Frequency: 10 - 150 - 10 Hz Sweep speed: 1octave/min 5g (60.1Hz...150Hz) Amplitude: 0.35mm (10Hz...60.1Hz) Test duration per axis: 2.5 h Glow-wire test Specification: IEC 60695-2-11:2000-10 Temperature: 960°C Time of exposure: 30 s Ambient conditions Ambient temperature (operation): -40°C ... 100°C (Depending on the current carrying capacity/derating curve) Ambient temperature (storage/transport): -40°C ... 70°C Relative humidity (storage/transport): 30 % ... 70 % Ambient temperature (assembly): -5°C ... 100°C Ambient temperature (actuation): -5°C ... 100°C |
Packaging specifications | Type of packaging: packed in cardboard |
ECLASS | ECLASS-11.0: 27141134 ECLASS-13.0: 27141134 ECLASS-12.0: 27141134 |
ETIM | ETIM 9.0: EC001283 |
UNSPSC | UNSPSC 21.0: 39121400 |
Description other products