Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1708752
PHOENIX CONTACTNot available

TW 95/ 1-CL - Panel feed-through terminal block

Panel feed-through terminal block, connection method: T-LOX knee lever connection, Cable lug connection, number of positions: 1, load current: 232 A, connection direction of the conductor to plug-in direction: 0 °, width: 45 mm
Product Code: 1708752
Partner cod.: 1708752
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Panel feed-through terminal block
Product family: TW 95/.. -CL
Number of positions: 1
Pitch: 25 mm
Number of connections: 2
Number of rows: 1
Number of potentials: 1
Insulation characteristics
Overvoltage category: III
Degree of pollution: 3
Electrical propertiesNominal current IN: 232 A
Nominal voltage UN: 1000 V
Degree of pollution: 3
Rated voltage (III/3): 1000 V
Rated surge voltage (III/3): 8 kV
Rated voltage (III/2): 1000 V
Rated surge voltage (III/2): 8 kV
Rated voltage (II/2): 1000 V
Rated surge voltage (II/2): 6 kV
Connection dataConnection technology
Connector system: TW 95
Nominal cross section: 95 mm²
Conductor connection exterior
Connection method: T-LOX knee lever connection
Connection direction of the conductor to plug-in direction: 0°
Single-conductor/terminal point multi-stranded: 25 mm² ... 95 mm²
Conductor cross section flexible: 25 mm² ... 95 mm²
Conductor cross section flexible, with ferrule without plastic sleeve: 25 mm² ... 95 mm²
Conductor cross section, flexible, with ferrule, with plastic sleeve: 25 mm² ... 95 mm²
Stripping length: 25 mm
Conductor connection interior
Connection method: Cable lug connection
Connection direction of the conductor to plug-in direction: 0°
MountingPlate thickness: 1 mm ... 5 mm
Material specificationsMaterial data - contact
Note: WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201
Contact material: Cu alloy
Surface characteristics: tin-plated
Material data - housing
Color (Housing): gray (7042)
Insulating material: PA
Insulating material group: I
CTI according to IEC 60112: 600
Flammability rating according to UL 94: V0
Glow wire flammability index GWFI according to EN60695-2-12: 850
Glow wire ignition temperature GWIT according to EN60695-2-13: 775
Temperature for the ball pressure test according to EN60695-10-2: 125°C
NotesSafety note
Safety note: • Only electrically qualified personnel may install and operate the product.
To recognize and prevent danger, the qualified personnel must be familiar with the basics of electrical engineering.
• Observe the technical data provided here and refer to the documents listed under “Downloads”. The download area contains important information, such as installation notes, technical drawings, and 3D data.
• The cable entry funnel is not safe to touch. Never connect or disconnect the terminal when it is energized. Take appropriate steps to ensure touch protection.
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/e840d33717330747ad0c7b5d4b264f71/-S204x204-FJPG
Pitch: 25 mm
Width [w]: 45 mm
Height [h]: 81.8 mm
Length [l]: 120.05 mm
External dimensions
Height [h1]: 75.75 mm
Length [l1]: 52.9 mm
Internal dimensions
Height [h2]: 65.6 mm
Length [l2]: 67.15 mm
Mechanical testsTest for conductor damage and slackening
Specification: IEC 60947-7-1:2009-04
Result: Test passed
Pull-out test
Specification: IEC 60947-7-1:2009-04
Conductor cross section/conductor type/tractive force setpoint/actual value: 25 mm² / solid / > 135 N
25 mm² / flexible / > 135 N
95 mm² / solid / > 351 N
95 mm² / flexible / > 351 N
25 mm² / flexible with ferrule / > 135 N
95 mm² / flexible with ferrule / > 351 N
Electrical testsTemperature-rise test
Specification: IEC 60947-7-1:2009-04 (following)
Requirement temperature-rise test: Increase in temperature ≤45K
Short-time withstand current
Specification: IEC 60947-7-1:2009-04
Air clearances and creepage distances | 1. Insulation coordination
Specification: IEC 60947-1:2007-06 + A1:2010-12
Insulating material group: I
Comparative tracking index (IEC 60112): CTI 600
Rated insulation voltage (III/3): 1000 V
Rated surge voltage (III/3): 8 kV
minimum clearance value - non-homogenous field (III/3): 8 mm
minimum creepage distance (III/3): 12.5 mm
Rated insulation voltage (III/2): 1000 V
Rated surge voltage (III/2): 8 kV
minimum clearance value - non-homogenous field (III/2): 8 mm
minimum creepage distance (III/2): 8 mm
Rated insulation voltage (II/2): 1000 V
Rated surge voltage (II/2): 6 kV
minimum clearance value - non-homogenous field (II/2): 5.5 mm
minimum creepage distance (II/2): 5.5 mm
Environmental and real-life conditionsVibration test
Specification: IEC 60068-2-6:2007-12
Frequency: 10 - 150 - 10 Hz
Sweep speed: 1octave/min
5g (60.1Hz...150Hz)
Amplitude: 0.35mm (10Hz...60.1Hz)
Test duration per axis: 2.5 h
Glow-wire test
Specification: IEC 60695-2-11:2014-02
Temperature: 960°C
Time of exposure: 30 s
Ambient conditions
Ambient temperature (operation): -40°C ... 100°C (Depending on the current carrying capacity/derating curve)
Ambient temperature (storage/transport): -40°C ... 70°C
Relative humidity (storage/transport): 30 % ... 70 %
Ambient temperature (assembly): -5°C ... 100°C
Packaging specificationsType of packaging: packed in cardboard
Technical Specs
ECLASSECLASS-11.0: 27141134
ECLASS-12.0: 27141134
ECLASS-13.0: 27141134
ETIMETIM 9.0: EC001283
UNSPSCUNSPSC 21.0: 39121400
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00234.pdf

Application_note_00090.pdf

Approvals_00495.pdf

Approvals_00517.pdf

Manufacturer_declaration_00118.pdf

Manufacturer_declaration_02522.pdf

Manufacturer_declaration_05482.pdf

Package_slip_02489.pdf

Technical_drawing_20319.pdf