Industrial Automation
Notes | General: The necessary requirements for insulation (basic insulation or reinforced insulation) from adjacent modules (in DIN-rail direction) must be realized by applying suitable measures (e.g., partition plates). Ensure that the supply voltage of the device has a common reference potential. For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Product properties | Product type: Potential distributor Product family: VARIOFACE Insulation characteristics Insulation: Functional insulation Insulation characteristicsâ Insulation: Functional insulation Pollution degree: 2 |
Electrical properties | Nominal voltage UN: 230 V AC/DC Max. total current of all branches: 12 A Rated insulation voltage: 230 V Rated surge voltage: 2.1 kV (1.2/50 üs) |
Connection data | Service Entrance Number of connections: 2 Pitch: 5.08 mm Distribution Number of connections: 12 |
Dimensions | Width: 25 mm Height: 97 mm Depth: 42 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP00 Degree of protection (Installation location): ⥠IP54 (Installation location) Ambient temperature (operation): -20°C ... 50°C Altitude: ⤠2000 m |
Standards and regulations | Standards/regulations: EN60664-1 |
Mounting | Mounting type: DIN rail mounting Mounting position: any |
ECLASS | ECLASS-11.0: 27400609 ECLASS-12.0: 27400609 ECLASS-13.0: 27400609 |
ETIM | ETIM 9.0: EC001894 |
UNSPSC | UNSPSC 21.0: 39121400 |
Description other products