Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area Utilization restrictionâ CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Interface converter MTTF: 1439 Years (SN29500 standard, temperature25°C, operating cycle21%) 717 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 305 Years (SN29500 standard, temperature40°C, operating cycle100%) MTBF: 1247 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) 261 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical properties | Electrical isolation: VCC // TBUS // RS-485 (A) // RS-485 (B) Maximum power dissipation for nominal condition: 1.8 W Test voltage data interface/power supply: 1.5 kVrms (50Hz, 1min.) Test voltage data interfaces: 1.5 kV Supply Supply voltage range: 18 VDC ... 30 VDC (via pluggable COMBICON screw terminal block) Nominal supply voltage: 24 VDC (in acc. with UL) Typical current consumption: 75 mA (24VDC ï) Max. current consumption: ⤠2 A (For operation in a joining station, via the DIN rail connector) |
Connection data | Supply Stripping length: 7 mm Tightening torque: 0.6 Nm ... 0.8 Nm |
Interfaces | Bit distortion, input: max. ± 35 % Bit distortion, output: < 6.25 % Bit delay: < 1 bit Signal: Modbus Transmission channels: 2 (1/1), TD, RD, half duplex Data: RS-485 interface, in acc. with EIA/TIA-485, DIN 66259-4/RS-485 2-wire Transmission speed: 4.8/9.6/19.2/38.4/57.6/75/93.75/115.2/136/187.5/375/500 kbps (Can be set manually) Connection method: Pluggable screw connection Transmission length: ⤠1200 m (depends on transmission speed, bus system and cable type) Termination resistor: 390 é (Can be connected to port A and B) 150 é 390 é Single conductor/terminal point, rigid: 0.2 mm² ... 2.5 mm² Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Max. AWG conductor cross section, flexible: 12 Min. AWG conductor cross section, flexible: 24 Single-wire/terminal point, rigid AWG max.: 12 Single-wire/terminal point, rigid AWG min.: 24 Transmission medium: 2-wire twisted pair, shielded File format/coding: UART (11/10 bit switchable; NRZ) Data direction switching: Automatic control, min. station response time 2 bits |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8281444dbf78ec4d841d03868663771e/-S204x204-FJPG Width: 35 mm Height: 99 mm Depth: 105 mm |
Material specifications | Material: PA 6.6-FR |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 60°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠5000 m (For restrictions, see the manufacturer's declaration for altitude operation) ⤠2000 m (Hazardous locations) Permissible humidity (operation): 10 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec IIC T5 Gc Certificate: UL 21 ATEX 2550X Note: Please follow the special installation instructions in the documentation! IECEx Identification: Ex ec IIC T5 Gc Certificate: IECEx ULD 21.00013X UL, USA/Canada Identification: Class I, Zone 2, AEx ec IIC T5 Gc Ex ec IIC T5 Gc X Class I, Div. 2, Groups A, B, C, D Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A |
EMC data | Noise immunity: EN 61000-4-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: ± 6 kV Discharge in air: ± 8 kV Comments: Criterion B Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 3 GHz Field intensity: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: ± 2 kV Signal: ± 2 kV Comments: Criterion B Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Input: ± 0.5 kV Signal: ± 1 kV Comments: Criterion B Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Comments: Criterion A Voltage: 10 V Emitted interference Standards/regulations: EN55011 Comments: Class A, industrial applications Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
Standards and regulations | Free from substances that could impair the application of coating: in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 Standards/regulations: EN62368 |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27242208 ECLASS-12.0: 27242208 ECLASS-13.0: 27242208 |
ETIM | ETIM 9.0: EC001423 |
UNSPSC | UNSPSC 21.0: 43222600 |