PHOENIX CONTACT 2316363
PHOENIX CONTACTNot available

GW PL FF/MODBUS - Protocol converter

Modbus/RTU to FOUNDATION Fieldbus protocol converter
Product Code: 2316363
Partner cod.: 2316363
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Product propertiesProduct type: Interface converter
Insulation characteristics
Overvoltage category: II
Degree of pollution: 2
Electrical propertiesSupply
Supply voltage range: 18 VDC ... 30 VDC
Nominal supply voltage: 24 VDC
Max. current consumption: 34 mA
Connection dataSupply
Connection method: COMBICON plug-in screw terminal block
Conductor cross section, flexible: 0.20 mm² ... 2.50 mm²
Conductor cross section, rigid: 0.20 mm² ... 2.50 mm²
Conductor cross section AWG: 24 ... 12
Tightening torque: 0.5 Nm ... 0.6 Nm
InterfacesSignal: Modbus
Data: FOUNDATION Fieldbus
Data rate: 31.25 kbps
Number of connections: 1
Connection method: COMBICON
No. of channels: 1
Tightening torque: 0.5 Nm ... 0.6 Nm
Connection technology: Screw connection
Termination resistor: Switchable
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section AWG max.: 12
Conductor cross section AWG min.: 24
Protocols supported: Modbus/RTU, FOUNDATION Fieldbus
Data: Modbus/RTU
Transmission speed: 1200 kbps (min.)
Data rate: 115.2 kbps (max.)
Number of connections: 2
Connection method: COMBICON
No. of channels: 4 (Modbus/RTU devices)
Tightening torque: 0.5 Nm ... 0.6 Nm
Connection technology: Screw connection
Termination resistor: Switchable
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section, rigid min.: 0.02 mm²
Conductor cross section AWG max.: 12
Conductor cross section AWG min.: 24
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/5c3eedbdcf496542b3796b96afeb271f/-S204x204-FJPG
Width: 22.5 mm
Height: 99 mm
Depth: 114.5 mm
Material specificationsColor: gray
Housing material: PA V0
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 85°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: 2000 m
Permissible humidity (operation): 0 % ... 95 % (non-condensing)
Shock: 30g, 18 ms
Vibration (operation): 5g, 10Hz ... 150Hz
ApprovalsEx data
ATEX: PRESAFE 16ATEX7686X, II 3G, Ex nA IIC T4 Gc
IECEx: IECEx PRE 16.0001X, Ex nA IIC T4 Gc
UL, USA / Canada: Class I, Div. 2, Groups A, B, C, D
Class I, Zone 2, AEx nA IIC T4, Ex nA IIC T4 GcX
MountingMounting type: DIN rail: 35 mm
Assembly instructions: on standard DIN rail NS 35 in accordance with EN 60715
Mounting position: On horizontal DIN rail NS 35 in acc. with EN 60715
Technical Specs
ECLASSECLASS-11.0: 27242208
ECLASS-12.0: 27242208
ECLASS-13.0: 27242208
ETIMETIM 9.0: EC001423
UNSPSCUNSPSC 21.0: 32151700
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00456.pdf

Approvals_00462.pdf

Data_sheet_03092.pdf

Manufacturer_declaration_00099.pdf

Manufacturer_declaration_14261.pdf

Package_slip_00075.pdf

Technical_drawing_37352.pdf

Various_00070.pdf

Various_00071.pdf