Industrial Automation
AXL P FBPS BASE - Base module


Connection data | Supply Conductor cross section, flexible: 0.20 mm² ... 1.50 mm² Conductor cross section, rigid: 0.20 mm² ... 1.50 mm² Conductor cross section AWG: 24 ... 16 |
Interfaces | Data: Axioline P local bus Connection method: Bus base module Data: PROFIBUS PA Connection method: Push-in / plug connection Number of bus devices: 256 Termination resistor: 100 é |
Electrical properties | Maximum power dissipation for nominal condition: 17.58 W Supply Supply voltage range: 18.5 VÃDC ... 30.5 VÃDC Typical current consumption: 750 mA () Max. current consumption: 950 mA (18.5ÃVÃDC, 500ÃmA load) |
Product properties | Product type: Power supply Product family: Axioline P Insulation characteristics Overvoltage category: II Degree of pollution: 2 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d43e81415659ce4693ebf2a433dc07d5/-S204x204-FJPG Width: 35 mm Height: 130 mm Depth: 125 mm |
Mounting | Mounting type: DIN rail mounting |
Material specifications | Color: gray |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C (Mounting position: wall mounting on horizontal DIN rail) Ambient temperature (storage/transport): -40°C ... 85°C Altitude: 2000 m (above sea level) Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % Shock: 15g Vibration (operation): 2g |
Standards and regulations | Standards/regulations Standards/regulations: Ring wave noise immunity in acc. with IEC 61000-4-12 PROFIBUS standardization Standards/regulations: IEC 61158-2 |
Approvals | ATEX Identification: ïà II 3 G Ex ec IIC T4 Gc Certificate: IBExU 18ATEXB018 X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx IBE 18.0023X UKCAÃExÃ(UKEX) Identification: II 3G Ex ec IIC T4 Gc X Certificate: PxCAI22UKEx2316390X Ex data UL, USA / Canada: Class I, Div. 2, Groups A, B, C, D T4 Class I, Zone 2, IIC T4 |
Notes | Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China. |