Industrial Automation
Notes | Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Control box |
Electrical properties | Supply Max. current consumption: 6.5 mA (No-load) 680 mA (trunk) |
Ex data | Safety data Input voltage Ui: 32 V (IIB (C/D)) 24 V (IIC (A/B)) 17.5 V (FISCO) Inductance Li: 4 µH Capacitance Ci: 0 µF Max. output voltage Uo: Uin (spur) Max. output current Io: 56 mA (per spur) Max. output power Po: 1.792 W Safety-related maximum voltage Um: 17.5 V IIC/IIB (per spur): Max. external inductivity Lo / Max. external capacitance Co: / 80 nF 0.26 mH |
Interfaces | Signal: FOUNDATION Fieldbus PROFIBUS Data No. of channels: 12 Termination resistor: Integrated termination, activated with bridge located in correct terminals Conductor cross section flexible max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section, rigid min.: 0.2 mm² Conductor cross section AWG max.: 12 Conductor cross section AWG min.: 24 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/7828c761eaa26046a0b84522d64f86af/-S204x204-FJPG Width: 355.6 mm Height: 304.8 mm Depth: 127 mm |
Material specifications | Color: gray Housing material: Stainless steel |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP66 Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 70°C Altitude: 2000 m Max. permissible relative humidity (operation): < 95 % (non-condensing) |
Approvals | Conformity/Approvals Conformance: CE-compliant, additionally EN 61326-1 Ex data ATEX: DEMKO 16ATEX1704X II 3 G D Ex nA [ic] IIC T4 Gc, Ex nA nC [ic] IIC T4 Gc Ex ic IIC T4 Gc, FISCO ic spurs Ex tc IIIC T135 Dc IP66 IECEx: IECEx UL 16.0079X Ex nA [ic] IIC T4 Gc, Ex nA nC [ic] IIC T4 Gc Ex ic IIC T4 Gc, FISCO ic spurs Ex tc IIIC T135 Dc IP66 UL, USA / Canada: Class I, Zone 2, AEx nA [ic] IIC T4 Gc, AEx nA nC[ic] IIC T4 Gc Entity/FISCO spurs Class I, Div. 2, Groups A, B, C, D, T4 Class I, Zone 22, AEx tc IIIC T135 Dc IP66 |
Standards and regulations | Standards Standards/regulations: EN61326-1 EN60079-0 EN60079-11 EN60079-15 |
Mounting | Mounting type: Wall mounting |
ECLASS | ECLASS-11.0: 27180101 ECLASS-12.0: 27180101 |
ETIM | ETIM 9.0: EC000261 |
UNSPSC | UNSPSC 21.0: 31261500 |
Description other products