PHOENIX CONTACT 2320283
PHOENIX CONTACT 2320283
PHOENIX CONTACTNot available

QUINT4-UPS/1AC/1AC/1KVA - Uninterruptible power supply

Uninterruptible power supply with IQ technology for DIN rail mounting. Input: 120/230 V AC, output: 120/230 V AC/1 kVA. Provides information regarding the state of charge, remaining runtime, and service life of the rechargeable battery module at any time, thereby increasing system availability.
Product Code: 2320283
Partner cod.: 2320283
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Input dataAC operation
Input voltage: 100 VAC -10%/+20%
110 VAC -10%/+20%
120 VAC -10%/+20%
130 VAC -10%/+20%
200 VAC -20%/+20%
210 VAC -20%/+20%
220 VAC -20%/+20%
230 VAC -20%/+15%
240 VAC -20%/+10%
Input voltage range: 90 VAC ... 264 VAC
Input voltage range AC: 184 VAC ... 264 VAC
96 VAC ... 144 VAC
Typical national grid voltage: 120 VAC
230 VAC
Voltage type of supply voltage: AC
AC frequency range: 45 Hz ... 65 Hz
Buffer period: 1 h (38 AH)
Current consumption: 10.4 A (100VAC)
10.5 A (110VAC)
10.5 A (120VAC)
9.7 A (130VAC)
6.4 A (200VAC)
6 A (210VAC)
5.7 A (220 V AC)
5.5 A (230 V AC)
5.3 A (240VAC)
Variable connect threshold: Can be configured using UPS-CONF software
Power factor (cos phi): 0.9
Bypass fuse: T15A/250V (MDA-15-R)
Permissible backup fuse: B16 230 V AC
20 A (120VAC, Listed breaker)
Digital Control (configurable)
Designation: Remote
Low signal: Connection to SGnd with < 2.7 kΩ
High signal: Open (> 35 kΩ between Remote and SGnd)
Digital Control Low-Active (configurable)
Battery-operated start 120 VAC low signal: Connection to SGnd with < 2.7 kΩ
Battery-operated start 120 VAC high signal: Open (> 200 kΩ between Bat.-Start and SGnd)
Output dataClassification according to IEC 62040-3: VFI-SS-111
Efficiency: > 92 % (120VAC)
> 94 % (230 V AC)
Nominal output voltage: 100 VAC
110 VAC
120 VAC
130 VAC
200 VAC
210 VAC
220 VAC
230 VAC
240 VAC
Form of output voltage: Pure sine
Nominal output current (IN): 7.8 A (100VAC)
8.1 A (110VAC)
8.3 A (120VAC)
7.7 A (130VAC)
5 A (200VAC)
4.8 A (210VAC)
4.5 A (220 V AC)
4.3 A (230 V AC)
4.2 A (240VAC)
POWER BOOST (IBoost): 13 A (120VAC)
7 A (230 V AC)
Output power: 778 VA (700W)
889 VA (800W)
1000 VA (900W)
1000 VA (900W)
1000 VA (900W)
1000 VA (900W)
1000 VA (900W)
1000 VA (900W)
1000 VA (900W)
Apparent power: 1 kVA (UN120 V AC)
Nominal power: 900 W (UN120 V AC)
Maximum no-load power dissipation: typ. 17 W (120VAC)
typ. 25 W (230 V AC)
Power loss nominal load max.: typ. 79 W (120VAC)
typ. 55 W (230 V AC)
Crest factor: 2.8
Switch-over time: 0 ms
Connection in parallel: yes, 2
Connection in series: No
Mains operation
Nominal output voltage: 120 VAC ±2%
230 VAC ±2%
Nominal output current (IN): 8.3 A
4.3 A (230 V AC)
POWER BOOST (IBoost): 13 A
7 A
Battery operation
Nominal output voltage: 120 VAC ±2%
230 VAC ±2%
Nominal output current (IN): 4.3 A (230 V AC)
8.3 A (120VAC)
POWER BOOST (IBoost): 7 A (230 V AC)
13 A (120VAC)
Nominal output frequency: ± 60 Hz ±0.5% (At an input frequency of 55Hzto<65Hz)
± 50 Hz ±0.5% (At an input frequency of 45Hzto<55Hz)
Signal: AC OK
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal: Alarm
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal: Battery mode
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal: Ready
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal: P>P
Output voltage: 24 V (SELV)
Continuous load current: ≤ 20 mA
Energy storageNominal voltage UN: 2x 24 VDC
End-of-charge voltage: 58 V (temperature compensated)
Charging current: 5 A
Nominal capacity range: 3.4 Ah ... 190 Ah (5x38Ah)
Battery technology: VRLA, VRLA-WTR
Charge characteristic curve: IU0U
Permissible backup fuse: 50 A/58V
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm²
Conductor cross section AWG min.: 30
Conductor cross section AWG max.: 10
Stripping length: 8 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm²
Conductor cross section AWG min.: 30
Conductor cross section AWG max.: 10
Stripping length: 8 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm²
Conductor cross section AWG min.: 30
Conductor cross section AWG max.: 12
Stripping length: 8 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
InterfacesInterface: MINI-USB type B
Features: lockable
Maximum cable length: 3 m
SignalingTypes of signaling: LED
Active switching output
Signal output: Transistor output, active
Signalization designation: AC OK
Status display: LED
Color: green
Signal output: Transistor output, active​
Signalization designation: Alarm
Status display: LED
Color: red
Signal output: Transistor output, active​​
Signalization designation: Battery mode
Status display: LED
Color: yellow
Signal output: Transistor output, active​​​
Signalization designation: Ready
Signal output: Transistor output, active​​​​
Signalization designation: P>Pn
Status display: LED
Color: green
Signal output
Signalization designation: Reference potential for the signal inputs and outputs
Electrical propertiesNumber of phases: 1.00
Product propertiesProduct type: AC UPS
Product family: QUINTAC-USV
MTBF (IEC 61709, SN 29500): 217546 h (230 V AC, at 40°C)
Insulation characteristics
Protection class: I
Overvoltage category: II
Pollution degree: 3 (≤130VAC)
2 (>200VAC)
Life expectancy (electrolytic capacitors)
Time: 68970 h
DimensionsWidth: 290 mm
Height: 130 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting type: DIN rail mounting
Material specificationsHousing material: Metal
Hood version: Sheet steel, DIN EN ISO2081 coat - Fe/Zn 18/B/TopCoat transparent blue
Side element version: Aluminum plate, DIN EN 573-3
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 60°C (>50°C: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Maximum altitude: ≤ 3000 m (>2000m:0,6%/100m)
Climatic class: 3K3 (EN60721)
Max. permissible relative humidity (operation): ≤ 95 %
Shock: 15g in all directions (EN60068-2-27)
Vibration (operation): 5Hz...100Hz, 0.7g (EN60068-2-6)
Standards and regulationsUninterruptible power supply systems
Standard designation: Uninterruptible power supply systems
Standards/specifications: EN62040-1
ApprovalsUL
Identification: UL/C-ULRecognizedUL1778
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
Interference emission: Noise emission in accordance with EN62040-2
Noise immunity: Immunity in accordance with EN62040-2
Immunity in accordance with EN61000-6-1 (residential), EN61000-6-2 (industrial)
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Conducted noise emission: EN62040-02 (Class C2)
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: ± 6 kV
Discharge in air: ± 8 kV
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 6 GHz
Test field strength: 10 V/m
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: ± 2 kV
Output: ± 2 kV
Signal: ± 2 kV
± 2 kV (USB)
Comments: Criterion A (B for USB)
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Signal: 1 kV (asymmetrical)
Comments: Criterion A
Input/Output: ± 1 kV (symmetrical)
± 2 kV (asymmetrical)
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V
Power frequency magnetic field
Standards/regulations: EN61000-4-8
Frequency: 50 Hz
60 Hz
Test field strength: 100 A/m
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Technical Specs
ECLASSECLASS-11.0: 27040705
ECLASS-13.0: 27040705
ECLASS-12.0: 27040705
ETIMETIM 9.0: EC000382
UNSPSCUNSPSC 21.0: 39121000
Description
Uninterruptible power supply with IQ technology for DIN rail mounting. Input: 120/230 V AC, output: 120/230 V AC/1 kVA. Provides information regarding the state of charge, remaining runtime, and service life of the rechargeable battery module at any time, thereby increasing system availability.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00250.pdf

Approvals_00251.pdf

Approvals_01254.pdf

Approvals_01255.pdf

Approvals_01418.pdf

Data_sheet_03117.pdf

Manufacturer_declaration_01067.pdf

Manufacturer_declaration_03126.pdf

Manufacturer_declaration_05509.pdf

Package_slip_01476.pdf

Package_slip_02160.pdf

Technical_drawing_37400.pdf

Various_00006.pdf