Industrial Automation
IB IL CAN-MA-PAC - Communication module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8f49d2b498684640a945b59e148b2698/-S204x204-FJPG Width: 12.2 mm Height: 136.8 mm Depth: 71.5 mm |
Interfaces | Inline local bus Number of interfaces: 2 Connection method: Inline data jumper Transmission speed: 500 kbps CAN bus Number of interfaces: 1 Connection method: Inline shield connector Transmission speed: 250 kbps Protocols supported: CAN S-PORT Number of interfaces: 1 (Interface with plugged in memory stick) |
System properties | Local diagnostics Error messages via the bus: CAN bus voltage faulty Bus stop Module ID code (dec.): 191 ID code (hex): BF Length code (hex): 20 Length code (dec): 32 Process data channel: 64 Byte Input address area: max. 64 Byte Output address area: max. 64 Byte Register length: 64 Byte Required parameter data: 1 Byte Required configuration data: 5 Byte |
Product properties | Type: modular Product type: I/O component Product family: Inline Scope of delivery: including Inline connector and labeling field Operating mode: Process data mode with up to 64 words |
Electrical properties | Power dissipation: 0.9 W (Module) Potentials Power consumption: typ. 1.06 W (entire device) max. 1.16 W (entire device) Potentials: Communications power (U Supply voltage: 7.5 VÃDC (via voltage jumper) Current draw: max. 115 mA typ. 110 mA Potentials: Main circuit supply (U Supply voltage: 24 VÃDC (via voltage jumper) Current draw: max. 12 mA typ. 10 mA Electrical isolation/isolation of the voltage ranges Test voltage: 24 V supply UM, bus, logic/CAN interface: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV supply UM, bus, logic/functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: CAN interface/functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: Inline connector Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.08 mm² ... 1.5 mm² Conductor cross section flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.08 mm² ... 1.5 mm² Conductor cross section, flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 55°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -25°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 10 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting |
Description other products