Industrial Automation
AXL F AI8 XC 1F - Analog module
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3f783436b27c3846a361ee861b282789/-S204x204-FJPG Width: 53.6 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715). |
Interfaces | AxiolineFlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps |
System properties | Module Input address area: 16 Byte Output address area: 16 Byte Required parameter data: 27 Byte Required configuration data: 6 Byte |
Input data | Analog Input name: Analog inputs Description of the input: Differential inputs, voltage or current can be chosen separately Number of inputs: 8 A/D conversion time: 2 µs A/D converter resolution: 16 bit Connection method: Push-in connection Connection technology: 2-conductor Note regarding the connection technology: shielded, twisted pair Current input signal: 0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA Input resistance current input: 104 é (typical) Voltage input signal: 0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V Input resistance of voltage input: 268 ké (typical) Data formats: IB IL, S7-compatible Input filter: 30 Hz, 12 kHz and mean-value generation (can be parameterized) Filtering: RFI filtering / passive TP 1st order Limit frequency (3 dB): 30 Hz 12 kHz (in fast mode) Common mode voltage range signal - ground: -50 VDC ... 50 VDC Measured value representation: 16 bits (15 bits + sign bit) Protective circuit: Transient protection of inputs; Suppressor diode Overload protection of the current inputs; No; ±5.2VDC, maximum, Imax = 50mA Overload protection of the voltage inputs; ±30 V DC, maximum |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineF Mounting position: any (no temperature derating) Scope of delivery: including bus base module and AxiolineF connectors Insulation characteristics Overvoltage category: II (IEC 60664-1, EN60664-1) Pollution degree: 2 (IEC 60664-1, EN60664-1) |
Electrical properties | Maximum power dissipation for nominal condition: 4.2 W Potentials Power consumption: typ. 1.255 W (at UBus and UA (from HW02)) typ. 1.365 W (at UBus and UA (up to HW01)) max. 1.62 W (at UBus and UA (from HW02)) max. 1.605 W (at UBus and UA (up to HW01)) Potentials: AxiolineF local bus supply (U Supply voltage: 5 VDC (via bus base module) Current draw: max. 130 mA (up to HW01) max. 60 mA (from HW02) typ. 105 mA (up to HW01) typ. 45 mA (from HW02) Power consumption: max. 650 mW (up to HW01) max. 300 mW (from HW02) typ. 525 mW (up to HW01) typ. 225 mW (from HW02) Potentials: Supply for analog modules (U Supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 55 mA (from HW02) max. 45 mA (up to HW01) typ. 43 mA (from HW02) typ. 35 mA (up to HW01) Power consumption: max. 1.32 W (from HW02) max. 1.08 W (up to HW01) Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection; Polarity protection diode Transient protection; Suppressor diode Electrical isolation/isolation of the voltage ranges Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min. Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineF connector Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C (Standard) -40°C ... 70°C (Extended, see section âTested successfully: use under extreme ambient conditionsâ in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |
ECLASS | ECLASS-11.0: 27242601 ECLASS-12.0: 27242601 ECLASS-13.0: 27242601 |
ETIM | ETIM 9.0: EC001596 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products