Industrial Automation
IB IL AO 2/UI-XC-PAC - Analog module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/2182c65be3908e489150116208cdf69e/-S204x204-FJPG Width: 12.2 mm Height: 119.8 mm Depth: 71.5 mm Note on dimensions: Housing dimensions |
Interfaces | Inline local bus Number of interfaces: 2 Connection method: Inline data jumper Transmission speed: 500 kbps Transmission physics: Copper |
System properties | Module ID code (dec.): 91 ID code (hex): 5B Length code (hex): 04 Length code (dec): 04 Process data channel: 64 bit Input address area: 8 Byte Output address area: 8 Byte Register length: 64 bit Required parameter data: 10 Byte Required configuration data: 5 Byte |
Output data | Analog Output name: Analog outputs Connection technology: 2-conductor Note regarding the connection technology: shielded Number of outputs: 2 D/A conversion time: typ. 10 õs D/A converter resolution: 12 bit Protective circuit: Short-circuit and overload protection; Electronic Transient protection; Suppressor diode Data formats: IB IL, S7-compatible Representation of output values: 12 bits (11 bits + sign bit) Process data update: bus-synchronous Current output signal: 0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA Load/output load current output: ââ°¤ 450 é Voltage output signal: 0 V ... 10 V -10 V ... 10 V Load/output load voltage output: > 1 ké Permissible cable length: max. 250 m (The specifications refer to nominal operation after complying with installation instructions. The specifications refer to the following reference cable type: Shielded power station cable: LiYCY; 2 x 2 x 0,5Ãmm²; VDE0812) |
Product properties | Type: modular Product type: I/O component Product family: Inline Scope of delivery: including Inline connector and labeling field Diagnostics messages: Failure of the internal I/O supply I/O error message sent to the bus coupler I/O supply failure Message in the diagnostic code (in the IBÃIL format) Short circuit/overload of the outputs Message in the diagnostic code (in the IBÃIL format) Configuration invalid Message in the diagnostic code (in the IBÃIL format) |
Electrical properties | Potentials Power consumption: typ. 1.32 W (Nominal voltage load (UOUT1/2Ã=Ã10ÃV, RLÃ=Ã1Ãké)) typ. 1.97 W (Nominal current load (IOUT1/2Ã=Ã20ÃmA, RLÃ=Ã0Ãé)) Potentials: Communications power (U Supply voltage: 7.5 VÃDC (via voltage jumper) Current draw: max. 65 mA typ. 55 mA Potentials: Supply of analog modules (U Supply voltage: 24 VÃDC (via voltage jumper) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 75 mA (Nominal current load (IOUT1/2Ã=Ã20ÃmA, RLÃ=Ã0Ãé)) max. 30 mA (No-load) typ. 38 mA (Nominal voltage load (UOUT1/2Ã=Ã10ÃV, RLÃ=Ã1Ãké)) max. 45 mA (Nominal voltage load (UOUT1/2Ã=Ã10ÃV, RLÃ=Ã1Ãké)) typ. 65 mA (Nominal current load (IOUT1/2Ã=Ã20ÃmA, RLÃ=Ã0Ãé)) typ. 24 mA (No-load) Electrical isolation/isolation of the voltage ranges Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O): 500 VÃAC, 50 Hz, 1 min. Test voltage: 7.5ÃV supply (bus logic)/functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV analog supply (analog I/O)/functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: Inline connector Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.08 mm² ... 1.5 mm² Conductor cross section flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.08 mm² ... 1.5 mm² Conductor cross section, flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 55°C (Standard) -40°C ... 70°C (Extended, see section ââ¬Ã Tested successfully: use under extreme ambient conditionsâ⬠in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (according to DINÃENÃ61131-2) Permissible humidity (storage/transport): 10 % ... 95 % (according to DINÃENÃ61131-2) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting |
Description other products