Industrial Automation
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/172c7c5767999646b422d3edebda44f8/-S204x204-FJPG Width: 35 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715). |
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Interfaces | AxiolineFlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps |
System properties | Module Input address area: 8 Byte Output address area: 8 Byte Required parameter data: 7 Byte Required configuration data: 6 Byte |
Input data | Analog Input name: Analog inputs Description of the input: Differential inputs, current Number of inputs: 4 A/D conversion time: 31.25 µs A/D converter resolution: 16 bit Connection method: Push-in connection Connection technology: 2-, 3-, 4-conductor Note regarding the connection technology: shielded Current input signal: 0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA Input resistance current input: 104 é (typical) Data formats: IB IL, S7-compatible Input filter: 30 Hz, 12 kHz and mean-value generation (can be parameterized) Limit frequency (3 dB): 30 Hz 12 kHz Measured value representation: 16 bits (15 bits + sign bit) Protective circuit: Transient protection of inputs; Suppressor diode Overload protection of the inputs; No; ±5.2VDC, maximum, Imax = 50mA |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineF Mounting position: any (no temperature derating) Scope of delivery: including bus base module and AxiolineF connectors Insulation characteristics Overvoltage category: II (IEC 60664-1, EN60664-1) Pollution degree: 2 (IEC 60664-1, EN60664-1) |
Electrical properties | Potentials Power consumption: typ. 1.51 W (Device, total, plus the power consumption of the external sensors) max. 1.83 W (Device, total, plus the power consumption of the external sensors) Potentials: AxiolineF local bus supply (U Supply voltage: 5 VDC (via bus base module) Current draw: max. 150 mA typ. 120 mA Power consumption: max. 0.75 W typ. 0.6 W Potentials: Supply for analog modules (U Supply voltage: 24 VDC (I/O supply and sensor supply) Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 245 mA (IiS = 4 x 50 mA (full load)) max. 45 mA (IiS = 0 mA) typ. 118 mA (IiS = 4 x 20 mA (nominal load)) max. 125 mA (IiS = 4 x 20 mA (nominal load)) typ. 238 mA (IiS = 4 x 50 mA (full load)) Power consumption: max. 5.88 W (Full load) Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection; up to HW02: polarity protection diodefrom HW03: parallel diode; with external 5A fuse (for startup only) Transient protection; Suppressor diode Supply: Designation: Sensor supply UiS Supply voltage: 24 VDC (from UA) Current consumption: max. 50 mA (per channel) Electrical isolation/isolation of the voltage ranges Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min. Test voltage: 5V supply of the local bus (UBus)/analog inputs: 500 VAC, 50 Hz, 1 min. Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: 24 V supply (I/O)/analog inputs: 500 VAC, 50 Hz, 1 min. Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: Analog inputs/functional ground: 500 VAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineF connector Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C (Standard, applications with UL approval, use in zone2 potentially explosive area) -40°C ... 70°C (Extended, see section âTested successfully: use under extreme ambient conditionsâ in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Approvals | ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: UL 20 ATEX 2441X UKEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: PxCIMA22UKEX2701949X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx ULD 20.0026X UL, USA/Canada Identification: cULus Certificate: E238705 UL Ex, USA / Canada Identification: Class I, Zone 2, AEx ec IIC T4 Class I, Division 2, Groups A, B, C, and D, T4 Ex ec IIC T4 Gc X Certificate: E366272 CCC/China-Ex Identification: Ex ec IIC T4 Gc Certificate: ï¬, 2021122309114456 |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |