Industrial Automation
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/2b2eb0c33edfa2498509f0333c695851/-S204x204-FJPG Width: 60 mm Height: 141 mm Depth: 20 mm Note on dimensions: The height is 170 mm including fixing clips. The depth is 30 mm including the connector. |
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Material specifications | Housing material: Pocan® Color: anthracite grey RAL 7016 |
Input data | Digital Input name: Digital inputs Description of the input: EN 61131-2 types 1 and 3 Number of inputs: 8 Cable length: max. 30 m (to the sensor) Connection method: M12 connector Connection technology: 4-conductor Input voltage range "0" signal: -3 V ... 5 VDC Input voltage range "1" signal: 11 VDC ... 30 VDC Nominal input voltage UIN: 24 VDC Nominal input current at UIN: typ. 2.4 mA Input filter time: 1 ms Protective circuit: Overload protection, short-circuit protection of sensor supply Polarity reversal protection of the inputs IO-Link Number of ports: 1 Connection method: M12 connector, A-coded Connection technology: 3-conductor Port type: Class A Specification: V1.1.2 Reverse polarity protection: yes Transmission speed: 230.4 kbps (COM3) Cycle Time: < 1 ms Process data update: < 1 ms Amount of process data: 16 bit (Input data) |
Product properties | Type: Stand-Alone Product type: I/O component Product family: AxiolineE |
Electrical properties | Supply: IO-Link Designation: IO-Link port supply (L+) Nominal voltage for I/O supply: 24 VDC (Provided via the IO-Link interface of the IO-Link master.) Supply voltage range: 20 VDC ... 30 VDC (including all tolerances, including ripple) Nominal current per device: approx. 40 mA (15mA no load + current consumption sensors) Permissible cable length: max. 20 m Protective circuit: Reverse polarity protection; yes Supply: Designation: Power supply for sensors Current consumption: max. 1.28 A (per port) max. 1.28 A (Device dependent; observe the current of the IO-Link master that is made available via L+.) Electrical isolation/isolation of the voltage ranges Test voltage: 24 V supply / functional ground: 500 VAC, 50 Hz, 1 min. |
Connection data | Connection method: M12 connector Note on the connection method: in accordance with IEC 61076-2-101, M12 fast connection technology (SPEEDCON) |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP65/IP67 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -25°C ... 70°C Permissible humidity (operation): 5 % ... 95 % Permissible humidity (storage/transport): 5 % ... 95 % |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Mounting | Mounting type: Wall mounting |
ECLASS | ECLASS-11.0: 27242604 ECLASS-12.0: 27242604 ECLASS-13.0: 27242604 |
ETIM | ETIM 9.0: EC001599 |
UNSPSC | UNSPSC 21.0: 32151600 |