Industrial Automation
AXL E IOL TC4/K M12 - Analog module
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Type: Stand-Alone Product type: Interface converter Product family: AxiolineE Insulation characteristics Pollution degree: 2 (EN60664-1) |
Electrical properties | Supply: IO-Link Designation: IO-Link port supply (L+) Nominal voltage for I/O supply: 24 VDC (Provided via the IO-Link interface of the IO-Link master.) Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Nominal current per device: typ. 35 mA (±15% (at 24 V DC), max. 70 mA) Protective circuit: Reverse polarity protection; yes Short-circuit protection; yes Overload protection; yes Electrical isolation/isolation of the voltage ranges Test voltage: IO-Link bus logic: 500 VAC, 50 Hz, 1 min. Test voltage: Thermocouple I/O devices: 500 VAC, 50 Hz, 1 min. Test voltage: Functional ground: 500 VAC, 50 Hz, 1 min. |
Input data | IO-Link Number of ports: 1 Connection method: M12 connector (A-coded) Connection technology: 3-conductor Port type: Class A Specification: V1.1.2 Reverse polarity protection: yes Transmission speed: 230.4 kbps (COM3) Process data update: < 310 ms Amount of process data: 64 bit (4x 16-bit input data) Analog Input name: Analog TC inputs Description of the input: Differential inputs Number of inputs: 4 Connection method: Push-in technology Connection technology: 2-conductor A/D conversion time: typ. 40 ms A/D converter resolution: 24 bit Sensor types that can be used (TC): K/J Measuring principle: Sigma/Delta process Measured value representation: 16 bits Protective circuit: Transient protection of inputs Overload protection Wire-break detection |
Connection data | Thermocouples Connection method: Push-in technology Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/cda820a37a86fc44b987db43d25a2615/-S204x204-FJPG Width: 150 mm Height: 54 mm Depth: 118 mm Note on dimensions: When installing, note the length of the M12 connector for the IO-Link cable and the bending radii of the TC cables. |
Material specifications | Color: light grey RAL 7035 Housing material: Polycarbonate |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP65 (not UL-tested) Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -25°C ... 85°C Permissible humidity (operation): 5 % ... 95 % Permissible humidity (storage/transport): 5 % ... 95 % |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
ECLASS | ECLASS-11.0: 27242601 ECLASS-12.0: 27242601 ECLASS-13.0: 27242601 |
ETIM | ETIM 8.0: EC001596 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products