Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area Utilization restrictionâ CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Media converter MTTF: 212 Years (SN29500 standard, temperature25°C, operating cycle21%) 150 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 86 Years (SN29500 standard, temperature40°C, operating cycle100%) MTBF: 149 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) 24 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical properties | Electrical isolation: VCC // RS-485 Maximum power dissipation for nominal condition: 2.88 W Test voltage data interface/power supply: 1.5 kVrms (50Hz, 1min.) Supply Supply voltage range: 18 VDC ... 30 VDC (via pluggable COMBICON screw terminal block) Nominal supply voltage: 24 VDC (in acc. with UL) Typical current consumption: 120 mA (24VDC) Max. current consumption: 130 mA ⤠2 A (For operation in a joining station, via the DIN rail connector) |
Output data | Switching Output name: Relay output Output description: Alarm output Number of outputs: 1 Maximum switching voltage: 60 VDC (Resistive Load, General Load) 30 VAC (Resistive load) 42 VAC (peak, resistive load) Limiting continuous current: 0.46 A |
Connection data | Supply Connection method: COMBICON plug-in screw terminal block Stripping length: 7 mm Tightening torque: 0.56 Nm ... 0.79 Nm |
Interfaces | Bit distortion, input: ± 35 % (permitted) Bit distortion, output: < 6.25 % Bit delay: < 1 bit (DIP7 = OFF, standard operation) 11 bit (DIP7 =ON, redundancy operation) Signal: PROFIBUS Data: optical FO No. of channels: 2 Transmit capacity, minimum: -4.2 dBm (200/230µm) -17.8 dBm (50/125µm) -14.6 dBm (62,5/125 µm) Transmission length incl. 3 dB system reserve: 2600 m (with F-G 50/125 2.5 dB/km) 3300 m (with F-G 62,5/125 3.0 dB/km) 800 m (F-K 200/230 10dB/km with quick mounting connector) Connection method: B-FOC (ST®) Wavelength: 850 nm Minimum receiver sensitivity: -30 dBm (50/125µm) Maximum receiver sensitivity: -3 dBm (200/230µm) Transmission medium: PCF fiber Multi-mode fiberglass Data: PROFIBUS acc. to IEC 61158, RS-485 2-wire, half duplex, automatic control Serial transmission speed: ⤠12 Mbps Connection method: D-SUB-9 female connector Transmission length: ⤠1200 m (depending on the data rate, with shielded, twisted pair data cable) Single conductor/terminal point, rigid: 0.2 mm² ... 2.5 mm² Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Max. AWG conductor cross section, flexible: 14 Min. AWG conductor cross section, flexible: 24 Single-wire/terminal point, rigid AWG max.: 14 Single-wire/terminal point, rigid AWG min.: 24 Transmission medium: Copper File format/coding: UART (11 Bit, NRZ) Data direction switching: Automatic control Output nominal voltage: 5 V ±0.25 (50 mA) |
Dimensions | Width: 35 mm Height: 99 mm Depth: 105 mm |
Material specifications | Material: PA 6.6-FR |
Cable/line | FO cable Fiber types: 50/125 µm 62.5/125 µm Fiberglass |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 60°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠5000 m (For restrictions, see the manufacturer's declaration for altitude operation) ⤠2000 m (Hazardous locations) Permissible humidity (operation): 30 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex nA nC IIC T4 Gc X Note: Please follow the special installation instructions in the documentation! ATEX, FO interface Identification: ï II (2) G [Ex op is Gb] IIC ï II (2) D [Ex op is Db] IIIC Certificate: PTB06ATEX2042U Note: Please follow the special installation instructions in the documentation! UL, USA/Canada Identification: Class I, Zone 2, AEx nc IIC T5 Class I, Zone 2, Ex nC nL IIC T5 X Class I, Div. 2, Groups A, B, C, D PROFIBUS interoperability Note: Tested by independent PNO test laboratory (PN059-485-01) Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A Shipbuilding Identification: DNV GL DNV GL data Temperature: B Humidity: A Vibration: A EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
Standards and regulations | Air clearances and creepage distances Standards/regulations: DINEN60664-1 VDE0110-1 DINEN50178 EN60950 |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 19170411 ECLASS-12.0: 19170411 ECLASS-13.0: 19170411 |
ETIM | ETIM 9.0: EC001467 |
UNSPSC | UNSPSC 21.0: 43201500 |
Description other products