Industrial Automation
Product properties | Product type: Feed-through terminal block Number of positions: 4 Number of connections: 8 Number of rows: 1 Potentials: 4 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Rated surge voltage: 8 kV Maximum power dissipation for nominal condition: 1.82 W |
Connection data | Number of connections per level: 8 Nominal cross section: 10 mm² Screw thread: M4 Tightening torque: 1.5 ... 1.8 Nm Stripping length: 12 mm Internal cylindrical gage: A3 Connection in acc. with standard: IEC 60947-7-1 Conductor cross section rigid: 0.5 mm² ... 16 mm² Cross section AWG: 20 ... 6 (converted acc. to IEC) Conductor cross section flexible: 0.5 mm² ... 10 mm² Conductor cross section, flexible [AWG]: 20 ... 8 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.5 mm² ... 16 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.5 mm² ... 16 mm² 2 conductors with same cross section, solid: 0.5 mm² ... 6 mm² 2 conductors with same cross section, flexible: 0.5 mm² ... 6 mm² 2 conductors with same cross section, flexible, with ferrule without plastic sleeve: 0.5 mm² ... 6 mm² 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve: 0.5 mm² ... 6 mm² Nominal current: 57 A Maximum load current: 76 A (with 16 mm² conductor cross section) Nominal voltage: 800 V |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d6f1789e07f335459b2079a628dea24e/-S204x204-FJPG Width: 57 mm Height: 33 mm Depth: 31 mm Hole diameter: 4.2 mm |
Material specifications | Color: gray Flammability rating according to UL 94: V2 Insulating material group: I Insulating material: PA Static insulating material application in cold: -40°C Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)): 125°C Relative insulation material temperature index (Elec., UL 746 B): 125°C |
Electrical tests | Surge voltage test Test voltage setpoint: 9.8 kV Result: Test passed Temperature-rise test Requirement temperature-rise test: Increase in temperature â¤45K Result: Test passed Short-time withstand current 10 mm²: 1.2 kA Short-time withstand current 16 mm²: 1.92 kA Power-frequency withstand voltage Test voltage setpoint: 2 kV Result: Test passed |
Mechanical properties | Mechanical data Open side panel: No |
Mechanical tests | Mechanical strength Result: Test passed Test for conductor damage and slackening Rotation speed: 10rpm Revolutions: 135 Conductor cross section/weight: 0.5 mm² / 0.3 kg 10 mm² / 2 kg 16 mm² / 2.9 kg Result: Test passed |
Environmental and real-life conditions | Needle-flame test Time of exposure: 30 s Result: Test passed Ambient conditions Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24h, -60°C to +70°C) Ambient temperature (assembly): -5°C ... 70°C Ambient temperature (actuation): -5°C ... 70°C Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-1 |
Mounting | Mounting type: direct screw connection |
Description other products