PHOENIX CONTACT 2804416
PHOENIX CONTACTNot available

VAL-CP-MOSO 60-3C-FM - Type 2 surge arrester

Combination of type 2 surge protection and arrester backup fuse, with arrester monitoring, in combination with a diagnostic and status indicator and remote indication contact. Design: 4-conductor system (L1, L2, L3, PEN), mounting on 60 mm system technology (power rail system)
Product Code: 2804416
Partner cod.: 2804416
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC test classification: II
T2
EN type: T2
IEC power supply system: TN-C
TT
Type: Module for 60 mm system technology
Product type: Surge arrester
Number of positions: 3
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Nominal voltage UN: 240 VAC (230/400 V AC ... 240/415 V AC)
Indicator/remote signaling
Connection name: Remote fault indicator contact
Switching function: Changeover contact
Operating voltage: 5 VAC ... 250 VAC
125 VDC (200 mA DC)
Operating current: 5 mA AC ... 1 A AC
1 ADC (30VDC)
Connection dataPEN conductor connection
Connection method: Screw connection
Screw thread: M5
Tightening torque: 4.5 Nm
Stripping length: 16 mm
Conductor cross section flexible: 2.5 mm² ... 16 mm²
Conductor cross section rigid: 2.5 mm² ... 25 mm²
Conductor cross section AWG: 12 ... 4
Phase conductor connection
Connection method: 60 mm power rail system
Remote fault indicator contact
Connection method: Pluggable screw connection
Screw thread: M2
Tightening torque: 0.25 Nm
Stripping length: 7 mm
Conductor cross section flexible: 0.14 mm² ... 1.5 mm²
Conductor cross section rigid: 0.14 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/991179eb9229a64a9610ae6ebbe50b38/-S204x204-FJPG
Width: 54 mm
Height: 220 mm
Depth: 134 mm
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PBT, PA6, PA66
Material group: I
Housing material: PBT
PA 6
PA 6.6
Protective circuitMode of protection: L-PEN
Direction of action: 3L-PEN
Nominal voltage UN: 240/415VAC (TN-C)
240/415VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 350 VAC
Nominal discharge current In (8/20) µs: 20 kA
Maximum discharge current Imax (8/20) µs: 25 kA
Short-circuit current rating ISCCR: 25 kA
Voltage protection level Up: ≤ 2.5 kV
Residual voltage Ures: ≤ 2.1 kV (at In)
≤ 1.9 kV (at 10 kA)
≤ 1.8 kV (at 5 kA)
≤ 1.7 kV (at 3kA)
TOV behavior at UT: 415 VAC (5s / withstand mode)
440 VAC (120min / safe failure mode)
Response time tA: ≤ 25 ns
Max. backup fuse with branch wiring: not required
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 55°C
Ambient temperature (storage/transport): -40°C ... 75°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Standards and regulationsAir clearances and creepage distances
Standards/regulations: DINVDE0110-1 / IEC 60664-1 / IEC 61643-11
Standards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: 60 mm system technology (power rail)
Technical Specs
ECLASSECLASS-11.0: 27130805
ECLASS-13.0: 27171202
ETIMETIM 9.0: EC000941