Product properties | IEC test classification: II T2 EN type: T2 IEC power supply system: TN-C TT Type: Module for 60 mm system technology Product type: Surge arrester Number of positions: 3 Surge protection fault message: Optical, remote indicator contact Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) Nominal voltage UN: 240 VAC (230/400 V AC ... 240/415 V AC) Indicator/remote signaling Connection name: Remote fault indicator contact Switching function: Changeover contact Operating voltage: 5 VAC ... 250 VAC 125 VDC (200 mA DC) Operating current: 5 mA AC ... 1 A AC 1 ADC (30VDC) |
Connection data | PEN conductor connection Connection method: Screw connection Screw thread: M5 Tightening torque: 4.5 Nm Stripping length: 16 mm Conductor cross section flexible: 2.5 mm² ... 16 mm² Conductor cross section rigid: 2.5 mm² ... 25 mm² Conductor cross section AWG: 12 ... 4 Phase conductor connection Connection method: 60 mm power rail system Remote fault indicator contact Connection method: Pluggable screw connection Screw thread: M2 Tightening torque: 0.25 Nm Stripping length: 7 mm Conductor cross section flexible: 0.14 mm² ... 1.5 mm² Conductor cross section rigid: 0.14 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/991179eb9229a64a9610ae6ebbe50b38/-S204x204-FJPG Width: 54 mm Height: 220 mm Depth: 134 mm |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PBT, PA6, PA66 Material group: I Housing material: PBT PA 6 PA 6.6 |
Protective circuit | Mode of protection: L-PEN Direction of action: 3L-PEN Nominal voltage UN: 240/415VAC (TN-C) 240/415VAC (TT) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 350 VAC Nominal discharge current In (8/20) µs: 20 kA Maximum discharge current Imax (8/20) µs: 25 kA Short-circuit current rating ISCCR: 25 kA Voltage protection level Up: ⤠2.5 kV Residual voltage Ures: ⤠2.1 kV (at In) ⤠1.9 kV (at 10 kA) ⤠1.8 kV (at 5 kA) ⤠1.7 kV (at 3kA) TOV behavior at UT: 415 VAC (5s / withstand mode) 440 VAC (120min / safe failure mode) Response time tA: ⤠25 ns Max. backup fuse with branch wiring: not required |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 55°C Ambient temperature (storage/transport): -40°C ... 75°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % |
Standards and regulations | Air clearances and creepage distances Standards/regulations: DINVDE0110-1 / IEC 60664-1 / IEC 61643-11 Standards/specifications: IEC 61643-11 EN61643-11 Note: 2011 2012 |
Mounting | Mounting type: 60 mm system technology (power rail) |
ECLASS | ECLASS-11.0: 27130805 ECLASS-13.0: 27171202 |
ETIM | ETIM 9.0: EC000941 |
UNSPSC | UNSPSC 21.0: 39121600 |