Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2814715
PHOENIX CONTACTNot available

MCR-S-1-5-UI-DCI-NC - Current transducers

MCR current transducer, programmable and configurable, for measuring direct, alternating and distorted currents, input current 0...0.2 to 0...11 A, unconfigured
Product Code: 2814715
Partner cod.: 2814715
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Current transducer
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesTotal error: ≤ 1.5 % (Temperature range)
Maximum power dissipation for nominal condition: 2.2 W
Measuring category: III
Test voltage output/power supply: 500 VAC (50Hz, 60s)
Test voltage input/output: 4 kV AC (50Hz, 60s)
Test voltage input/power supply: 4 kV AC (50Hz, 60s)
Protective circuit: Surge protection; 33V suppressor diode
Step response (10-90%): 330 ms (AC)
40 ms (DC)
Temperature coefficient, typical: < 0.025 %/K
Maximum transmission error: < 0.5 % (of nominal range value under nominal conditions)
Rated insulation voltage: 300 VAC (to earth)
Supply
Supply voltage range: 20 VDC ... 30 VDC
Max. current consumption: < 40 mA (without load)
Input dataMeasurement
Number of inputs: 3
Configurable/programmable: Yes, unconfigured
Input current range: 0 A AC/DC ... 11 A AC/DC (Permitted continuous overload: 120%)
Current measuring range: 0 A AC/DC ... 1 A AC/DC
0 A AC/DC ... 5 A AC/DC
0 A AC/DC ... 10 A AC/DC
Setting range for min. input current: 0 mA AC/DC ... 200 mA AC/DC
Setting range for max. input current: 0 A AC/DC ... 11 A AC/DC
LSB: Current: 1 µA (1A)
2 µA (2A)
5 µA (5A)
10 µA (10A)
50 µA (50A)
100 µA (100A)
Overload capacity: 2 x IN (continuous)
Surge strength: 20 x IN (1 s)
Frequency measuring range: 15 Hz ... 400 Hz
Curve type: AC, DC or distorted currents
Operate threshold: 2 % (of measuring range nominal value 1/5/10 A)
Output dataSignal: Voltage/current
Configurable/programmable: Yes, unconfigured
Voltage output signal: 0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
2 V ... 10 V
-5 V ... 5 V
-10 V ... 10 V
10 V ... 0 V
10 V ... 2 V
10 V ... -10 V
5 V ... 0 V
5 V ... 1 V
5 V ... -5 V
Current output signal: 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Load/output load voltage output: > 10 kΩ
Load/output load current output: < 500 Ω
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
SignalingStatus display: Green LED
DimensionsItem dimensions
Width: 22.5 mm
Height: 99 mm
Depth: 114.5 mm
Material specificationsHousing material: Polyamide PA non-reinforced
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -20°C ... 60°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: < 2000 m
Permissible humidity (operation): 10 % ... 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
UL, USA/Canada
Identification: Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive
Noise immunity: EN 61000-6-2
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Standards and regulationsStandards/regulations: IEC 61010-2-030
MountingMounting type: DIN rail mounting
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27210123
ECLASS-12.0: 27210123
ECLASS-13.0: 27210123
ETIMETIM 9.0: EC002475
UNSPSCUNSPSC 21.0: 39121000
Description
MCR current transducer, programmable and configurable, for measuring direct, alternating and distorted currents, input current 0...0.2 to 0...11 A, unconfigured
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01560.pdf

Approvals_01561.pdf

Data_sheet_03468.pdf

Manufacturer_declaration_01044.pdf

Manufacturer_declaration_01839.pdf

Manufacturer_declaration_15108.pdf

Package_slip_01586.pdf

Product_information_00033.pdf

Product_information_00373.pdf

Technical_drawing_38628.pdf