Industrial Automation
Product properties | IEC test classification: II T2 EN type: T2 IEC power supply system: TN TT Type: DIN rail module, two-section, divisible Product type: Surge arrester Product family: VALVETRAB MS Number of positions: 1 Surge protection fault message: Optical, remote indicator contact Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) Indicator/remote signaling Connection name: Remote fault indicator contact Switching function: Changeover contact Operating voltage: 5 VAC ... 250 VAC 30 VDC Operating current: 5 mA AC ... 1 A AC 1 ADC |
Connection data | Connection method: Screw connection Fork-type cable lug Screw thread: M5 Tightening torque: 3 Nm (1.5mm² ... 16mm²) 4.5 Nm (25mm²...35mm²) Stripping length: 16 mm Conductor cross section flexible: 1.5 mm² ... 25 mm² 1.5 mm² ... 16 mm² Conductor cross section rigid: 1.5 mm² ... 35 mm² Conductor cross section AWG: 15 ... 2 Remote fault indicator contact Connection method: Plug-in/screw connection via COMBICON Screw thread: M2 Tightening torque: 0.25 Nm Stripping length: 7 mm Conductor cross section flexible: 0.14 mm² ... 1.5 mm² Conductor cross section rigid: 0.14 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/4f232daac991f04688a8f82ac0c5dbbd/-S204x204-FJPG Width: 17.6 mm Height: 96.8 mm Depth: 65.7 mm (incl. DIN rail 7.5mm) Horizontal pitch: 1 Div. |
Material specifications | Color: Copper Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA 6.6/PBT Material group: I Housing material: PA 6.6 PBT |
Protective circuit | Mode of protection: N-PE Direction of action: N-PE Nominal voltage UN: 240/415VAC (TN - only N-PE) 240/415VAC (TT - only N-PE) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 260 VAC Rated load current IL: 80 A Residual current IPE: ⤠5 µA Standby power consumption PC: ⤠1.5 mVA Nominal discharge current In (8/20) µs: 20 kA Maximum discharge current Imax (8/20) µs: 40 kA Follow current interrupt rating Ifi: 100 A Voltage protection level Up: ⤠1.5 kV Residual voltage Ures: ⤠0.4 kV (at In) ⤠0.25 kV (at 10 kA) ⤠0.15 kV (at 5 kA) ⤠0.1 kV (at 3kA) Front of wave sparkover voltage at 6 kV (1.2/50) µs: ⤠1.5 kV TOV behavior at UT: 1200 VAC (200ms / withstand mode) Response time tA: ⤠100 ns Max. backup fuse with V-type through wiring: 80 A (gG) Additional technical data Maximum continuous voltage UC: 305 VAC |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (only when all terminal points are used) Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
Approvals | UL specifications Maximum continuous operating voltage MCOV (N-G): 260 VAC Nominal discharge current In (N-G): 20 kA Mode of protection: N-G Power distribution system: Single phase Nominal frequency: 50/60 Hz Measured limiting voltage MLV (N-G): 1490 V SPD Type: 4CA UL indicator/remote signaling Operating voltage: 125 VAC AC operating current: 1 A AC UL connection data Tightening torque: 30 lbf-in. Conductor cross section AWG: 14 ... 2 |
Standards and regulations | Standards/specifications: IEC 61643-11 EN61643-11 Note: 2011 2012 |
Mounting | Mounting type: DIN rail: 35 mm |
ECLASS | ECLASS-11.0: 27130805 ECLASS-13.0: 27171202 |
ETIM | ETIM 9.0: EC000941 |
UNSPSC | UNSPSC 21.0: 39121600 |
Description other products