PHOENIX CONTACT 2861467
PHOENIX CONTACTNot available

IB IL AO 2/U/BP-PAC - Analog module

Inline, Analog output terminal, Analog outputs: 2, 0 V ... 10 V, -10 V ... 10 V, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
Product Code: 2861467
Partner cod.: 2861467
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8f49d2b498684640a945b59e148b2698/-S204x204-FJPG
Width: 12.2 mm
Height: 136.8 mm
Depth: 71.5 mm
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Utilization restriction​
CCCex note: Use in potentially explosive areas is not permitted in China.
InterfacesInline local bus
Number of interfaces: 2
Connection method: Inline data jumper
Transmission speed: 500 kbps
Transmission physics: Copper
System propertiesModule
ID code (dec.): 91
ID code (hex): 5B
Length code (hex): 02
Length code (dec): 02
Process data channel: 32 bit
Input address area: 4 Byte
Output address area: 4 Byte
Register length: 32 bit
Required parameter data: 6 Byte
Required configuration data: 5 Byte
Output dataAnalog
Output name: Analog outputs
Output description: Single-ended
Connection technology: 2-conductor
Note regarding the connection technology: shielded
Number of outputs: 2
D/A conversion time: < 100 ns
Protective circuit: Transient protection of outputs
Data formats: IB IL, IB ST
Representation of output values: 16 bits (15 bits + sign)
DAC resolution: 13 bit
Process data update: < 1 ms
Voltage output signal: 0 V ... 10 V
-10 V ... 10 V
Load/output load voltage output: > 2 kΩ
Permissible cable length: max. 500 m (The specifications refer to nominal operation after complying with installation instructions. The specifications refer to the following reference cable type: Shielded power station cable: LiYCY; 2 x 2 x 0,5mm²; VDE0812)
Product propertiesType: modular
Product type: I/O component
Product family: Inline
Scope of delivery: including Inline connector and labeling field
Diagnostics messages: Failure of or insufficient communications power UL I/O error message sent to the bus coupler
Electrical propertiesMaximum power dissipation for nominal condition: 1.8 W
Potentials
Power consumption: typ. 0.68 W (No-load)
typ. 0.85 W (Full load (RL = 2kΩ))
Potentials: Communications power (U
Supply voltage: 7.5 VDC (via voltage jumper)
Current draw: max. 40 mA
typ. 33 mA
Potentials: Supply of analog modules (U
Supply voltage: 24 VDC (via voltage jumper)
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 35 mA (Full load (RL = 2kΩ))
max. 28 mA (No-load)
typ. 25 mA (Full load (RL = 2kΩ))
typ. 18 mA (No-load)
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O: 500 VAC, 50 Hz, 1 min.
Test voltage: 7.5V supply (bus logic), 24V supply UANA / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: Inline connector
Conductor connection
Connection method: Spring-cage connection
Conductor cross section rigid: 0.08 mm² ... 1.5 mm²
Conductor cross section flexible: 0.08 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
Stripping length: 8 mm
Inline connector
Connection method: Spring-cage connection
Conductor cross section, rigid: 0.08 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.08 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 55°C
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -25°C ... 85°C
Permissible humidity (operation): 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 10 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
MountingMounting type: DIN rail mounting
Technical Specs
ECLASSECLASS-11.0: 27242601
ECLASS-12.0: 27242601
ECLASS-13.0: 27242601
ETIMETIM 9.0: EC001596
UNSPSCUNSPSC 21.0: 32151600
Description
Inline, Analog output terminal, Analog outputs: 2, 0 V ... 10 V, -10 V ... 10 V, connection method: 2-wire, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00102.pdf

Application_note_00104.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00156.pdf

Approvals_01165.pdf

Approvals_01166.pdf

Approvals_01174.pdf

Approvals_01216.pdf

Data_sheet_03517.pdf

Manual_00085.pdf

Manufacturer_declaration_00884.pdf

Manufacturer_declaration_01728.pdf

Manufacturer_declaration_15221.pdf

Package_slip_00193.pdf

Package_slip_01356.pdf

Package_slip_02503.pdf

Product_information_00033.pdf

Product_information_00421.pdf

Technical_drawing_38906.pdf

Various_00038.pdf