Industrial Automation
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/61847ea072ac2f4a94bf2299909bd975/-S204x204-FJPG Width: 48.8 mm Height: 140.5 mm Depth: 71.5 mm |
Interfaces | Inline local bus Connection method: Inline data jumper Transmission speed: 500 kbps Transmission physics: Copper Transmission length: 116.1 mm |
System properties | Module ID code (dec.): 191 ID code (hex): BF Length code (hex): 02 Length code (dec): 02 Process data channel: 32 bit Input address area: 4 Byte Output address area: 4 Byte Register length: 4 Byte Required parameter data: 6 Byte Required configuration data: 5 Byte |
Input data | Absolute encoder Number of inputs: 1 Adjustable resolution: 26 bit (maximum) Transmission frequency: 400 kHz Digital Number of inputs: 3 Input voltage: 24 VDC Input voltage range "0" signal: -30 VDC ... 5 VDC Input voltage range "1" signal: 13 VDC ... 30 VDC Connection method: Inline connector Connection technology: 3-conductor |
Output data | Digital Number of outputs: 4 Output voltage: 24 VDC Protective circuit: electronic short-circuit / overload protection |
Product properties | Type: modular Product type: I/O component Product family: Inline Number of plugs: 1 |
Electrical properties | Test section: 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 VAC 50 Hz 1 min. 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 VAC 50 Hz 1 min. 7.5 V supply (bus logics)/24 V supply (I/O) 500 VAC 50 Hz 1 min. 7.5V supply (bus logic)/functional ground of the encoder supply 500 VAC 50 Hz 1 min. 24V supply (I/O) / functional ground 500 VAC 50 Hz 1 min. 24V supply (I/O)/functional ground of the encoder supply 500 VAC 50 Hz 1 min. Functional ground of the encoder supply/functional ground 500 VAC 50 Hz 1 min. Supply Drawing encoder supply voltage: Main circuit UM Encoder supply voltage: 5 VDC 24 VDC Encoder supply current: 500 mA I/O voltage: 24 VDC I/O voltage range: 19.2 VDC ... 30 VDC Residual ripple: ± 1.2 V Max. current consumption: 60 mA Potentials: Communications power (U Supply voltage: 7.5 VDC (via voltage jumper) Current draw: max. 60 mA Potentials: Main circuit supply (U Supply voltage: 24 VDC (via voltage jumper) Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 1 A Potentials: Segment circuit supply (U Supply voltage: 24 VDC (via voltage jumper) Current draw: max. 2 A |
Connection data | Connection technology Connection name: Inline connector Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.08 mm² ... 1.5 mm² Conductor cross section flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.08 mm² ... 1.5 mm² Conductor cross section, flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 55°C Ambient temperature (storage/transport): -25°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (DIN EN 61131-2) Permissible humidity (storage/transport): 10 % ... 95 % (DIN EN 61131-2) Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27242605 ECLASS-12.0: 27242605 ECLASS-13.0: 27242605 |
ETIM | ETIM 9.0: EC001601 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products