Industrial Automation
MINI MCR-SL-NAM-2RNO - Switching amplifier
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Isolating switch transf. Product family: MINI Analog No. of channels: 1 Configuration: DIP switches Insulation characteristics Overvoltage category: II Pollution degree: 2 |
System properties | Functionality Configuration: DIP switches |
Electrical properties | No. of channels: 1 Rated insulation voltage: 150 VAC (Input/relay outputs (reinforced insulation)) 150 VAC (Supply/relay outputs (reinforced insulation)) 150 VAC (Relay output 1/relay output 2 (reinforced insulation)) 30 VAC (Input/supply) 50 VDC (Input/supply) Electrical isolation: Reinforced insulation in accordance with EN61010-1 Electrical isolation between input and output: yes Test voltage, input/output/supply: 1.5 kV AC (50Hz, 60s) Supply Designation: Supply Nominal supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715) Max. current consumption: < 25 mA Power consumption: < 600 mW |
Input data | Signal: NAMUR Number of inputs: 1 Available input sources: NAMUR proximity sensors (IEC/EN60947-5-6) Floating switch contacts Switch contacts with resistance circuit Switching threshold "0" signal current: < 1.2 mA (blocking) Switching threshold "1" signal, current: > 2.1 mA (conductive) Line fault detection: > 6 mA (Short circuit) < 0.35 mA (Line break) Activated /deactivated via DIP switch Non-load voltage: 8.2 VDC ±10% |
Output data | Switching: Relay Output description: Output 1: Signal output; Output 2: Fault signaling output or signal duplicator, can be set via DIP switches Contact switching type: 2 N/O contacts Contact material: Hard gold plated AgNi Maximum switching voltage: 250 VAC 125 VDC 150 VAC (UL) 125 VDC (UL) Maximum inrush current: 2 A Min. switching current: 1 mA (5 V DC) Typical response time: 15 ms Typical turn-off time: 20 ms Switching frequency: 0.5 Hz (240VAC / 30VDC / 2A) 10 Hz (without load) Signal Number of outputs: 2 |
Connection data | Connection method: Screw connection Stripping length: 12 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 26 ... 12 |
Signaling | Status display: Red LED (error messages) Yellow LED (relay status messages) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8450693c9d67004aa7841c306225c8da/-S204x204-FJPG Width: 6.2 mm Height: 93.1 mm Depth: 101.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 65°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant UL, USA/Canada Identification: UL508 Recognized Class I, Div. 2, Groups A, B, C, D T4 Shipbuilding approval Certificate: DNV GL TAA000020N DNV GL data Temperature: B Humidity: B Vibration: B EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Evaluation criterion: A Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Evaluation criterion: A Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Evaluation criterion: A |
Standards and regulations | Electrical isolation: Reinforced insulation in accordance with EN61010-1 |
Mounting | Mounting type: DIN rail mounting Mounting position: any |
ECLASS | ECLASS-11.0: 27210121 ECLASS-12.0: 27210121 ECLASS-13.0: 27210121 |
ETIM | ETIM 9.0: EC001485 |
UNSPSC | UNSPSC 21.0: 39121000 |