MINI MCR-SL-F-UI-NC - Frequency measuring transducer

The configurable frequency transducer is suitable for the connection of NAMUR proximity sensors as well as for sensors with NPN and PNP outputs. Configurable via DIP switch and teach-in wheel. Screw connection, standard configuration.
Product Code: 2902832
Partner cod.: 2902832
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Product propertiesProduct type: Frequency value transformer
Product family: MINI Analog
No. of channels: 1
Operating elements: Press/slide button
Configuration: DIP switches
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
System propertiesFunctionality
Configuration: DIP switches
Electrical propertiesNo. of channels: 1
Electrical isolation: 3-way isolation
Electrical isolation between input and output: yes
Protective circuit: Transient protection
Step response (0–99%): < 35 ms (At f > 500 Hz)
Maximum temperature coefficient: 0.01 %/K
Transmission error in the set measuring range: 0.1%
Electrical isolation Input/output/power supply
Rated insulation voltage: 50 V AC/DC
Test voltage: 1.5 kV AC (50Hz, 60s)
Insulation: Basic insulation in accordance with IEC/EN61010
Supply
Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715)
Typical current consumption: < 28 mA (at IOUT = 20 mA, 24 V DC, load 500 Ω)
Power consumption: < 800 mW (at IOUT = 20 mA, 9.6 V DC, load 500 Ω)
Input dataMeasurement: Frequency
Configurable/programmable: Yes
Available input sources: NPN/PNP transistor outputs
NAMUR initiators
Floating relay contact (dry contact)
Max. voltage input signal: 30 V (incl. DC voltage)
Frequency measuring range: 0.002 Hz ... 20 kHz (DIP switch)
0.002 Hz ... 80 kHz (Teach-in wheel)
Signal
Number of inputs: 1
Input signal: Frequency
Output dataSignal: Voltage/current
Number of outputs: 1
Configurable/programmable: Yes
Voltage output signal: 0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
10 V ... 0 V
Max. voltage output signal:  12.3 V
Current output signal: 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. current output signal: 24.6 mA
Load/output load voltage output: ≥ 10 kΩ
Load/output load current output: 500 Ω (20mA)
Ripple: < 20 mVPP
< 20 mVPP (500 Ω)
Connection dataConnection method: Screw connection
Stripping length: 12 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 26 ... 12
SignalingStatus display: LED red
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8450693c9d67004aa7841c306225c8da/-S204x204-FJPG
Width: 6.2 mm
Height: 93.1 mm
Depth: 101.2 mm
Material specificationsFire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2
Housing material: PBT
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -20°C ... 65°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
UL, USA/Canada
Identification: UL508 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
Shipbuilding approval
Certificate: DNV GL TAA00002R0
DNV GL data
Temperature: B
Humidity: B
Vibration: B
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Comments: Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation: Electromagnetic RF field
Standards/regulations: EN61000-4-3
Typical deviation from the measuring range final value: 0.1 %
Fast transients (burst)
Designation: Fast transients (burst)
Standards/regulations: EN61000-4-4
Typical deviation from the measuring range final value: 2 %
Surge current load (surge)
Standards/regulations: EN61000-4-5
Conducted interference
Designation: Conducted interferences
Standards/regulations: EN61000-4-6
Typical deviation from the measuring range final value: 0.3 %
Standards and regulationsElectrical isolation: 3-way isolation
MountingMounting type: DIN rail mounting
Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail.
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27210128
ECLASS-12.0: 27210128
ECLASS-13.0: 27210128
ETIMETIM 9.0: EC002918
UNSPSCUNSPSC 21.0: 39121000
Description
The configurable frequency transducer is suitable for the connection of NAMUR proximity sensors as well as for sensors with NPN and PNP outputs. Configurable via DIP switch and teach-in wheel. Screw connection, standard configuration.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_01328.pdf

Approvals_01329.pdf

Approvals_01435.pdf

Data_sheet_03776.pdf

Manual_00026.pdf

Manufacturer_declaration_02355.pdf

Manufacturer_declaration_04759.pdf

Manufacturer_declaration_15734.pdf

Package_slip_01650.pdf

Product_information_00033.pdf

Product_information_00570.pdf

Technical_drawing_39659.pdf