Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Frequency value transformer Product family: MINI Analog No. of channels: 1 Operating elements: Press/slide button Configuration: DIP switches Insulation characteristics Overvoltage category: II Pollution degree: 2 |
System properties | Functionality Configuration: DIP switches |
Electrical properties | No. of channels: 1 Electrical isolation: 3-way isolation Electrical isolation between input and output: yes Protective circuit: Transient protection Step response (0â99%): < 35 ms (At f > 500 Hz) Maximum temperature coefficient: 0.01 %/K Transmission error in the set measuring range: 0.1% Electrical isolation Input/output/power supply Rated insulation voltage: 50 V AC/DC Test voltage: 1.5 kV AC (50Hz, 60s) Insulation: Basic insulation in accordance with IEC/EN61010 Supply Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715) Typical current consumption: < 28 mA (at IOUT = 20 mA, 24 V DC, load 500 é) Power consumption: < 800 mW (at IOUT = 20 mA, 9.6 V DC, load 500 é) |
Input data | Measurement: Frequency Configurable/programmable: Yes Available input sources: NPN/PNP transistor outputs NAMUR initiators Floating relay contact (dry contact) Max. voltage input signal: 30 V (incl. DC voltage) Frequency measuring range: 0.002 Hz ... 20 kHz (DIP switch) 0.002 Hz ... 80 kHz (Teach-in wheel) Signal Number of inputs: 1 Input signal: Frequency |
Output data | Signal: Voltage/current Number of outputs: 1 Configurable/programmable: Yes Voltage output signal: 0 V ... 5 V 1 V ... 5 V 0 V ... 10 V 10 V ... 0 V Max. voltage output signal: ï» 12.3 V Current output signal: 0 mA ... 20 mA 4 mA ... 20 mA 20 mA ... 0 mA 20 mA ... 4 mA Max. current output signal: 24.6 mA Load/output load voltage output: ⥠10 ké Load/output load current output: 500 é (20mA) Ripple: < 20 mVPP < 20 mVPP (500 é) |
Connection data | Connection method: Screw connection Stripping length: 12 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 26 ... 12 |
Signaling | Status display: LED red |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8450693c9d67004aa7841c306225c8da/-S204x204-FJPG Width: 6.2 mm Height: 93.1 mm Depth: 101.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 65°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant UL, USA/Canada Identification: UL508 Listed Class I, Div. 2, Groups A, B, C, D T4 Class I, Zone 2, Group IIC Shipbuilding approval Certificate: DNV GL TAA00002R0 DNV GL data Temperature: B Humidity: B Vibration: B EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Comments: Safety measures must be taken to prevent electrostatic discharge. Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Typical deviation from the measuring range final value: 0.1 % Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Typical deviation from the measuring range final value: 2 % Surge current load (surge) Standards/regulations: EN61000-4-5 Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Typical deviation from the measuring range final value: 0.3 % |
Standards and regulations | Electrical isolation: 3-way isolation |
Mounting | Mounting type: DIN rail mounting Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail. Mounting position: any |