Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Temperature transmitter Product family: MINI Analog Configuration: DIP switches Insulation characteristics Overvoltage category: II Pollution degree: 2 |
Electrical properties | Maximum power dissipation for nominal condition: 235.5 mW Protective circuit: Transient protection Step response (0â99%): < 200 ms Maximum temperature coefficient: < 0.02 %/K Transmission error in the set measuring range: ((50 K / à Temp)+ 0.05)% Transmission error in the full measuring range: â¤0.25% Electrical isolation Input/output/power supply Rated insulation voltage: 50 V AC/DC Test voltage: 1.5 kV AC (50Hz, 60s) Insulation: Basic insulation in accordance with IEC/EN61010 Supply Nominal supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715) Max. current consumption: < 21 mA (at 24 V DC) Power consumption: < 500 mW |
Input data | Signal Number of inputs: 1 Measurement Sensor types (RTD) that can be used: Pt 100 (IEC 60751/EN 60751) Temperature measuring range: min. 50 K Sensor type:: -50°C ... 200°C (configurable) Sensor input current: 1 mA (constant) Max. permissible overall conductor resistance: 10 é (Per cable) Connection technology: 2-, 3-, 4-conductor |
Output data | Signal: Voltage/current Number of outputs: 1 Configurable/programmable: Yes Voltage output signal: 0 V ... 5 V 1 V ... 5 V 0 V ... 10 V 10 V ... 0 V Max. voltage output signal: ï» 12.5 V Non-load voltage: ï» 12.5 V Current output signal: 0 mA ... 20 mA 4 mA ... 20 mA 20 mA ... 0 mA 20 mA ... 4 mA Max. current output signal: 23 mA Short-circuit current: ï» 10 mA Load/output load voltage output: > 10 ké Load/output load current output: < 500 é (at 20 mA) Ripple: < 20 mVPP (at 500 é) < 20 mVPP (at 10 ké) |
Connection data | Connection method: Screw connection Stripping length: 12 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 26 ... 12 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8450693c9d67004aa7841c306225c8da/-S204x204-FJPG Width: 6.2 mm Height: 93.1 mm Depth: 101.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 65°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant UL, USA/Canada Identification: UL508 Recognized Class I, Div. 2, Groups A, B, C, D T5 Shipbuilding approval Certificate: DNV GL TAA00002R0 DNV GL data Temperature: B Humidity: B Vibration: B EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Comments: Safety measures must be taken to prevent electrostatic discharge. Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Typical deviation from the measuring range final value: 10 % Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Typical deviation from the measuring range final value: 10 % Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Comments: Criterion B Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Typical deviation from the measuring range final value: 10 % |
Mounting | Mounting type: DIN rail mounting Mounting position: any |
ECLASS | ECLASS-11.0: 27210129 ECLASS-12.0: 27210129 ECLASS-13.0: 27210129 |
ETIM | ETIM 9.0: EC002919 |
UNSPSC | UNSPSC 21.0: 41112100 |
Description other products