Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2865599
PHOENIX CONTACT 2865599
PHOENIX CONTACTNot available

MACX MCR-S-MUX - HART multiplexer

HART Multiplexer for online configuration and diagnostics of HART-compatible field devices, as well as for continuous documentation of process variables and states with a PC or management system for mounting on NS 35/7.5 or NS 32
Product Code: 2865599
Partner cod.: 2865599
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Multiplexer
Electrical propertiesError monitoring: Processor error: The "PWR" LED flashes; error in the HART communication: the "ERR" LED flashes
Electrical isolation HART signal/RS-485
Electrical isolation: 350 VAC
Electrical isolation HART signals/HART signals
Electrical isolation: 100 VDC (capacitive)
Electrical isolation Supply/HART signal/RS-485
Electrical isolation: 300 VAC
Supply
Supply voltage: 24 VDC
Supply voltage range: 18 V ... 31.2 V
Typical current consumption: 55 mA
Nominal power consumption: 1.35 W
Undervoltage monitoring: Yes (no faulty devices / output states)
InterfacesHART
Designation: HART FSK
Channels: 16 or 32; adjustable using a switch
Connection method: Flat-ribbon cable, 14-pos. (inclusive)
HART specification: HART Field Communication Protocol Rev. 6.0 (downward compatible up to Rev 4.0); FSK Physical Layer Specification (Rev. 8.1)
Data transmission display: Two yellow "Tx" and "Rx" "HART" LEDs
Display error: Red "ERR" LED (flashes in case of an error in the HART bus)
RS-485
Number: 1
Connection method: D-SUB-9 female connector
Designation: RS-485
Data flow control/protocols: Compatible with OPC HART server, PDM, PRM, and FDT/DTM
Number of HART multiplexers per bus segment: Max 31
Address setting: 0...127; using a rotary switch at the front
Serial transmission speed: 9600 / 19200 / 38400 / 57600 [bps]; via rotary switch at the front
Transmission length: ≤ 1200 m
Display: Two yellow "Tx" and "Rx" "RS-485" LEDs
SignalingOperating voltage display: Green "PWR" LED
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/cb16f98657900e4594f78d7b41802675/-S204x204-FJPG
Width: 35.2 mm
Height: 108.8 mm
Depth: 114.5 mm
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -20°C ... 60°C (aligned)
-20°C ... 70°C (Stand-alone device)
Ambient temperature (storage/transport): -40°C ... 80°C
Max. permissible relative humidity (operation): ≤ 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
MountingMounting type: DIN rail mounting
Technical Specs
ECLASSECLASS-11.0: 27242608
ECLASS-12.0: 27242608
ECLASS-13.0: 27242608
ETIMETIM 9.0: EC001604
UNSPSCUNSPSC 21.0: 32151600
Description
HART Multiplexer for online configuration and diagnostics of HART-compatible field devices, as well as for continuous documentation of process variables and states with a PC or management system for mounting on NS 35/7.5 or NS 32
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00115.pdf

Data_sheet_03606.pdf

Manufacturer_declaration_03587.pdf

Manufacturer_declaration_04695.pdf

Manufacturer_declaration_15290.pdf

Package_slip_01549.pdf

Technical_drawing_39010.pdf