PHOENIX CONTACT 2866284
PHOENIX CONTACT 2866284
PHOENIX CONTACTNot available

MINI-PS- 12- 24DC/24DC/1 - DC/DC converter

Please use the following items in new systems: 1066703, 1066716, 1066718, 1066714.
Primary-switched MINI DC/DC converter for DIN rail mounting, input: 12-24VDC, output: 24VDC/1A
Product Code: 2866284
Partner cod.: 2866284
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Input dataDC operation
Nominal input voltage range: 12 VDC ... 24 VDC
Input voltage range: 10 VDC ... 32 VDC
Wide-range input: yes
Input voltage range DC: 10 VDC ... 32 VDC
Voltage type of supply voltage: DC
Inrush current: < 15 A (typical)
Inrush current integral (I2t): 1.8 A2s
Frequency range DC: 0 Hz
Mains buffering time: typ. 3 ms (12VDC)
typ. 20 ms (24VDC)
Current consumption: 2.6 A (12VDC)
1.3 A (24VDC)
Typical response time: < 0.5 s
Input fuse: 6.3 A (slow-blow, internal)
Output dataEfficiency: > 83 % (at 24 V DC and nominal values)
Output characteristic: U/I
Nominal output voltage: 24 VDC ±1%
Setting range of the output voltage (USet): 22.5 VDC ... 28.5 VDC (> 24 VDC, constant capacity restricted)
Nominal output current (IN): 1 A (-25°C...60°C)
Derating: 60°C ... 70°C (2.5%/K)
Residual ripple: < 30 mVPP (20MHz)
Output power: 24 W
Peak switching voltages nominal load: < 100 mVPP (20MHz)
Maximum no-load power dissipation: < 1.2 W
Power loss nominal load max.: < 5 W
Connection in parallel: yes, for assembling redundant systems and increasing efficiency
Connection in series: yes
Signal: DC OK active
Output description: UOUT > 21.5 V: High signal
Maximum switching voltage: ≤ 24 VDC
Output voltage: + 24 V (Signal)
Continuous load current: ≤ 20 mA
Connection dataInput
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 7 mm
Screw thread: M3
Output
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 7 mm
Screw thread: M3
Signal
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
SignalingTypes of signaling: LED
Active switching output
Operating voltage display: Green LED
Signal output: DC OK active
Status display: "DC OK" LED green
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 1.5 kV (type test)
1 kV (routine test)
Product propertiesProduct type: DC/DC converters
MTBF (IEC 61709, SN 29500): > 2569000 h (40°C)
Insulation characteristics
Protection class: III
DimensionsWidth: 22.5 mm
Height: 99 mm
Depth: 107 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm (≤ 70°C)
Installation distance top/bottom: 50 mm / 50 mm (≤ 70°C)
MountingAssembly instructions: alignable: horizontally 0mm, vertically 50mm
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Plastic
Type of housing: Polyamide PA, color: green
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Standards and regulationsRail applications: EN50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV)
Standard - Electrical safety: EN60950-1/VDE0805 (SELV)
Standard - Safe isolation: DINVDE0100-410
DINVDE0106-101
ApprovalsShipbuilding approval: DNVGL(EMCA)
UL approvals: UL/C-UL listed UL508
UL/C-UL Recognized UL60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Noise emission: EN 55011 (EN 55022)
Electrostatic discharge
Standards/regulations: EN61000-4-2
Housing: > Level 3
Electrostatic discharge​
Contact discharge: 8 kV (Contact discharge)
Discharge in air: 8 kV (Air discharge)
Comments: Criterion B
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 3 GHz
Test field strength: 10 V/m
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (level 4 - asymmetrical: conductor to ground)
Output: 2 kV (level 3 - asymmetrical: conductor to ground)
Signal: 1 kV
Comments: Level 2 - asymmetrical cable to ground
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
Input/Output: Level 3
Frequency range: 0.15 MHz ... 80 MHz (10V)
Voltage dips
Standards/regulations: EN61000-4-11
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Technical Specs
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_01302.pdf

Approvals_01887.pdf

Data_sheet_03630.pdf

Manual_00213.pdf

Manufacturer_declaration_00601.pdf

Manufacturer_declaration_03029.pdf

Manufacturer_declaration_05493.pdf

Manufacturer_declaration_15305.pdf

Package_slip_01684.pdf

Product_information_00033.pdf

Product_information_00475.pdf

Technical_drawing_39036.pdf

Various_00006.pdf