TRIO-PS/1AC/12DC/10 - Power supply unit


Input data | Nominal input voltage range: 100 VÃAC ... 240 VÃAC Input voltage range: 85 VÃAC ... 264 VÃAC (derating < 90 V AC: 2.5 % per Kelvin) Derating: < 90 VÃAC (2.5Ã%/V) Input voltage range AC: 85 VÃAC ... 264 VÃAC (derating < 90 V AC: 2.5 % per Kelvin) Electric strength, max.: 300 VÃAC Voltage type of supply voltage: AC Inrush current: < 15 A Inrush current integral (I2t): < 1.1 A2s AC frequency range: 45 Hz ... 65 Hz Mains buffering time: > 20 ms (120ÃVÃAC) > 86 ms (230 V AC) Current consumption: 1.7 A (120ÃVÃAC) 0.9 A (230 V AC) Nominal power consumption: 218.7 VA Protective circuit: Transient surge protection; Varistor Power factor (cos phi): 0.63 Typical response time: < 1 s Permissible backup fuse: B6 B10 B16 Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K) Discharge current to PE: < 3.5 mA |
Output data | Efficiency: > 86 % (for 230 V AC and nominal values) Output characteristic: U/I Nominal output voltage: 12 VÃDC ñ1Ã% Setting range of the output voltage (USet): 10 VÃDC ... 18 VÃDC (> 12 VÃDC, constant capacity restricted) Nominal output current (IN): 10 A (-25ðCÃ...Ã55ðC) Derating: 55°C ... 70°C (2.5%/K) Feedback voltage resistance: 25 VÃDC Protection against overvoltage at the output (OVP): < 25 VÃDC Max. capacitive load: unlimited Active current limitation: Approx. 12 A (in the event of a short-circuit) Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 2 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ñ10 %) Residual ripple: < 20 mVPP Output power: 120 W Peak switching voltages nominal load: < 70 mVPP Maximum no-load power dissipation: 1.1 W Power loss nominal load max.: 18 W Rise time: < 2 ms (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes |
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 Stripping length: 9 mm Screw thread: M2,5 Tightening torque, min: 0.4 Nm Tightening torque max: 0.5 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 Stripping length: 9 mm Screw thread: M2,5 Tightening torque, min: 0.4 Nm Tightening torque max: 0.5 Nm |
Signaling | Types of signaling: LED Operating voltage display: Green LED Signal output Status display: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: LED flashing |
Electrical properties | Insulation voltage input/output: 4 kV AC (type test) 2 kV AC (routine test) Insulation voltage output / PE: 500 VÃDC (type test) Insulation voltage input / PE: 2 kV AC (type test) 2 kV AC (routine test) |
Product properties | Product type: Power supply Product family: TRIO POWER MTBF (IEC 61709, SN 29500): > 1871000 h (40ðC) Insulation characteristics Protection class: I (with PE connection) Overvoltage category: III Degree of pollution: 2 |
Dimensions | Width: 40 mm Height: 130 mm Depth: 115 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 50 mm / 50 mm |
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: horizontally 0Ãmm, vertically 50Ãmm Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No |
Material specifications | Housing material: Metal Type of housing: Steel sheet, zinc-plated Side element version: Aluminum |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (> 55° C derating : 2.5%/K) Ambient temperature (storage/transport): -40°C ... 85°C Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 15g in all directions in acc. with IEC 60068-2-27 Vibration (operation): < 15 Hz, amplitude ñ2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and regulations | Rail applications: ENÃ50121-4 Standard ââ¬Ã¢ Electronic equipment for use in electrical power installations and their assembly into electrical power installations: ENÃ50178/VDEÃ0160 (PELV) Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard - Electrical safety: ENÃ60950-1/VDEÃ0805 (SELV) ENÃ61558-2-17 Standard ââ¬Ã¢ Protection against shock currents, basic requirements for protective separation in electrical equipment: ENÃ50178 Standard ââ¬Ã¢ Safety extra-low voltage: ENÃ60950-1 (SELV) ENÃ60204 (PELV) Standard - Safe isolation: DINÃVDEÃ0100-410 |
Approvals | UL approvals: UL/C-UL listed ULÃ508 UL/C-UL Recognized ULÃ60950-1 Conformity/Approvals SIL in accordance with IEC 61508: 0 |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 6 kV (Test Level 3) Discharge in air: 8 kV (Test Level 3) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 3 GHz Test field strength: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 4 kV (Test Level 4 - asymmetrical) Signal: 2 kV (Test Level 3 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 2 kV (Test Level 3 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: ENÃ61000-4-11 Emitted interference Standards/regulations: ENÃ61000-6-3 Radio interference voltage in acc. with EN 55011: ENÃ55011 (ENÃ55022) ClassÃB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential |