Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2866734
PHOENIX CONTACT 2866734
PHOENIX CONTACTNot available

QUINT-PS/3AC/24DC/ 5 - Power supply unit

Primary-switched power supply unit QUINT POWER, Pluggable screw connection, SFB Technology (Selective Fuse Breaking), input:3-phase, output: 24 VDC / 5 A
Product Code: 2866734
Partner cod.: 2866734
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
Input dataAC operation
Nominal input voltage range: 3x 400 VÂAC ... 500 VÂAC
Input voltage range: 3x 320 VÂAC ... 575 VÂAC
2x 360 VÂAC ... 575 VÂAC
450 VÂDC ... 800 VÂDC
Voltage type of supply voltage: AC/DC
Inrush current: < 15 A (typical)
Inrush current integral (I2t): < 1 A2s
AC frequency range: 45 Hz ... 65 Hz
Frequency range DC: 0 Hz
Mains buffering time: > 20 ms (400ÂVÂAC)
> 30 ms (500 VÂAC)
Current consumption: 3x 0.8 A (400ÂVÂAC)
3x 0.7 A (500 VÂAC)
0.2 A (600 VÂDC)
Nominal power consumption: 268 VA
Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi): 0.5
Typical response time: < 0.06 s
Permissible backup fuse: B6 B10 B16 AC:
Permissible DC backup fuse: DC: Connect a suitable fuse upstream
Recommended breaker for input protection: 6 A ... 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: > 89 % (at 400 V AC and nominal values)
Output characteristic: U/I
Nominal output voltage: 24 VÂDC ±1Â%
Setting range of the output voltage (USet): 18 VÂDC ... 29.5 VÂDC (> 24 VÂDC, constant capacity restricted)
Nominal output current (IN): 5 A (-25°CÂ...Â60°C, UOUT =Â24ÂVÂDC)
POWER BOOST (IBoost): 7.5 A (-25°CÂ...Â40°C permanent, UOUT = 24ÂVÂDC )
Selective Fuse Breaking (ISFB): 30 A (12Âms)
Magnetic circuit breaker tripping: B2 / B4 / C2
Derating: 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: max. 35 VÂDC
Protection against overvoltage at the output (OVP): < 35 VÂDC
Residual ripple: < 20 mVPP (with nominal values)
Output power: 120 W
Peak switching voltages nominal load: < 20 mVPP (at nominal values, 20 MHz)
Maximum no-load power dissipation: 4 W
Power loss nominal load max.: 14 W
Rise time: < 0.04 s (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal: DC OK active
Output description: UOUT > 0.9 x UN: High signal
Switching voltage range: 18 VÂDC ... 24 VÂDC
Maximum inrush current: ≤ 20 mA (short-circuit-proof)
Continuous load current: ≤ 20 mA
Signal: DC OK floating
Output description: Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage: 30 V AC/DC
24 VÂDC
Maximum inrush current: 0.5 A
1 A
Continuous load current: ≤ 1 A
Signal: POWER BOOST, active
Output description: IOUT < IN: High signal
Switching voltage range: 18 VÂDC ... 24 VÂDC
Output voltage: + 24 VÂDC
Maximum inrush current: ≤ 20 mA (short-circuit-proof)
Continuous load current: ≤ 20 mA
Connection dataInput
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 20
Conductor cross section AWG max.: 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 20
Conductor cross section AWG max.: 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 20
Conductor cross section AWG max.: 12
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
SignalingTypes of signaling: LED
Active switching output
Relay contact
Operating voltage display: Green LED
Signal output: DC OK active
Status display: UOUT > 0.9 x UN: "DC OK" LED green
Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED
Signal output: DC OK floating
Status display: UOUT > 0.9 x UN: "DC OK" LED green
Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED
Signal output: POWER BOOST, active
Status display: IOUT > IN: LED "BOOST" yellow
Electrical propertiesNumber of phases: 3.00
Insulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE: 500 VÂDC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 1290000 h (25°C)
> 680000 h (40°C)
> 290000 h (60°C)
Insulation characteristics
Protection class: I
Degree of pollution: 2
DimensionsWidth: 40 mm
Height: 130 mm
Depth: 125 mm
Alternative assembly
Width: 122 mm
Height: 130 mm
Depth: 43 mm
MountingAssembly instructions: alignable: PN ≥50%, 5Âmm horizontally, 15Âmm next to active components, 50Âmm vertically
alignable: PN <50%, 0Âmm horizontally, 40Âmm vertically top, 20 mm vertically bottom
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Metal
Hood version: Galvanized sheet steel, free from chrome (VI)
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>Â60°C Derating: 2,5Â%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: 5000 m
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsRail applications: ENÂ50121-4
ENÂ50121-3-2
Standard âۉ€œ Limitation of mains harmonic currents: ENÂ61000-3-2
Standard - Electrical safety: IEC 61010-2-201Â(SELV)
Standard - Equipment safety: GS (tested safety)
Standard - Approval for medical use: IEC 60601-1, 2ÂxÂMOOP
Standard âۉ€œ Protection against shock currents, basic requirements for protective separation in electrical equipment: ENÂ50178
Standard âۉ€œ Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Standard - surge resistance: VDEÂ0160 (curve W2)
Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMI F47-0706 Compliance Certificate
Overvoltage category
EN 62477-1: III
ApprovalsCSA: CAN/CSA-C22.2 No.Â60950-1-07
CSA-C22.2 No.Â107.1-01
Shipbuilding approval: DNVÂGLÂ(EMCÂA), ABS, LR, RINA, NK, BV
UL approvals: UL Listed ULÂ508
UL/C-UL Recognized ULÂ60950-1 (3-wire + PE, star net)
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: ENÂ61000-6-3
ENÂ61000-6-4
EMC requirements for noise immunity: ENÂ61000-6-1
ENÂ61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations: ENÂ61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: ENÂ61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: ENÂ61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: ENÂ61000-4-5
Input: 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: ENÂ61000-4-6
Conducted interferenceâۉ€¹
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Emitted interference
Standards/regulations: ENÂ61000-6-3
Radio interference voltage in acc. with EN 55011: ENÂ55011 (ENÂ55022) ClassÂB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00054.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00165.pdf

Approvals_00177.pdf

Approvals_00179.pdf

Approvals_00182.pdf

Approvals_00184.pdf

Approvals_00249.pdf

Approvals_01302.pdf

Data_sheet_03657.pdf

Manufacturer_declaration_03006.pdf

Manufacturer_declaration_04724.pdf

Manufacturer_declaration_05497.pdf

Manufacturer_declaration_15336.pdf

Package_slip_02083.pdf

Package_slip_02091.pdf

Product_information_00033.pdf

Product_information_00152.pdf

Product_information_00481.pdf

Technical_drawing_39067.pdf

Various_00006.pdf

Various_00080.pdf